2021-01-13 10:22:59 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 20121335 |
| 1/13/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| NFPA 58-14 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE SUBMITTED SURVEY INDICATES THE 250-GALLON LP |
| TANK AS EXISTING HOWEVER THE TANK PERMIT- 10090018 HAS |
| EXPIRED AND FINAL INSPECTION OF THE TANK WAS NEVER |
| PERFORMED. PLEASE NOTE THAT THE SCOPE OF WORK FOR |
| PERMIT 10090018 WAS TO MANIFOLD TOGETHER A NEW |
| 250-GALLON LP TANK TO AN EXISTING LP TANK. BECAUSE YOUR |
| PERMIT WILL INVOLVE CONNECTING THE NEW GAS LINE FROM |
| THE TANKS TO THE GENERATOR, THE NEW TANK MUST ALSO |
| RECEIVE FINAL APPROVAL EITHER UNDER THIS NEW GAS |
| PERMIT, OR UNDER THE PREVIOUS PERMIT THAT WAS OBTAINED |
| BY TANKS AND MOORE GAS SERVICE. PLEASE SEND AN EMAIL TO |
| [email protected] FOR FURTHER ASSISTANCE. |
| |
| 2) THE GAS RISER DRAWING HAS AN INCOMPLETE UG LP TANK |
| HOLD DOWN DETAIL HOWEVER THE RISER INDICATES THE TANK |
| AS EXISTING. AGAIN, IT IS NOT CLEAR WHICH CONTRACTOR |
| WILL BE ACCEPTING RESPONSIBILITY FOR THE NEW TANK |
| INSTALLATION, HOWEVER PLEASE NOTE THAT COMPLETE DETAILS |
| FOR INSTALLATION OF THE TANK ARE REQUIRED FOR THE FINAL |
| INSPECTION. PLEASE REVISE THE RISER AND PROVIDE |
| ADDITIONAL DETAILS PER ITEMS A- F BELOW: |
| |
| A) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO |
| UNDERGROUND TANKS. A 3FT. SEPARATION IS REQUIRED PER |
| TABLE 6.3.1.1 NFPA 58. |
| |
| B) REVISE THE RISER DRAWING TO SHOW THE TANKS |
| MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW |
| THE PIPING INTERCONNECTION WILL BE MADE- SECTION |
| 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE |
| USED FOR PERMANENT INTERCONNECTION OF THE TANKS- |
| SECTION 6.9.3.9B NFPA 58. |
| |
| C) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE |
| MANIFOLD- SECTION 6.8.1.1 NFPA 58. |
| |
| D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| 250-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| SECTION 5.2.1.1 NFPA 58. |
| |
| E) PROVIDE LP TANK INSTALLATION DETAILS SHOWING HOW THE |
| TANK WILL BE ANCHORED TO PREVENT FLOTATION, COLLAPSE, |
| OR LATERAL MOVEMENT- SECTION 6.6.1.6. PLEASE INCLUDE A |
| FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE BURIAL |
| DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, SIZES, |
| AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND THE TYPE |
| OF PROTECTIVE SLEEVES FOR THE CABLES OR STRAPS. |
| |
| F) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| HOW IT WILL BE TESTED- SECTION 6.17.1. |
| |
| 3) PLEASE MARK UP THE SURVEY DRAWING TO SHOW BOTH OF |
| THE TANKS AND THE AND REQUIRED 10 FT. UG TANK CLEARANCE |
| DISTANCES TO THE HOUSE AND ADJACENT PROPERTY LINES- |
| TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANKS |
| ARE LESS TANK 10 FT. FROM THE DRIVEWAY, THE SHELLS FOR |
| THE TANKS SHALL BE 18 IN. BELOW GRADE OR VEHICULAR |
| BARRIER PROTECTION WILL BE REQUIRED- SECTIONS 6.6.6.1 |
| (A). |
| |
| 4) THE ADDRESS OF THE PROJECT, SIGNATURE AND PRINTED |
| NAME OF THE CONTRACTOR ARE CUT OFF SLIGHTLY ON THE |
| RISER DRAWING AND CANNOT BE VIEWED PROPERLY. PLEASE |
| PROVIDE ALL THE INFORMATION CLEARLY ON THE REVISED |
| DRAWING- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |