Plan Review Stops For Permit 20121326 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2021-02-21 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-02-21 |
Time |
06:35 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-02-21 |
Time |
06:35 |
Sent To |
|
|
Notes |
2021-02-21 06:36:04 | PER RESPONSE TO COMMENTS, HALF ADDRESS WILL BE REMOVED. | | PRIMARY ADDRESS TO REMAIN. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2021-01-04 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2021-01-04 |
Time |
12:13 |
Sent To |
|
|
Notes |
2021-01-04 12:13:57 | CURRENTLY THERE IS A 1/2 ADDRESS ON THIS PROPERTY, WIL | | THIS SINGLE FAMILY HOME BE ONE UNIT ONLY? PLEASE EMAIL | | RESPONCE TO [email protected] | | OK WITH PRIMARY ADDRESS BEING 2404 GEORGIA AVE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-07-06 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-07-06 |
Time |
13:24 |
Sent To |
|
|
Notes |
2021-07-06 13:26:01 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- PROVIDE PRODUCT APPROVAL FOR: | | A)OVERHEAD GARAGE DOOR. | | B)METAL ROOFING. | | C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. | | D)EXTERIOR DOORS. | | E)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR | | DOORS. | | F) WINDOW MULLIONS. AND SPECIFY MULLION SIZE. | | | | 2- ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS. | | | | 3-PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). NOTE: TABLE R301.5 | | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE | | "H". | | | | 4- PROVIDE BALCONY CABLE RAILINGS SHOP DRAWINGS | | (REVIEWED BY ARCHITECT OF RECORD). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-04-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-04-12 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-04-12 |
Time |
10:24 |
Sent To |
|
|
Notes |
2021-04-12 12:26:24 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | PERMIT #20121326 | | | | NOTE: | | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO | | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER | | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID | | CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO | | ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR | | IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT | | ISSUANCE. | | | | IMPORTANT: | | ENERGY CALCULATIONS MUST BE SIGNED BY THE OWNER/AGENT | | PRIOR TO ISSUING PERMIT. | | | | | | | | ORIGINAL COMMENT: | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5.1 FBC-ENERGY CONSERVATION. | | | | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY | | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS | | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, | | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO | | BEGIN CONSTRUCTION. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | A)ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED AND | | DATED BY THE OWNER OR LEGAL AGENT AS REQUESTED ON THE | | FIRST REVIEW. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION | | | | REPEAT COMMENT. NOT ADDRESSED. | | B)FORM SUBMITTED R405-2020 IS FOR THE 2020 FBC EDITION. | | THIS PERMIT APPLICATION AND PLANS WERE REVIEWED UNDER | | THE 2017 FBC. NEED TO REVISE AND RESUBMIT FORM BASED ON | | THE 2017 FBC. | | CHAPTER 553 F.S. | | | | REPEAT COMMENT. NOT ADDRESSED. | | C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF | | FORM. OWNER INFORMATION IS INCORRECT. PROVIDE BUILDER'S | | NAME. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | D)ITEM #2 ON PAGE 1 OF 5 IS INCORRECT. SEE QUESTION AND | | REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | E)ITEM #10 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE | | INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | F)ITEM #11 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE | | INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | G)ROOF TYPE ON PAGE 2 OF 5 IS INCOMPLETE. THERE ARE | | MORE ROOF TYPES IN THIS HOUSE. SEE PLANS AND REVISE AS | | REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | H)WINDOWS INFORMATION ON PAGE 4 OF 5 IS INCORRECT. SEE | | PLANS AND REVISE WINDOW ORIENTATION, WINDOW AREA, | | WINDOW OVERHANG DEPTH AND SEPARATION. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | REPEAT COMMENT. NOT ADDRESSED. | | I)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE | | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY | | CONSERVATION. | | | | | | 2- OK. | | 3- OK | | 4- OK | | 5- OK | | | | 6-SHEET A.1: | | A)OK | | B)OK | | | | C) GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED | | PULL-DOWN ACCESS LADDER (22-1/2" X 54"). SPECIFY THE | | ADDITIONAL ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 | | FBC-RESIDENTIAL. | | | | RESPONSE: | | REPEAT COMMENT. NOT ADDRESSED. | | INFORMATION REGARDING THE ADDITIONAL ATTIC LIVE LOAD | | FOR STORAGE AS REQUIRED BY TABLE R301.5 WAS NOT | | PROVIDED. | | | | 7- OK | | | | 8- PROVISO: TO BE SUBMITTED LATER AS DEFERRED | | SUBMITTAL. | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL): | | | | A)OVERHEAD GARAGE DOOR. | | B)METAL ROOFING. | | C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. | | D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR | | DOORS. | | E)OVERHEAD GARAGE DOOR | | | | 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | RESPONSE: | | PRODUCT APPROVALS ALREADY SUBMITTED WERE NOT | | REVIEWED/APPROVED BY THE ARCHITECT OF RECORD. EITHER | | REVIEW AND APPROVED THOSE PRODUCT APPROVALS THAT WERE | | ALREADY SUBMITTED OR ALL THE PRODUCT APPROVALS CAN BE | | SUBMITTED AS DEFERRED SUBMITTAL AFTER THE PERMIT IS | | ISSUED TO AVOID CONFLICT/DELAYS. SEE PROVISO ON ITEM #8 | | ABOVE. | | | | 10- PROVISO: | | HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS | | SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC | | EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN | | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | 11- DEFERRED SUBMITTAL: | | A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). NOTE: TABLE R301.5 | | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE | | "H". | | | | B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-03-08 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-03-08 |
Time |
11:06 |
Sent To |
|
|
Notes |
2021-03-08 15:53:03 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | PERMIT #20121326 | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5.1 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL | | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | AGENT TO AVOID CONFLICT/DELAYS. | | | | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY | | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS | | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, | | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO | | BEGIN CONSTRUCTION. | | | | RESPONSE: | | A)ENERGY CALCULATIONS SUBMITTED WERE NOT SIGNED AND | | DATED BY THE OWNER OR LEGAL AGENT AS REQUESTED ON THE | | FIRST REVIEW. SEC. R103.1.1.2 FBC-ENERGY CONSERVATION | | | | B)FORM SUBMITTED R405-2020 IS FOR THE 2020 FBC EDITION. | | THIS PERMIT APPLICATION AND PLANS WERE REVIEWED UNDER | | THE 2017 FBC. NEED TO REVISE AND RESUBMIT FORM BASED ON | | THE 2017 FBC. | | CHAPTER 553 F.S. | | | | C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF | | FORM. OWNER INFORMATION IS INCORRECT. PROVIDE BUILDER'S | | NAME. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | D)ITEM #2 ON PAGE 1 OF 5 IS INCORRECT. SEE QUESTION AND | | REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | E)ITEM #10 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE | | INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | F)ITEM #11 ON PAGE 1 OF 5 DOESN'T MATCH PLANS. SEE | | INSULATION NOTES ON SHEET A.1.1 AND REVISE AS REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | G)ROOF TYPE ON PAGE 2 OF 5 IS INCOMPLETE. THERE ARE | | MORE ROOF TYPES IN THIS HOUSE. SEE PLANS AND REVISE AS | | REQUIRED. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | H)WINDOWS INFORMATION ON PAGE 4 OF 5 IS INCORRECT. SEE | | PLANS AND REVISE WINDOW ORIENTATION, WINDOW AREA, | | WINDOW OVERHANG DEPTH AND SEPARATION. | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | I)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE | | LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY | | CONSERVATION. | | | | | | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | FOLLOWING: | | R401.3 FBC-RESIDENTIAL. | | SEC. 107.2.5 CITY AMENDMENTS. | | SEC. 110.9 CITY AMENDMENTS. | | | | RESPONSE: | | REVISED SITE PLOT PLAN SHOWS A GRADE ELEVATION OF 20.70 | | AT THE NORTH EAST CORNER OF THE LOT. THERE IS NOT | | INFORMATION GIVEN ABOUT THE GRADE ELEVATION AT THE | | ADJACENT PROPERTY. WHAT WAS THIS ELEVATION BASED ON?. | | WHAT IS THE GRADE ELEVATION AT THE PROPERTY LINE? | | IN ADDITION, AFTER REVIEWING THE REVISED SITE PLOT PLAN | | IT WAS NOTICED THAT THE SIZE OF THE LOT IS SHOWN AS | | 55.90' X 100.00'. ACCORDING TO CITY PLAT RECORDS THE | | SIZE OF THIS LOT IS 54.9' X 100'. | | | | SINCE THERE IS DISCREPANCY ON THE SIZE OF THE LOT, A | | SURVEY WILL BE REQUIRED TO SHOW THE ACTUAL SIZE OF THE | | LOT AND TO SHOW THE ADJACENT GRADES TO VERIFY PROPOSED | | DRAINAGE. SEC. 107.2.5 CITY AMENDMENTS. | | | | NOTE: | | NEED TO CHECK SIZE OF PROPOSED STRUCTURE. PLANS SHOW A | | BUILDING WIDTH OF 40'-8". THIS SIZE OF BUILDING MAY NOT | | COMPLY WITH THE ZONING SETBACKS. COORDINATE WITH ZONING | | TO AVOID CONFLICTS/DELAYS. | | | | | | 3- OK | | | | 4- OK | | | | 5- OK | | | | 6-SHEET A.1: | | A)OK | | B)OK | | | | C) GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED | | PULL-DOWN ACCESS LADDER (22-1/2" X 54"). SPECIFY THE | | ADDITIONAL ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 | | FBC-RESIDENTIAL. | | | | RESPONSE: | | INFORMATION REGARDING THE ADDITIONAL ATTIC LIVE LOAD | | FOR STORAGE AS REQUIRED BY TABLE R301.5 WAS NOT | | PROVIDED. | | | | | | 7- OK | | | | 8- PROVISO: TO BE SUBMITTED LATER AS DEFERRED | | SUBMITTAL. | | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 | | FOR | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL): | | | | A)OVERHEAD GARAGE DOOR. | | B)METAL ROOFING. | | C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. | | D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR | | DOORS. | | E)OVERHEAD GARAGE DOOR | | | | 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | RESPONSE: | | PRODUCT APPROVALS ALREADY SUBMITTED WERE NOT | | REVIEWED/APPROVED BY THE ARCHITECT OF RECORD. EITHER | | REVIEW AND APPROVED THOSE PRODUCT APPROVALS THAT WERE | | ALREADY SUBMITTED OR ALL THE PRODUCT APPROVALS CAN BE | | SUBMITTED AS DEFERRED SUBMITTAL AFTER THE PERMIT IS | | ISSUED TO AVOID CONFLICT/DELAYS. SEE PROVISO ON ITEM #8 | | ABOVE. | | | | 10- PROVISO: | | HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS | | SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC | | EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN | | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | 11- DEFERRED SUBMITTAL: | | A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). NOTE: TABLE R301.5 | | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE | | "H". | | | | B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-01-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-01-22 |
Time |
18:08 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-01-22 |
Time |
17:25 |
Sent To |
|
|
Notes |
2021-01-22 18:10:59 | NEW SINGLE FAMILY RESIDENCE (R3)BUILDING REVIEW | | COMMENTS | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | PERMIT #20121326 | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | R101.5.1 FBC-ENERGY CONSERVATION. | | NOTE: PLEASE MAKE SURE CALCULATIONS ARE SIGNED BY ALL | | THE REQUIRED PARTIES, INCLUDING THE OWNER OR AUTHORIZED | | AGENT TO AVOID CONFLICT/DELAYS. | | | | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND | | DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY | | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS | | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, | | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO | | BEGIN CONSTRUCTION. | | | | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE | | FOLLOWING: | | R401.3 FBC-RESIDENTIAL. | | SEC. 107.2.5 CITY AMENDMENTS. | | SEC. 110.9 CITY AMENDMENTS. | | | | 3- MISSING SHEET A2.1 LISTED ON THE SHEET LIST ON SHEET | | A.0. THIS SHEET HAS THE WINDOWS AND DOORS SCHEDULES. | | UNABLE TO REVIEW EGRESS WINDOWS (SEC. R310.2.1 | | FBC-RESIDENTIAL AND IF SECOND FLOOR WINDOWS WILL | | REQUIRE WINDOW FALL PROTECTION (SEC. R312.2 | | FBC-RESIDENTIAL). PLEASE PROVIDE THIS SHEET. SEC. | | 107.2.1 CITY AMENDMENTS. | | | | 4- FOUNDATION PLAN ON SHEET S.1: | | EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS THAN 12 | | INCHES BELOW GRADE AS REQUIRED BY SEC. R403.1.4 | | FBC-RESIDENTIAL. REVISE DEPTH OF FOOTINGS AS REQUIRED. | | NOTE: COORDINATE FOOTING DEPTH WITH THE REQUIRED | | CLEARANCE REQUIRED ABOVE GRADE FOR TERMITE INSPECTION. | | SEC. R318.7 FBC-RESIDENTIAL. | | | | 5- SHEET S.2.1: | | REVISE THE ROOF NET UPLIFT DIAGRAM. THE UPPER ZONE OF | | THE GABLE END IS ZONE #3 NOT ZONE #2. SEE FIGURE | | R301.2(7) FBC-RESIDENTIAL AND REVISE AS REQUIRED. | | | | 6- SHEET A.1: | | A)NEED BATHROOM WITH A DOOR THAT PROVIDES 29" MIN. | | CLEAR OPENING AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL. | | FIRST FLOOR BATHROOM (MASTER BATH/POWDER ROOM) DOESN'T | | PROVIDE DOOR WITH 29" CLEAR OPENING WHEN ENTERING THE | | POWDER ROOM. REVISE AS REQUIRED. | | | | B)STAIRWAY ON THE 1ST FLOOR PLAN SHOWS (17)RISERS @ | | 7.76 INCHES. THIS EXCEEDS THE MAXIMUM RISER HEIGHT OF | | 7-3/4 INCHES REQUIRED BY SEC. R311.7.5.1 | | FBC-RESIDENTIAL. REVISE AS REQUIRED. | | | | C)GROUND FLOOR ON SHEET A.1 SHOWS A PREFABRICATED | | PULL-DOWN ACCESS LADDER. SPECIFY THE ADDITIONAL ATTIC | | LIVE LOADS AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. | | ALSO, SPECIFY SIZE OF ATTIC ACCESS OPENING (SEC. R807 | | FBC-RESIDENTIAL). | | | | 7- SHEET A.1.1: SPECIFY ATTIC ACCESS SIZE AND LOCATION | | SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL. | | | | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL): | | | | A)OVERHEAD GARAGE DOOR. | | B)METAL ROOFING. | | C)ALL WINDOW TYPES SHOWN ON PLANS AND WINDOW SCHEDULES. | | D)ENTRY DOOR IF DIFFERENT THAN ALL OTHER EXTERIOR | | DOORS. | | E)OVERHEAD GARAGE DOOR | | | | NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR | | MULLIONS. PLANS DON'T SHOW ANY MULLIONS. | | | | 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | 10- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS | | SPECIFYING R-30 SPRAY INSULATION. PROVIDE ICC | | EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN | | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | 11- DEFERRED SUBMITTAL: | | A)PROVIDE GLAZED RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). NOTE: TABLE R301.5 | | FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE | | "H". | | | | B)BALCONY CABLE RAILINGS SHOP DRAWINGS (REVIEWED BY | | ARCHITECT OF RECORD). | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET OR | | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2021-01-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-01-05 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-01-05 |
Time |
09:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
Rev No |
1 |
Status |
P |
Date |
2021-01-05 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-01-05 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-01-05 |
Time |
09:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-02-23 |
Time |
17:48 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-02-23 |
Time |
17:43 |
Sent To |
|
|
Notes |
2021-02-23 17:48:52 | 02/23/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-01-05 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-01-05 |
Time |
06:47 |
Sent To |
|
|
Notes |
2021-01-05 11:10:48 | 01/05/20 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE PROVIDE A DIMENSION ON A HOUSE PLAN SHOWING | | THE TANK-LESS WATER HEATER'S LOCATION AND THE LOCATION | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE | | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. | | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 2. GAS UNITS REQUIRE CONDENSATE, AND THEY NEED TO BE 1' | | AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC R318.5. | | | | 3. PLEASE PROVIDE A SPECIFICATION THAT SHOWS LISTED AND | | LABELED IN ACCORDANCE WITH A SYMBOL OR OTHER | | IDENTIFYING MARK OF A NATIONALLY RECOGNIZED TESTING | | LABORATORY, INSPECTION AGENCY, OR OTHER ORGANIZATION | | CONCERNED WITH PRODUCT EVALUATION THAT MAINTAINS | | PERIODIC INSPECTION OF THE PRODUCTION OF THE | | ABOVE-LABELED ITEMS AND WHOSE LABELING INDICATES EITHER | | THAT THE EQUIPMENT, MATERIAL OR PRODUCT MEETS | | IDENTIFIED STANDARDS OR HAS BEEN TESTED AND FOUND | | SUITABLE FOR A SPECIFIED PURPOSE. | | | | 4. PLEASE SHOW ALL REGULATORS AND UNIONS IN FRONT OF | | REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC | | G2421.2 OR 2017 FBC FG SEC 410.2. | | | | 5. NEED A HARD CAP FOR A FUTURE FIRE PIT; PLEASE SHOW | | ON GAS ISOMERIC G.1 APPLIANCE SHUTOFF 2017 FBC FG SEC. | | 409.5 OR 2017 FBC RES. SEC. G2401.1.3. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-07-29 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-07-21 |
Time |
12:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-07-06 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-06-21 |
Time |
09:53 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-04-20 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2021-04-20 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2021-03-25 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-03-08 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-02-18 |
Time |
12:05 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-01-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-01-22 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2020-12-30 |
Time |
09:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-08-09 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-08-09 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-07-21 |
Time |
12:06 |
Sent To |
|
|
Notes |
2021-08-09 16:36:16 | RECEIPT MU-2021-036216 - $546.52 PAID | 2021-07-21 12:06:18 | 7/21/21 EMAILED IMPACT FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2021-01-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-01-12 |
Time |
17:13 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-01-12 |
Time |
17:13 |
Sent To |
|
|
Notes |
2021-01-12 17:15:13 | IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR | | IMPACT FEE ASSESSMENT. | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-07-06 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-07-06 |
Time |
15:49 |
Sent To |
|
|
Notes |
2021-07-06 13:54:00 | REVISED HVAC LOAD CALCULATIONS. JG. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-01 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-01 |
Time |
08:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2021-01-07 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-01-07 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-01-07 |
Time |
10:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-02-23 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-02-23 |
Time |
17:48 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-02-23 |
Time |
17:43 |
Sent To |
|
|
Notes |
2021-02-23 17:49:26 | 02/23/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2021-01-05 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-01-05 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-01-05 |
Time |
06:45 |
Sent To |
|
|
Notes |
2021-01-05 10:36:02 | 01/05/20 1ST REVIEW**DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING | | REFERENCED USED PER THE WPB AMENDMENTS TO THE FBC SEC. | | 101.4 REFERENCED CODES. ON PAGE A.0, IT REFERENCES THE | | BUIDING CODE, AND THESE PLANS ARE UNDER THE RESIDENTIAL | | CODE FOR THE DWELLING; PLEASE CLARIFY. | | | | 2. A SEPARATE PERMIT WILL BE REQUIRED FOR DEMOLITION | | AND CAP OFF PLUMBING PER THE WPB AMENDMENTS TO FBC SEC. | | 105.1. PLEASE PROVIDE A WATER SOURCE EITHER ON A FIRE | | HYDRANT OR WITH A BACKFLOW DEVICE THAT REQUIRES A | | PERMIT FOR THE DEMO WORK. | | | | 3. ON SHEET P.3, | | | | A. THE WASHING MACHINE IS SHOWN ON A STANDPIPE BELOW | | THE SLAB, WHICH EXCEEDS THE 42" MAX PER THE 2017 FBC | | SEC. R 2706.1.1 | | | | B. THE VENT IS ON A DRY VENT CONNECTING TO A HORIZONTAL | | DRAIN SHALL CONNECT ABOVE THE HORIZONTAL DRAIN PIPE'S | | CENTERLINE PER THE 2017 R 3104.3 VENT CONNECTION TO THE | | DRAINAGE SYSTEM. PLEASE SHOE CONNECTION ON A SANITARY | | FITTING TO P-TRAP. | | | | 4. THE UPSTAIRS DOUBLE LAV IS MISSING THE SECOND | | P-TRAP; PLEASE CORRECT PER THE WPB AMENDMENTS TO THE | | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | 5. THE TANKLESS HEATER HAS PIPES NOT IN CONDITION SPACE | | AND NEEDS TO BE INSULATED WITH A MINIMUM R-3 PER THE | | 2017 FBC SEC. RE 403.5.3. | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
3 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-07-06 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-07-06 |
Time |
15:14 |
Sent To |
|
|
Notes |
2021-07-06 15:15:04 | ROOFING REVIEW PROVISO (PROVIDE COMPLETE INFORMATION | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR | | | | A)METAL ROOFING. | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2021-03-08 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-03-08 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-03-08 |
Time |
15:53 |
Sent To |
|
|
Notes |
2021-03-08 15:55:40 | ROOFING REVIEW PROVISO (PROVIDE COMPLETE INFORMATION | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR | | | | A)METAL ROOFING. | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2021-01-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-01-22 |
Time |
18:11 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-01-22 |
Time |
18:11 |
Sent To |
|
|
Notes |
2021-01-22 18:12:25 | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | 61G20-3.001 FOR | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | RECORD PRIOR TO SUBMITTAL): | | | | A)METAL ROOFING. | | | | 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-07-06 |
Time |
15:17 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-07-06 |
Time |
15:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-01 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-01 |
Time |
08:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2021-01-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2021-01-22 |
Time |
18:15 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2021-01-22 |
Time |
18:14 |
Sent To |
|
|
Notes |
2021-01-05 10:48:40 | DIGITAL SIG. VALID ON ELECTRICAL PLANS. CT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
6 |
Status |
P |
Date |
2021-08-20 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2021-08-20 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2021-08-20 |
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-07-27 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2021-07-27 |
Time |
|
Sent To |
|
|
Notes |
2021-07-27 11:25:47 | *****************ZONING REVIEW | | FAILED******************** | | | | SURVEY HAS A 5 FOOT REAR SETBACK AND THE SITE PLAN HAS | | 10 FEET. A MINIMUM OF 10 FEET IS REQUIRED. | | | | A SEPARATE LANDSCAPE PERMIT IS REQUIRED. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2021-07-06 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2021-07-06 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2021-07-06 |
Time |
|
Sent To |
|
|
Notes |
2021-07-06 09:56:56 | *******ZONING FAILED********** | | | | PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE | | DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE | | PLAN. | | | | THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING | | PLANS. | | | | SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT. | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-04-19 |
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
2021-04-19 |
Time |
|
Sent To |
|
|
Notes |
2021-04-19 15:58:31 | *******ZONING FAILED********** | | | | PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE | | DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE | | PLAN. | | | | THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING | | PLANS. | | | | SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT. | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-02-26 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2021-02-26 |
Time |
|
Rev Time |
0.00 |
Received By |
awooten |
Date |
2021-02-26 |
Time |
|
Sent To |
|
|
Notes |
2021-02-26 13:47:46 | *******ZONING FAILED********** | | | | PROVIDE A SURVEY OF THE PROPERTY AND MAKE SURE THAT THE | | DIMENSIONS OF THE LOT ARE CONSISTENT WITH THE SITE | | PLAN. | | | | THE LANDSCAPE PLANS ARE SUBMITTED WITH THE BUILDING | | PLANS. | | | | SUBMIT A SEPARATE LANDSCAPE AND IRRIGATION PERMIT. | | | | ADDITIONAL COMMENTS MAY FOLLOW FURTHER REVIEW. | | | | ALANA WOOTEN | | PLANNER | | PLANNING DIVISION | | 561-822-1449 | | [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-01-08 |
|
|
Cont ID |
|
Sent By |
awooten |
Date |
2021-01-08 |
Time |
|
Rev Time |
|
Received By |
awooten |
Date |
2021-01-08 |
Time |
|
Sent To |
|
|
Notes |
2021-01-08 15:21:22 | ZONING REVIEW | | | | PROVIDE DIMENSIONS OF ROOF OVERHANGS | | ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN | | THREE FEET INTO ANY SETBACK. | | | | A SEPARATE LANDSCAPE AND IRRIGATION PERMIT IS REQUIRED | | FOR ALL NEW SINGLE FAMILY DEVELOPMENT. | | | | SEPARATE PERMITS ARE REQUIRED FOR FENCES/WALLS, | | DRIVEWAYS, GENERATORS, POOLS, AND MECHANICAL EQUIPMENT. | | | | | | ALANA WOOTEN | | PLANNING DIVISION | | PLANNER | | 561-822-1449 | | [email protected] | | | | |
|
|