Plan Review Details - Permit 20121355
Plan Review Stops For Permit 20121355
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By cpuell Date 2021-03-24 Time 14:08 Rev Time 0.00
Received By cpuell Date 2021-03-24 Time 14:08 Sent To  
Notes
2021-03-24 14:09:34SUITE 304B HAS BEEN CHANGED TO 305, PLEASE EMAIL
 [email protected] TO CONFIRM ADDRESS CHANGE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-01-16 Cont ID  
Sent By jwitmer Date 2021-01-16 Time 11:37 Rev Time 0.00
Received By jwitmer Date 2021-01-16 Time 11:36 Sent To  
Notes
2021-01-16 11:37:06TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-01-16 Cont ID  
Sent By jwitmer Date 2021-01-16 Time 11:57 Rev Time  
Received By jwitmer Date 2021-01-16 Time 11:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 10:23 Rev Time 0.00
Received By equinone Date 2021-01-25 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By pleduc Date 2021-01-15 Time   Rev Time 0.00
Received By pleduc Date 2021-01-15 Time 15:27 Sent To  
Notes
2021-01-15 15:27:54THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE DEPARTMENT
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-25 Cont ID  
Sent By equinone Date 2021-01-25 Time 10:23 Rev Time 0.00
Received By equinone Date 2021-01-13 Time 08:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By medwards Date 2021-01-15 Time 15:01 Rev Time 0.00
Received By medwards Date 2021-01-15 Time 15:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By ccole Date 2021-01-22 Time 17:18 Rev Time 0.00
Received By ccole Date 2021-01-22 Time 16:27 Sent To  
Notes
2021-01-22 17:18:281ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20121355
 1/22/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL TO SEAL
 THE ANNULAR SPACE AROUND THE NEW SINK DRAIN PIPING
 PENETRATIONS- SECTION 315.1 FBC P AND SECTION 714.4.1.2
 FBC B. PLEASE CLARIFY IF THE NEW SINK DRAIN
 PENETRATIONS WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS- SECTION 107.2.1 WPB.
  
 2) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE THAT
 INCLUDES THE MAKES, MODELS, DIMENSIONS AND LISTING
 NUMBERS OF THE NEW SINKS- SECTIONS 418 & 424 FBC P. THE
 SCHEDULE ON THE PLAN INDICATES A JANITOR SINK WHICH
 NEEDS TO BE IDENTIFIED ON THE PLAN. IT IS NOT CLEAR
 WHAT THE REST OF THE SINKS IN THE TREATMENT ROOMS ARE
 TO BE USED FOR BECAUSE THEY ARE LISTED AS "BY OWNER".
 PLEASE CLARIFY THE USE OF THE SINKS AND NOTE THAT
 DEFERRED SUBMITTALS ARE ALLOWED, BUT ALL SPECIFICATIONS
 MUST BE REVIEWED AND APPROVED BY THE DESIGN
 PROFESSIONAL IN CHARGE- SECTION 107.3.4.1 WPB.
  
 3) P-1: CLARIFY IF THE NEW DRAIN PIPES WILL BE RUNNING
 THROUGH A PLENUM SPACE AND INDICATE THE TYPE OF PIPE
 MATERIALS TO BE INSTALLED- SECTION 303.2 FBC P AND
 107.2.1 WPB.
  
 4) P1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER INDICATING MAKE AND MODEL AND EFFICIENCY RATING
 IN COMPLIANCE WITH TABLE C404.2 FBC EC.
  
 5) P-1: PROVIDE AN INSTALLATION DETAIL OR ELEVATION
 VIEW OF THE WATER HEATER SHOWING:
  
 A) ACCESS FOR SERVICE, INSPECTION AND REPLACEMENT-
 SECTION 502.5 FBC P.
 B) WATER PIPING CONNECTIONS- SECTIONS 503 & 504 FBC P.
 C) MEANS OF CONTROLLING THERMAL EXPANSION- SECTION
 607.3 FBC P.
 D) LOCATION OF RECIRCULATION PUMP- PLEASE INCLUDE MAKE
 AND MODEL SPECIFICATION- SECTION 607.2.1 FBC P.
 E) TYPE AND SIZE OF WATER HEATER PAN- SECTION 504.7 &
 504.7.1 FBC P.
 F) TYPE AND SIZE OF DRAIN PAN PIPE, PIPE RUN, AND
 DISCHARGE LOCATION- 504.7.2 FBC P.
  
 6) SECTION 212.3 REQUIRES 5%, BUT NO FEWER THAN ONE, OF
 EACH TYPE IN EACH ACCESSIBLE ROOM TO BE IN COMPLIANCE
 WITH SECTION 606 FBC ACC. PLEASE PROVIDE THE FOLLOWING
 DETAILS PER THE FBC ACC.
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 NEW SINKS- SECTIONS 212.3 AND 606.
 B) KNEE AND TOE CLEARANCES FOR THE NEW SINKS- 606.2,
 305, & 306.
 C) HEIGHT OF THE SINK RIMS OR COUNTER SURFACES ABOVE
 THE FINISH FLOORS- 606.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By medwards Date 2021-01-15 Time 15:04 Rev Time 0.00
Received By medwards Date 2021-01-15 Time 15:04 Sent To  
Notes
2021-01-15 15:06:11THE A SHEETS MUST BE EITHER DIGITALLY SIGNED AND SEALED
 OR THE ORIGINAL SIGNED AND SEALED PAPER DRAWINGS CAN BE
 BROUGHT TO OUR OFFICE.
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  