Plan Review Details - Permit 20121235
Plan Review Stops For Permit 20121235
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-06-21 Cont ID  
Sent By rmcphers Date 2021-06-21 Time 13:15 Rev Time 0.00
Received By rmcphers Date 2021-06-21 Time 13:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-12 Cont ID  
Sent By rmcphers Date 2021-04-12 Time 15:34 Rev Time 0.00
Received By rmcphers Date 2021-04-12 Time 15:08 Sent To  
Notes
2021-04-12 15:31:57ADDING SECURITY GATES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) OVERHEAD ROLL UP GATE DRAWINGS SHOWS A WIND PRESSURE
 OF (-10 PSF) WHICH WILL NOT MEET THE REQUIRED WIND
 PRESSURES FOR THAT OPENING. WILL THERE BE SIGNAGE
 PROVIDED AS TO WHEN THE ROLL UP SCREEN DOOR WILL NEED
 TO BE IN THE ROLLED UP POSITION? FBC 2002.7 (2) WHERE
 SCREEN ENCLOSURES ARE DESIGNED IN ACCORDANCE WITH THE
 SCREEN REMOVAL ALTERNATES OF THIS SECTION, REMOVABLE
 SCREEN MAY CONSIST OF REMOVABLE PANELS, RETRACTABLE
 PANELS, OR BY DESIGNATING SPECIFIC SCREEN PANELS IN THE
 DESIGN IN WHICH THE SCREEN IS TO BE REMOVED BY CUTTING
 THE SCREEN. REMOVABLE PANELS SHALL BE REMOVED,
 RETRACTABLE PANELS SHALL BE PLACED IN THE RETRACTED
 POSITION WITHOUT INCREASING THE LOAD ON THE AFFECTED
 AREA. SCREEN DESIGNATED IN THE DESIGN TO BE CUT SHALL
 BE COMPLETELY CUT WHEN WIND SPEEDS ARE FORECAST TO
 EXCEED 75 MPH. (4) WHERE SCREEN ENCLOSURES ARE DESIGNED
 IN ACCORDANCE WITH THE SCREEN REMOVAL ALTERNATES OF
 THIS SECTION, RETRACTABLE SCREEN PANELS, REMOVABLE
 SCREEN PANELS, AND SCREEN PANELS IDENTIFIED TO BE CUT
 SHALL BE CLEARLY IDENTIFIED ON ADJACENT STRUCTURAL
 MEMBERS WITH HIGHLY VISIBLE PERMANENT LABELS, AT EACH
 PANEL, OR BY OTHER MEANS APPROVED BY THE LOCAL BUILDING
 DEPARTMENT.
 2) TRELLIS WALL SYSTEM TO BE DEFERRED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-15 Cont ID  
Sent By rmcphers Date 2021-01-15 Time 15:09 Rev Time 0.00
Received By rmcphers Date 2021-01-15 Time 13:14 Sent To  
Notes
2021-01-15 15:09:01ADDING SECURITY GATES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GATES AND OVERHEAD ROLLUP DOOR ARE SUBJECT TO WIND
 LOADS PLEASE SHOW ON THE DRAWINGS ALL ATTACHMENTS FOR
 SUCH OR PROVIDE MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS WITH WIND DESIGN PRESSURES THAT MEET OR
 EXCEED THE REQUIRED WIND PRESSURES FOR THE SPECIFIC
 OPENING. FBC 1609
 2) DRAWINGS SHOW CODE USED FOR DESIGN AS 2017 FBC -
 CODE IN EFFECT HAS CHANGED TO 2020 FBC - PLEASE REVISE
 THE DRAWINGS TO REFLECT THE CODE IN EFFECT.
 3) PROVIDE SIGNAGE FOR THE FOLLOWING FIX - FBC 1011.7.4
 ENCLOSURES UNDER EXTERIOR STAIRWAYS.
 THERE SHALL NOT BE ENCLOSED USABLE SPACE UNDER EXTERIOR
 EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED
 IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN
 SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR
 ANY PURPOSE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By jleahy Date 2021-04-12 Time 13:35 Rev Time 0.00
Received By jleahy Date 2021-04-12 Time 12:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-19 Cont ID  
Sent By jleahy Date 2021-01-19 Time 16:39 Rev Time 0.00
Received By jleahy Date 2021-01-19 Time 16:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-19 Cont ID  
Sent By pleduc Date 2021-01-19 Time   Rev Time 0.00
Received By pleduc Date 2021-01-19 Time 11:04 Sent To  
Notes
2021-01-19 11:05:11FIRE PROVISO:
  
  
 CARD READER INSTALLATION SHALL COMPLY WITH NFPA 101, CH
 7, MEANS OF EGRESS AND BE SUBMITTED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS, INCLUDING EQUIPMENT
 SPECIFICATION SHEETS,
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-23 Cont ID  
Sent By jgomez Date 2021-06-23 Time 17:07 Rev Time 0.00
Received By jgomez Date 2021-06-02 Time 12:18 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By lmarchan Date 2021-04-23 Time 08:19 Rev Time 0.00
Received By lmarchan Date 2021-04-06 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-19 Cont ID  
Sent By jleahy Date 2021-01-19 Time 16:39 Rev Time 0.00
Received By jleahy Date 2021-01-04 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-12 Cont ID  
Sent By rmcphers Date 2021-04-12 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2021-04-12 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-15 Cont ID  
Sent By rmcphers Date 2021-01-15 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2021-01-15 Time 15:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-06-22 Cont ID  
Sent By aaponte Date 2021-06-22 Time 14:01 Rev Time 0.00
Received By aaponte Date 2021-06-22 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-04-22 Cont ID  
Sent By aaponte Date 2021-04-22 Time 18:11 Rev Time 0.00
Received By aaponte Date 2021-04-22 Time 18:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By elevesqu Date 2021-01-07 Time 10:32 Rev Time 0.00
Received By elevesqu Date 2021-01-07 Time 10:32 Sent To  
Notes
2021-01-07 10:32:09STAFF DOES NOT SUPPORT THE DESIGN OF THE FENCING AROUND
 THE STAIRS. UNDERSTANDING SECURITY, THE FENCING NEEDS
 TO BE ARCHITECTURALLY COMPATIBLE WITH THE DESIGN OF THE
 STRUCTURE, PLEASE EVALUATE OTHER OPTIONS FOR
 ARCHITECTURALLY ENHANCED FENCING. THE SCREENING FORM
 THE UPPER FLOORS COULD BE CONTINUED DOWN FOR
 CONSISTENCY AND SECURITY
  
 LOCATION OF BURIED MOUNTED CAR-HEIGHT PEDESTAL ON SOUTH
 SIDE CANNOT ENCROACH INTO THE CITY ROW - PLEASE
 RELOCATE ONTO PRIVATE PROPERTY
  
 PLEASE INDICATE TIMING OF GARAGE GATE CLOSURES - WILL
 THESE ONLY BE CLOSED WHEN THE OFFICE IS CLOSED FOR
 BUSINESS?
  
 THE LOCATION OF THE PROPOSED GATE APPURTENCES AT THE
 SOUTH ENTRANCE APPEAR TO INTERFERE WITH THE SOUTHERN
 MOST PARKING SPACE INSIDE THE GARAGE - PARKING SPACES
 REQUIRED TO HAVE 8.6 WIDE, AND ADDITIONAL ONE FOOT IF
 NEXT TO WALL. THIS PARKING SPACE MAY NEED TO BE REMOVED
  
 HOW WILL THE PROPOSED PARKING GARAGE SYSTEM WORK WITH
 THE CEILLING MOUNTED PIPES AND EQUIPMENT WITHIN THE
 GARAGE?
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]
  
  