Plan Review Details - Permit 20121326
Plan Review Stops For Permit 20121326
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-02-21 Cont ID  
Sent By cpuell Date 2021-02-21 Time 06:35 Rev Time 0.00
Received By cpuell Date 2021-02-21 Time 06:35 Sent To  
Notes
2021-02-21 06:36:04PER RESPONSE TO COMMENTS, HALF ADDRESS WILL BE REMOVED.
 PRIMARY ADDRESS TO REMAIN.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-01-04 Cont ID  
Sent By cpuell Date 2021-01-04 Time 12:13 Rev Time 0.00
Received By cpuell Date 2021-01-04 Time 12:13 Sent To  
Notes
2021-01-04 12:13:57CURRENTLY THERE IS A 1/2 ADDRESS ON THIS PROPERTY, WIL
 THIS SINGLE FAMILY HOME BE ONE UNIT ONLY? PLEASE EMAIL
 RESPONCE TO [email protected]
 OK WITH PRIMARY ADDRESS BEING 2404 GEORGIA AVE

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 15:03 Rev Time 0.00
Received By jgomez Date 2021-07-06 Time 13:24 Sent To  
Notes
2021-07-06 13:26:01BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL FOR:
 A)OVERHEAD GARAGE DOOR.
 B)METAL ROOFING.
 C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES.
 D)EXTERIOR DOORS.
 E)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR
 DOORS.
 F) WINDOW MULLIONS. AND SPECIFY MULLION SIZE.
  
 2- ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS.
  
 3-PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD). NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H".
  
 4- PROVIDE BALCONY CABLE RAILINGS SHOP DRAWINGS
 (REVIEWED BY ARCHITECT OF RECORD).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-12 Cont ID  
Sent By jgomez Date 2021-04-12 Time 12:25 Rev Time 0.00
Received By jgomez Date 2021-04-12 Time 10:24 Sent To  
Notes
2021-04-12 12:26:24NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121326
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 ENERGY CALCULATIONS MUST BE SIGNED BY THE OWNER/AGENT
 PRIOR TO ISSUING PERMIT.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
  
 THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 A)ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED AND
 DATED BY THE OWNER OR LEGAL AGENT AS REQUESTED ON THE
 FIRST REVIEW. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION
  
 REPEAT COMMENT. NOT ADDRESSED.
 B)FORM SUBMITTED R405-2020 IS FOR THE 2020 FBC EDITION.
 THIS PERMIT APPLICATION AND PLANS WERE REVIEWED UNDER
 THE 2017 FBC. NEED TO REVISE AND RESUBMIT FORM BASED ON
 THE 2017 FBC.
 CHAPTER 553 F.S.
  
 REPEAT COMMENT. NOT ADDRESSED.
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. OWNER INFORMATION IS INCORRECT. PROVIDE BUILDER'S
 NAME.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 D)ITEM #2 ON PAGE 1 OF 5 IS INCORRECT. SEE QUESTION AND
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 E)ITEM #10 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE
 INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 F)ITEM #11 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE
 INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 G)ROOF TYPE ON PAGE 2 OF 5 IS INCOMPLETE. THERE ARE
 MORE ROOF TYPES IN THIS HOUSE. SEE PLANS AND REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 H)WINDOWS INFORMATION ON PAGE 4 OF 5 IS INCORRECT. SEE
 PLANS AND REVISE WINDOW ORIENTATION, WINDOW AREA,
 WINDOW OVERHANG DEPTH AND SEPARATION.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 REPEAT COMMENT. NOT ADDRESSED.
 I)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 2- OK.
 3- OK
 4- OK
 5- OK
  
 6-SHEET A.1:
 A)OK
 B)OK
  
 C) GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED
 PULL-DOWN ACCESS LADDER (22-1/2" X 54"). SPECIFY THE
 ADDITIONAL ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 INFORMATION REGARDING THE ADDITIONAL ATTIC LIVE LOAD
 FOR STORAGE AS REQUIRED BY TABLE R301.5 WAS NOT
 PROVIDED.
  
 7- OK
  
 8- PROVISO: TO BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL.
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)OVERHEAD GARAGE DOOR.
 B)METAL ROOFING.
 C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES.
 D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR
 DOORS.
 E)OVERHEAD GARAGE DOOR
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 PRODUCT APPROVALS ALREADY SUBMITTED WERE NOT
 REVIEWED/APPROVED BY THE ARCHITECT OF RECORD. EITHER
 REVIEW AND APPROVED THOSE PRODUCT APPROVALS THAT WERE
 ALREADY SUBMITTED OR ALL THE PRODUCT APPROVALS CAN BE
 SUBMITTED AS DEFERRED SUBMITTAL AFTER THE PERMIT IS
 ISSUED TO AVOID CONFLICT/DELAYS. SEE PROVISO ON ITEM #8
 ABOVE.
  
 10- PROVISO:
 HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- DEFERRED SUBMITTAL:
 A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD). NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H".
  
 B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-08 Cont ID  
Sent By jgomez Date 2021-03-08 Time 15:51 Rev Time 0.00
Received By jgomez Date 2021-03-08 Time 11:06 Sent To  
Notes
2021-03-08 15:53:03NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121326
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 RESPONSE:
 A)ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED AND
 DATED BY THE OWNER OR LEGAL AGENT AS REQUESTED ON THE
 FIRST REVIEW. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION
  
 B)FORM SUBMITTED R405-2020 IS FOR THE 2020 FBC EDITION.
 THIS PERMIT APPLICATION AND PLANS WERE REVIEWED UNDER
 THE 2017 FBC. NEED TO REVISE AND RESUBMIT FORM BASED ON
 THE 2017 FBC.
 CHAPTER 553 F.S.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. OWNER INFORMATION IS INCORRECT. PROVIDE BUILDER'S
 NAME.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)ITEM #2 ON PAGE 1 OF 5 IS INCORRECT. SEE QUESTION AND
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ITEM #10 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE
 INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)ITEM #11 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE
 INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)ROOF TYPE ON PAGE 2 OF 5 IS INCOMPLETE. THERE ARE
 MORE ROOF TYPES IN THIS HOUSE. SEE PLANS AND REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)WINDOWS INFORMATION ON PAGE 4 OF 5 IS INCORRECT. SEE
 PLANS AND REVISE WINDOW ORIENTATION, WINDOW AREA,
 WINDOW OVERHANG DEPTH AND SEPARATION.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REVISED SITE PLOT PLAN SHOWS A GRADE ELEVATION OF 20.70
 AT THE NORTH EAST CORNER OF THE LOT. THERE IS NOT
 INFORMATION GIVEN ABOUT THE GRADE ELEVATION AT THE
 ADJACENT PROPERTY. WHAT WAS THIS ELEVATION BASED ON?.
 WHAT IS THE GRADE ELEVATION AT THE PROPERTY LINE?
 IN ADDITION, AFTER REVIEWING THE REVISED SITE PLOT PLAN
 IT WAS NOTICED THAT THE SIZE OF THE LOT IS SHOWN AS
 55.90' X 100.00'. ACCORDING TO CITY PLAT RECORDS THE
 SIZE OF THIS LOT IS 54.9' X 100'.
  
 SINCE THERE IS DISCREPANCY ON THE SIZE OF THE LOT, A
 SURVEY WILL BE REQUIRED TO SHOW THE ACTUAL SIZE OF THE
 LOT AND TO SHOW THE ADJACENT GRADES TO VERIFY PROPOSED
 DRAINAGE. SEC. 107.2.5 CITY AMENDMENTS.
  
 NOTE:
 NEED TO CHECK SIZE OF PROPOSED STRUCTURE. PLANS SHOW A
 BUILDING WIDTH OF 40'-8". THIS SIZE OF BUILDING MAY NOT
 COMPLY WITH THE ZONING SETBACKS. COORDINATE WITH ZONING
 TO AVOID CONFLICTS/DELAYS.
  
  
 3- OK
  
 4- OK
  
 5- OK
  
 6-SHEET A.1:
 A)OK
 B)OK
  
 C) GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED
 PULL-DOWN ACCESS LADDER (22-1/2" X 54"). SPECIFY THE
 ADDITIONAL ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL.
  
 RESPONSE:
 INFORMATION REGARDING THE ADDITIONAL ATTIC LIVE LOAD
 FOR STORAGE AS REQUIRED BY TABLE R301.5 WAS NOT
 PROVIDED.
  
  
 7- OK
  
 8- PROVISO: TO BE SUBMITTED LATER AS DEFERRED
 SUBMITTAL.
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)OVERHEAD GARAGE DOOR.
 B)METAL ROOFING.
 C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES.
 D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR
 DOORS.
 E)OVERHEAD GARAGE DOOR
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 PRODUCT APPROVALS ALREADY SUBMITTED WERE NOT
 REVIEWED/APPROVED BY THE ARCHITECT OF RECORD. EITHER
 REVIEW AND APPROVED THOSE PRODUCT APPROVALS THAT WERE
 ALREADY SUBMITTED OR ALL THE PRODUCT APPROVALS CAN BE
 SUBMITTED AS DEFERRED SUBMITTAL AFTER THE PERMIT IS
 ISSUED TO AVOID CONFLICT/DELAYS. SEE PROVISO ON ITEM #8
 ABOVE.
  
 10- PROVISO:
 HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- DEFERRED SUBMITTAL:
 A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD). NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H".
  
 B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By jgomez Date 2021-01-22 Time 18:08 Rev Time 0.00
Received By jgomez Date 2021-01-22 Time 17:25 Sent To  
Notes
2021-01-22 18:10:59NEW SINGLE FAMILY RESIDENCE (R3)BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121326
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL
 THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED
 AGENT TO AVOID CONFLICT/DELAYS.
  
 THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND
 DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION.
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- MISSING SHEET A2.1 LISTED ON THE SHEET LIST ON SHEET
 A.0. THIS SHEET HAS THE WINDOWS AND DOORS SCHEDULES.
 UNABLE TO REVIEW EGRESS WINDOWS (SEC. R310.2.1
 FBC-RESIDENTIAL AND IF SECOND FLOOR WINDOWS WILL
 REQUIRE WINDOW FALL PROTECTION (SEC. R312.2
 FBC-RESIDENTIAL). PLEASE PROVIDE THIS SHEET. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- FOUNDATION PLAN ON SHEET S.1:
 EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12
 INCHES BELOW GRADE AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE DEPTH OF FOOTINGS AS REQUIRED.
 NOTE: COORDINATE FOOTING DEPTH WITH THE REQUIRED
 CLEARANCE REQUIRED ABOVE GRADE FOR TERMITE INSPECTION.
 SEC. R318.7 FBC-RESIDENTIAL.
  
 5- SHEET S.2.1:
 REVISE THE ROOF NET UPLIFT DIAGRAM. THE UPPER ZONE OF
 THE GABLE END IS ZONE #3 NOT ZONE #2. SEE FIGURE
 R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED.
  
 6- SHEET A.1:
 A)NEED BATHROOM WITH A DOOR THAT PROVIDES 29" MIN.
 CLEAR OPENING AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL.
 FIRST FLOOR BATHROOM (MASTER BATH/POWDER ROOM) DOESN'T
 PROVIDE DOOR WITH 29" CLEAR OPENING WHEN ENTERING THE
 POWDER ROOM. REVISE AS REQUIRED.
  
 B)STAIRWAY ON THE 1ST FLOOR PLAN SHOWS (17)RISERS @
 7.76 INCHES. THIS EXCEEDS THE MAXIMUM RISER HEIGHT OF
 7-3/4 INCHES REQUIRED BY SEC. R311.7.5.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 C)GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED
 PULL-DOWN ACCESS LADDER. SPECIFY THE ADDITIONAL ATTIC
 LIVE LOADS AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 ALSO, SPECIFY SIZE OF ATTIC ACCESS OPENING (SEC. R807
 FBC-RESIDENTIAL).
  
 7- SHEET A.1.1: SPECIFY ATTIC ACCESS SIZE AND LOCATION
 SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)OVERHEAD GARAGE DOOR.
 B)METAL ROOFING.
 C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES.
 D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR
 DOORS.
 E)OVERHEAD GARAGE DOOR
  
 NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 MULLIONS. PLANS DON'T SHOW ANY MULLIONS.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 11- DEFERRED SUBMITTAL:
 A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD). NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H".
  
 B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY
 ARCHITECT OF RECORD).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-05 Cont ID  
Sent By cthroop Date 2021-01-05 Time 10:44 Rev Time 0.00
Received By cthroop Date 2021-01-05 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-01-05 Cont ID  
Sent By cthroop Date 2021-01-05 Time 10:44 Rev Time 0.00
Received By cthroop Date 2021-01-05 Time 09:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 17:48 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 17:43 Sent To  
Notes
2021-02-23 17:48:5202/23/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By lcrespo Date 2021-01-05 Time 11:10 Rev Time 0.00
Received By lcrespo Date 2021-01-05 Time 06:47 Sent To  
Notes
2021-01-05 11:10:4801/05/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A DIMENSION ON A HOUSE PLAN SHOWING
 THE TANK-LESS WATER HEATER'S LOCATION AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1'
 AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC R318.5.
  
 3. PLEASE PROVIDE A SPECIFICATION THAT SHOWS LISTED AND
 LABELED IN ACCORDANCE WITH A SYMBOL OR OTHER
 IDENTIFYING MARK OF A NATIONALLY RECOGNIZED TESTING
 LABORATORY, INSPECTION AGENCY, OR OTHER ORGANIZATION
 CONCERNED WITH PRODUCT EVALUATION THAT MAINTAINS
 PERIODIC INSPECTION OF THE PRODUCTION OF THE
 ABOVE-LABELED ITEMS AND WHOSE LABELING INDICATES EITHER
 THAT THE EQUIPMENT, MATERIAL OR PRODUCT MEETS
 IDENTIFIED STANDARDS OR HAS BEEN TESTED AND FOUND
 SUITABLE FOR A SPECIFIED PURPOSE.
  
 4. PLEASE SHOW ALL REGULATORS AND UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC
 G2421.2 OR 2017 FBC FG SEC 410.2.
  
 5. NEED A HARD CAP FOR A FUTURE FIRE PIT; PLEASE SHOW
 ON GAS ISOMERIC G.1 APPLIANCE SHUTOFF 2017 FBC FG SEC.
 409.5 OR 2017 FBC RES. SEC. G2401.1.3.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-07-29 Time   Rev Time 0.00
Received By lmarchan Date 2021-07-21 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 17:16 Rev Time 0.00
Received By jgomez Date 2021-06-21 Time 09:53 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-20 Cont ID  
Sent By rmcphers Date 2021-04-20 Time 12:18 Rev Time 0.00
Received By rmcphers Date 2021-03-25 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-08 Cont ID  
Sent By jgomez Date 2021-03-08 Time 15:58 Rev Time 0.00
Received By jgomez Date 2021-02-18 Time 12:05 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-22 Cont ID  
Sent By jgomez Date 2021-01-22 Time 18:15 Rev Time 0.00
Received By jgomez Date 2020-12-30 Time 09:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-08-09 Cont ID  
Sent By lmarchan Date 2021-08-09 Time 16:35 Rev Time 0.00
Received By lmarchan Date 2021-07-21 Time 12:06 Sent To  
Notes
2021-08-09 16:36:16RECEIPT MU-2021-036216 - $546.52 PAID
2021-07-21 12:06:187/21/21 EMAILED IMPACT FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By jgomez Date 2021-01-12 Time 17:13 Rev Time 0.00
Received By jgomez Date 2021-01-12 Time 17:13 Sent To  
Notes
2021-01-12 17:15:13IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-07-06 Cont ID  
Sent By medwards Date 2021-07-06 Time 15:49 Rev Time 0.00
Received By medwards Date 2021-07-06 Time 15:49 Sent To  
Notes
2021-07-06 13:54:00REVISED HVAC LOAD CALCULATIONS. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 08:36 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 08:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By medwards Date 2021-01-07 Time 12:25 Rev Time 0.00
Received By medwards Date 2021-01-07 Time 10:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-23 Cont ID  
Sent By lcrespo Date 2021-02-23 Time 17:48 Rev Time 0.00
Received By lcrespo Date 2021-02-23 Time 17:43 Sent To  
Notes
2021-02-23 17:49:2602/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By lcrespo Date 2021-01-05 Time 10:35 Rev Time 0.00
Received By lcrespo Date 2021-01-05 Time 06:45 Sent To  
Notes
2021-01-05 10:36:0201/05/20 1ST REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING
 REFERENCED USED PER THE WPB AMENDMENTS TO THE FBC SEC.
 101.4 REFERENCED CODES. ON PAGE A.0, IT REFERENCES THE
 BUIDING CODE, AND THESE PLANS ARE UNDER THE RESIDENTIAL
 CODE FOR THE DWELLING; PLEASE CLARIFY.
  
 2. A SEPARATE PERMIT WILL BE REQUIRED FOR DEMOLITION
 AND CAP OFF PLUMBING PER THE WPB AMENDMENTS TO FBC SEC.
 105.1. PLEASE PROVIDE A WATER SOURCE EITHER ON A FIRE
 HYDRANT OR WITH A BACKFLOW DEVICE THAT REQUIRES A
 PERMIT FOR THE DEMO WORK.
  
 3. ON SHEET P.3,
  
 A. THE WASHING MACHINE IS SHOWN ON A STANDPIPE BELOW
 THE SLAB, WHICH EXCEEDS THE 42" MAX PER THE 2017 FBC
 SEC. R 2706.1.1
  
 B. THE VENT IS ON A DRY VENT CONNECTING TO A HORIZONTAL
 DRAIN SHALL CONNECT ABOVE THE HORIZONTAL DRAIN PIPE'S
 CENTERLINE PER THE 2017 R 3104.3 VENT CONNECTION TO THE
 DRAINAGE SYSTEM. PLEASE SHOE CONNECTION ON A SANITARY
 FITTING TO P-TRAP.
  
 4. THE UPSTAIRS DOUBLE LAV IS MISSING THE SECOND
 P-TRAP; PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. THE TANKLESS HEATER HAS PIPES NOT IN CONDITION SPACE
 AND NEEDS TO BE INSULATED WITH A MINIMUM R-3 PER THE
 2017 FBC SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 15:14 Rev Time 0.00
Received By jgomez Date 2021-07-06 Time 15:14 Sent To  
Notes
2021-07-06 15:15:04ROOFING REVIEW PROVISO (PROVIDE COMPLETE INFORMATION
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 A)METAL ROOFING.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-03-08 Cont ID  
Sent By jgomez Date 2021-03-08 Time 15:53 Rev Time 0.00
Received By jgomez Date 2021-03-08 Time 15:53 Sent To  
Notes
2021-03-08 15:55:40ROOFING REVIEW PROVISO (PROVIDE COMPLETE INFORMATION
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 A)METAL ROOFING.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-01-22 Cont ID  
Sent By jgomez Date 2021-01-22 Time 18:11 Rev Time 0.00
Received By jgomez Date 2021-01-22 Time 18:11 Sent To  
Notes
2021-01-22 18:12:251- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)METAL ROOFING.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-07-06 Cont ID  
Sent By jgomez Date 2021-07-06 Time 15:17 Rev Time 0.00
Received By jgomez Date 2021-07-06 Time 15:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 08:46 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 08:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-22 Cont ID  
Sent By jgomez Date 2021-01-22 Time 18:15 Rev Time 0.00
Received By jgomez Date 2021-01-22 Time 18:14 Sent To  
Notes
2021-01-05 10:48:40DIGITAL SIG. VALID ON ELECTRICAL PLANS. CT

Review Stop Z ZONING
Rev No 6 Status P Date 2021-08-20 Cont ID  
Sent By awooten Date 2021-08-20 Time   Rev Time 0.00
Received By awooten Date 2021-08-20 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status F Date   Cont ID  
Sent By   Date 2021-07-27 Time   Rev Time 0.00
Received By   Date 2021-07-27 Time   Sent To  
Notes
2021-07-27 11:25:47*****************ZONING REVIEW
 FAILED********************
  
 SURVEY HAS A 5 FOOT REAR SETBACK AND THE SITE PLAN HAS
 10 FEET. A MINIMUM OF 10 FEET IS REQUIRED.
  
 A SEPARATE LANDSCAPE PERMIT IS REQUIRED.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status F Date 2021-07-06 Cont ID  
Sent By awooten Date 2021-07-06 Time   Rev Time 0.00
Received By awooten Date 2021-07-06 Time   Sent To  
Notes
2021-07-06 09:56:56*******ZONING FAILED**********
  
 PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE
 DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE
 PLAN.
  
 THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING
 PLANS.
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT.
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2021-04-19 Time   Rev Time 0.00
Received By   Date 2021-04-19 Time   Sent To  
Notes
2021-04-19 15:58:31*******ZONING FAILED**********
  
 PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE
 DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE
 PLAN.
  
 THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING
 PLANS.
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT.
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2021-02-26 Cont ID  
Sent By awooten Date 2021-02-26 Time   Rev Time 0.00
Received By awooten Date 2021-02-26 Time   Sent To  
Notes
2021-02-26 13:47:46*******ZONING FAILED**********
  
 PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE
 DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE
 PLAN.
  
 THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING
 PLANS.
  
 SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT.
  
 ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-08 Cont ID  
Sent By awooten Date 2021-01-08 Time   Rev Time  
Received By awooten Date 2021-01-08 Time   Sent To  
Notes
2021-01-08 15:21:22ZONING REVIEW
  
 PROVIDE DIMENSIONS OF ROOF OVERHANGS
 ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN
 THREE FEET INTO ANY SETBACK.
  
 A SEPARATE LANDSCAPE AND IRRIGATION PERMIT IS REQUIRED
 FOR ALL NEW SINGLE FAMILY DEVELOPMENT.
  
 SEPARATE PERMITS ARE REQUIRED FOR FENCES/WALLS,
 DRIVEWAYS, GENERATORS, POOLS, AND MECHANICAL EQUIPMENT.
  
  
 ALANA WOOTEN
 PLANNING DIVISION
 PLANNER
 561-822-1449
 [email protected]
  
  