Plan Review Details - Permit 20121283
Plan Review Stops For Permit 20121283
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 13:05 Rev Time 0.00
Received By jwitmer Date 2021-03-08 Time 12:18 Sent To  
Notes
2021-03-08 13:04:53TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2021-03-08 Time 12:18 Sent To  
Notes
2021-03-08 13:48:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW / APPLY DATE 12/29/ 2020
 / 2017 FBC
 W. P. B. PERMIT: 20121283
 ADD: 1900 CONSULATE PLACE, SUITE 1603
 CONT: MOSS DEVCO INC.
 TEL: 561-662-0819
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 08TH/2021
 ACTION: DENIED
  
 1) THE 2 SUBMITTED PLANS WERE CREATED BY A DRAFTSMAN
 TOM CARDILLO. DRAFTSMAN CAN ONLY DRAW PLANS FOR SINGLE
 FAMILY DWELLING ACCORDING TO THE 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 107.3.4.3. UNDER THE CITY
 AMENDMENTS IF THE PLANS ARE NOT DESIGNED BY EITHER A
 ARCHITECT OR ENGINEER AND FALL UNDERNEATH THE
 REQUIREMENTS FOUND IN F. S. 471. AND 481 A CONTRACTOR
 MUST TAKE THE RESPONSIBILITY FOR THE AUTHORSHIP OF THE
 PLAN AS WELL AS THE RESPONSIBILITY. UNLESS THE
 CONTRACTOR IS LICENSED IN MORE THAN ONE TRADE THEY
 CANNOT DRAW PLANS NOR TAKE OWNERSHIP FOR ANY OTHER
 TRADE THAN WHAT THEY ARE LICENSED IN.
  
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 2) SHEET 1 OF 2:
  
 2A) THE AUTHOR OF THE PLAN NOTES HIS IS A BUILDING
 CONSTRUCTION TYPE III. THIS BUILDING IS A HIGHRISE, 19
 STORIES IN HEIGHT. THE 2017 FBC-B TABLE WOULD REQUIRE A
 BUILDING CONSTRUCTION TYPE I-A. PLEASE UPDATE THE PLAN.
  
 2B) THE SAME PLAN 1 OF 2 ALSO STATES THE OCCUPANCY TYPE
 AS 8 RESIDENTIAL. PLEASE REFER TO THE 2017 FBC-B
 SECTION 310.4, CONDOMINIUMS AND APARTMENTS (LONG TERM
 RESIDENCE, PRIMARILY PERMANENT IN NATURE ARE AN
 OCCUPANCY TYPE R-2. PLEASE UPDATE PLANS.
  
 2C) THE SHEET 1 OF 2 ALSO HAS A NOTE THAT THE
 ALTERATION LEVEL IS LEVEL 1 ALTERATION.
 LEVEL 1 IS DEFINED EXISTING BUILD. CODE 602.1 SCOPE.
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND
 REPLACEMENT OR THE COVERING OF EXISTING MATERIALS,
 ELEMENTS, EQUIPMENT, OR FIXTURES USING NEW MATERIALS,
 ELEMENTS, EQUIPMENT, OR FIXTURES THAT SERVE THE SAME
 PURPOSE.
 LEVEL 2. 603.1 SCOPE. LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION
 OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL
 EQUIPMENT.
 UNDER THE SCOPE OF WORK PAGE 1 OF 2 FOR ELECTRICAL
 CIRCUITS ADDED AS REQUIRED. THIS IS RECONFIGURATION OR
 EXTENSION OF A SYSTEM. PLEASE UPDATE THE PLANS.
  
 2D) THE PLANS ARE SILENT AS TO IF THE 2 SHOWERS ARE
 BEING EITHER RECONFIGURED OR RE-TILED? THE PLANS ARE
 ALSO SILENT IF ANY FLOORING IS TO BE REMOVED AND
 REPLACED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-25 Cont ID  
Sent By equinone Date 2021-02-25 Time 12:18 Rev Time 0.00
Received By equinone Date 2021-02-25 Time 09:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-02-25 Cont ID  
Sent By pleduc Date 2021-02-25 Time   Rev Time 0.00
Received By pleduc Date 2021-02-25 Time 15:45 Sent To  
Notes
2021-02-25 15:45:27PROTECT FIRE SPRINKLER HEADS & FIRE ALARM DEVICES
  
 DO NOT PAINT OVER FS HEADS & FA DEVICES
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-03-08 Time 14:00 Rev Time 0.00
Received By lmarchan Date 2021-02-12 Time 16:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-02-26 Cont ID  
Sent By abelisle Date 2021-02-26 Time 16:38 Rev Time 0.00
Received By abelisle Date 2021-02-26 Time 16:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By jwitmer Date 2021-03-08 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2021-03-08 Time 12:18 Sent To  
Notes
2021-03-08 13:49:581) THE 2 SUBMITTED PLANS WERE CREATED BY A DRAFTSMAN
 TOM CARDILLO. DRAFTSMAN CAN ONLY DRAW PLANS FOR SINGLE
 FAMILY DWELLING ACCORDING TO THE 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 107.3.4.3. UNDER THE CITY
 AMENDMENTS IF THE PLANS ARE NOT DESIGNED BY EITHER A
 ARCHITECT OR ENGINEER AND FALL UNDERNEATH THE
 REQUIREMENTS FOUND IN F. S. 471. AND 481 A CONTRACTOR
 MUST TAKE THE RESPONSIBILITY FOR THE AUTHORSHIP OF THE
 PLAN AS WELL AS THE RESPONSIBILITY. UNLESS THE
 CONTRACTOR IS LICENSED IN MORE THAN ONE TRADE THEY
 CANNOT DRAW PLANS NOR TAKE OWNERSHIP FOR ANY OTHER
 TRADE THAN WHAT THEY ARE LICENSED IN.
  
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  