Plan Review Details - Permit 20121101
Plan Review Stops For Permit 20121101
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-15 Cont ID  
Sent By rmcphers Date 2021-10-15 Time 11:45 Rev Time 0.00
Received By rmcphers Date 2021-10-15 Time 11:45 Sent To  
Notes
2021-10-15 11:53:06HOTEL REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2014 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING (A-4.2.01) SHOULD SHOW ROOF PLYWOOD AS FIRE
 RETARDANT PER FBC 603.1 (DRAWING A-0.0.02 SHOWS
 BUILDING CONSTRUCTION TYPE AS IIA)
 2) DRAWING (A-1.2.01) SHOWS ROOM 1204 TO BE 1 HR FIRE
 RATED - THE DOOR SCHEDULE DOES NOT SHOW THE DOOR HOURLY
 FIRE RATING AND THE SELF CLOSING AND LATCHING
 REQUIREMENT FBC TABLE 716.5 AND 716.5.9
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 14:45 Rev Time 0.00
Received By rmcphers Date 2021-06-28 Time 14:41 Sent To  
Notes
2021-07-02 14:42:39HOTEL REVISION 9
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2014 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) DRAWING (A-4.2.01) SHOULD SHOW ROOF PLYWOOD AS FIRE
 RETARDANT PER FBC 603.1 (DRAWING A-0.0.02 SHOWS
 BUILDING CONSTRUCTION TYPE AS IIA)
 2) DRAWING (S-2.04BT) SHOWS NOTE NUMBER (16) AS A NOTE
 FOR 4 X 10 LUMBER WHICH HAS BEEN CHANGED TO 2 X 10
 LUMBER - PLEASE REVISE THE NOTES.
 3) 1ST FLOOR LIFE SAFETY FLOOR PLAN SHOWS EGRESS PATH
 (RED DOTTED LINE) THROUGH THE WALL IN THE (1123)
 DINING/LOUNGE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By rmcphers Date 2021-03-24 Time 15:43 Rev Time 0.00
Received By rmcphers Date 2021-03-22 Time 14:40 Sent To  
Notes
2021-03-24 15:41:35HOTEL REVISION 9
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE CLOUD ALL REVISION 9 CHANGES - SOME CHANGES
 WERE MADE WITHOUT CLOUDS ON DRAWING (A-1.3.01) SUCH AS
 ROOMS 1142,1147,1146,1142A,1145 ETC.. PLEASE CHECK FOR
 ALL CHANGES.
 2) SOME OVERLAY (GHOST WALLS) ARE SHOWN ON THE REVISED
 FLOOR PLANS (A-1.3.01) SUCH AS IN ROOMS 1105, 1123,
 1211 CORRIDOR NEAR PANTRY, 1212, 1210, 1123 AT THE
 ENTRY TO THE DINING ROOM ETC..PLEASE CHECK ALL PLANS.
 3) 1ST FLOOR LIFE SAFETY FLOOR PLAN SHOWS EGRESS PATH
 THROUGH THE WALL IN THE (1123) DINING/LOUNGE.
 4) PLEASE SHOW THE OCCUPANCY LOAD FOR THE DINING/LOUNGE
 (1123) ALL ROOMS SHOULD SHOW THE OCCUPANCY LOAD. FBC
 1004.6 (PROVIDED OCCUPANCY LOAD CHART SHOULD SHOW THE
 ROOM NUMBER).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 13:50 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-03-17 Cont ID  
Sent By jleahy Date 2021-03-17 Time 08:42 Rev Time 0.00
Received By jleahy Date 2021-03-12 Time 12:54 Sent To  
Notes
2021-03-17 08:47:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PAGES E-1.4.01B, C, AND D SHOW ROOM 1146, AND 1147
 WITH WALLS OVERLAYING THE ROOMS, PLEASE CHECK WALL
 LOCATIONS IN THESE TWO AREAS.
  
 2) PAGE E-1.5.05 SHOWS A KING 12A IS THIS ELIMINATED OR
 JUST A MISTAKE?

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-10-04 Cont ID  
Sent By pleduc Date 2021-10-04 Time   Rev Time 0.00
Received By pleduc Date 2021-10-04 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-06-04 Cont ID  
Sent By pleduc Date 2021-06-04 Time   Rev Time 0.00
Received By pleduc Date 2021-06-04 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-03-16 Cont ID  
Sent By pleduc Date 2021-03-16 Time   Rev Time 0.00
Received By pleduc Date 2021-03-09 Time 09:42 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-06-28 Cont ID  
Sent By tklarge Date 2021-06-28 Time 09:06 Rev Time 0.00
Received By tklarge Date 2021-06-28 Time 09:06 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By tklarge Date 2021-04-22 Time 12:54 Rev Time 0.00
Received By tklarge Date 2021-04-22 Time 12:48 Sent To  
Notes
2021-04-22 12:54:231) SUBMIT A FLOOR PLAN SHOWING THE PIPING FOR THE GAS
 SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-3.0.07 - UNIONS ARE REQUIRED WITHIN ONE FOOT
 UPSTREAM OR DOWNSTREAM OF ALL GAS PRESSURE REGULATORS.
 FBC-FUEL GAS SEC.410.2 (7).
 3) SHT. P-3.0.08 HAS A NAMING CONVENTION OF "NATURAL
 GAS" BUT THE PLAN IS OR A CONDENSATE RISER. PLEASE
 REVISE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-23 Cont ID  
Sent By lmarchan Date 2023-02-23 Time 11:53 Rev Time 0.00
Received By lmarchan Date 2021-10-01 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-08 Cont ID  
Sent By lmarchan Date 2021-09-08 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2021-06-03 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-05-25 Cont ID  
Sent By lmarchan Date 2021-05-25 Time 11:05 Rev Time 0.00
Received By lmarchan Date 2021-03-03 Time 10:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-10-08 Cont ID  
Sent By medwards Date 2021-10-08 Time 06:32 Rev Time 0.00
Received By medwards Date 2021-10-08 Time 06:30 Sent To  
Notes
2021-10-08 06:34:17SEE BELOW THE COMMENT FROM THE 2ND CYCLE REVIEW ABOUT
 THE BATHEXHAUST DUCTS PASSING THROUGH THE RATED TENANT
 SEPARATION WALLS. HOW ARE YOU PROTECTING THE DUCT
 PENETRATIONS OF THE RATED WALLS? FIRE DAMPERS?
  
 1) SHEETS M-1.3.03A AND M-1.3.04A HAVE THE BATH EXHAUST
 DUCT TRAVELING THROUGH THE APARTMENT SHAFT, THROUGH THE
 NEIGHBORING TENANTS EXHAUST SHAFT THEN THROUGH THE
 NEIGHBORING TENANT?S ROOM AND INTO ANOTHER EXHAUST
 SHAFT. THESE CHANGES WERE NOT CLOUDED OR MENTIONED IN
 THIS LATEST REVISION SCOPE. PLEASE EXPLAIN WHY THIS
 CHANGE IS OCCURRING AND HOW YOU WILL PROTECT THE
 PENETRATIONS OF THESE SHAFTS. FBC 717.5.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-06-16 Cont ID  
Sent By medwards Date 2021-06-16 Time 06:45 Rev Time 0.00
Received By medwards Date 2021-06-15 Time 14:58 Sent To  
Notes
2021-06-16 06:45:452ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20121101
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-1.3.03A AND M-1.3.04A HAVE THE BATH EXHAUST
 DUCT TRAVELING THROUGH THE APARTMENT SHAFT, THROUGH THE
 NEIGHBORING TENANTS EXHAUST SHAFT THEN THROUGH THE
 NEIGHBORING TENANT?S ROOM AND INTO ANOTHER EXHAUST
 SHAFT. THESE CHANGES WERE NOT CLOUDED OR MENTIONED IN
 THIS LATEST REVISION SCOPE. PLEASE EXPLAIN WHY THIS
 CHANGE IS OCCURRING AND HOW YOU WILL PROTECT THE
 PENETRATIONS OF THESE SHAFTS. FBC 717.5.3
  
 2) SHEET M-0.0.02: IN THE EXHAUST FAN SCHEDULE CHART
 TE-1, TE-2 AND TE-3 WERE NOT MENTIONED IN THE SCOPE OF
 THIS REVISION NOR WERE THEY CLOUDED TO INDICATE A
 CHANGE. PLEASE SHOW THESE ON THE ROOF PLAN. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-03-23 Cont ID  
Sent By medwards Date 2021-03-23 Time 10:18 Rev Time 0.00
Received By medwards Date 2021-03-17 Time 06:01 Sent To  
Notes
2021-03-23 10:19:011ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20121101
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.3.01A: THE SUPPLY DUCT FROM AHU-2 IS
 MISSING A FD AT THE RATED WALL AT THE DESIGNATION OF
 ?COFFEE?.
  
 2) SHEET M-1.3.01A: PLEASE EXPLAIN WHAT (B 1220) IS IN
 THE BANQUETTE KITCHEN.
  
 3) SHEET M-1.3.01B: PLEASE SHOW THE FD IN THE DUCT
 PENETRATING THE RATED WALL AT SECURITY/RECEIVING.
  
 4) SHEET M-1.3.01B: PLEASE SHOW THE FD FOR DUCT
 PENETRATING RATED WALL IN THE DRY STORAGE ROOM.
  
 5) SHEET M-1.3.01B: PLEASE SHOW THE FD IN THE MEN?S
 LOCKER ROOM EXHAUST DUCT PENETRATING CORRIDOR WALL.
  
 6) SHEET M-1.3.01B: PLEASE EXPLAIN THE 10X10 EXHAUST
 DUCT IN WHAT APPEARS TO BE A KITCHEN TO THE LEFT OF THE
 MANICURE/PEDICURE ROOM. THIS EXHAUST DUCT IS
 PENETRATING A RATED WALL AT THIS ROOM, PLEASE SHOW HOW
 THE PENETRATION WILL BE PROTECTED.
  
 7) SHEET M-1.4.01: PLEASE SHOW HOW BOTH THE MANICURE
 AND THE PEDICURE PROCEDURE MEETS THE REQUIREMENT OF
 CONTAINMENT SOURCE WITHIN 12 INCHES OF CHEMICAL
 APPLICATION. FBC M 502.20
  
 8) SHEET M-1.4.01: KITCHEN HOOD SYSTEMS MUST HAVE A
 SEPARATE PERMIT AND REVIEW.
  
 9) SHEET M-1.4.02: KITCHEN AIR BALANCE SCHEDULE MUST
 SHOULD BE INCLUDED WITH THE HOOD SYSTEM PERMIT AND
 REVIEW. PLEASE DO NOT FORGET THAT ALL EXHAUST,
 INCLUDING THE BATHROOMS MUST BE APPLIED. FBC M
  
 10) SHEET M-1.5.01: KEY NOTE 1 REFERS TO SHEET M-5.0.03
 DETAIL #5 FOR THE TOILET EXHAUST SUBDUCT REQUIREMENT
 THIS SHEET ALONG WITH SEVERAL MORE ARE NOT INCLUDED
 WITH THIS SUBMITTAL. PLEASE PROVIDE A COMPLETE
 MECHANICAL DESIGN INCLUDING ALL M SHEETS. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-11-02 Cont ID  
Sent By lcrespo Date 2021-11-02 Time 06:19 Rev Time 0.00
Received By lcrespo Date 2021-10-26 Time 12:04 Sent To  
Notes
2021-11-02 06:21:1211/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT
 ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL
 COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE
 RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED"
 EMPLOYEES, WHICH HAS NOTHING TO DO WITH THE HEIGHT OF
 THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS
 WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS?2ND
 REQUEST.
  
 I WENT TO LOOK FOR SHEET D.2.4.02, AND IT IS MISSING.
 THE INDEX SAYS IT HAS A LOT MORE D THAN UPLOADED, SO
 THEY NEED TO BE CHECKED WITH PROJECT DOX TO SEE WHAT IS
 MISSING.
  
 2. DONE.
  
 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD
 WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS.
 REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND
 REQUEST.
  
 THE QUESTION WAS NOT ANSWERED; WE ARE LOOKING FOR THE
 STANDARD IN SIZING. WAS IT WITH THE ASME A112.14.3,
 ASME A112.14.4, ASME A112.14.6, CSA B481.3, OR PDI
 G101?
  
 4) DONE.
  
 5) SHT. P-1.5.05 - DONE AND NEW COMMENT;
  
 NEW COMMENT, WOULD YOU PLEASE LABEL THE RETURN IN THE
 LOOP WHERE THE 3/4 STARTS (HWR) TO WHERE IT GOES UP TO
 THE SECOND FLOOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6) SHT. P-1.5.06 DONE AND NEW COMMENT;
  
 A. THE VERBIAGE THAT IT SHALL COMPLY WITH ASSE 1024 IS
 WHAT WE LOOK FOR BUT NOT ON THE SHEET MOTIONED. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. THE GUESTROOM DESIGNATED SCF REFERS TO THE 2014
 FIFTH EDITION. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 7) DONE.
  
 8) DONE.
  
 9) SHT P 3.1.01 DONE AND NEW COMMENT;
  
 THERE ARE CONDENSATE LINES THAT HAVE A P-TRAP AND UNDER
 2017 FBC M307.2.4 AND P1002.1. EACH TRAP SHALL BE
 VENTED TO PERMIT THE ADMISSION OR EMISSION OF AIR SO
 THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT BE
 SUBJECTED TO A PRESSURE DIFFERENTIAL OF MORE THAN 1
 INCH OF WATER COLUMN PER THE 2017 FBC SECTION 901.2
 TRAP SEAL PROTECTION. THE CONDENSATE LINE DOES NOT SHOW
 ANY VENT TERMINATION AND LOCATION. THEY CANNOT
 TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR POSITIVE
 PRESSURE TO ALLOW IT TO HAVE A DIFFERENTIAL OF ONE-INCH
 WATER COLUMN. WOULD YOU PLEASE PROVIDE DETAIL OF HOW
 THEY WILL BE VENTED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-29 Cont ID  
Sent By tklarge Date 2021-06-29 Time 10:49 Rev Time 0.00
Received By tklarge Date 2021-06-24 Time 14:24 Sent To  
Notes
2021-06-28 09:12:121) SHT. A-1.3.01 - THE SINK IN ONE OF THE TREATMENT
 ROOMS AND ONE OF THE COUPLE'S SUITES AT THE SPA SHALL
 COMPLY WITH FBC-ACCESSIBILITY SECS. 212.3, 606.1. THE
 RESPONSE NARRATIVE REFERS TO STAFFING BY "ABLE-BODIED"
 EMPLOYEES WHICH HAS NOTHING TO DO WITH THE HEIGHT OF
 THE SINKS IN THESE ROOMS. SHOW COMPLIANCE ON THE PLANS
 WITH THE ACCESSIBILITY REQUIREMENTS FOR THE SINKS. 2ND
 REQUEST.
 2) THE FOLLOWING SHEETS DO NOT BEAR THE DIGITAL
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AS
 REQUIRED BY F.A.C. 61G15-23.0001, 61G15-23.004 -
 P-0.0.00, P-1.1.00, P-1.1.01A, P-1.1.01B, P-1.3.05B,
 P-1.5.01, P-3.0.02B, P-3.0.08. 2ND REQUEST.
 3) SHT. P-1.1.00 - INDICATE ON THE PLAN WHAT STANDARD
 WAS USED FOR THE SIZING OF THE GREASE INTERCEPTORS.
 REFER TO FBC-PLUMBING SECS.1003.2, 1003.3.4. 2ND
 REQUEST.
 4) PLACE MATCHLINES ON THE PLUMBING DRAWINGS ALONG WITH
 THE CORRELATING PAGE THAT SHOWS THE CONTINUATION OF THE
 PIPING.THE WORD "MATCHLINE " WAS PLACED ON THE PLUMBING
 SHEETS WITH NO CORRESPONDING REFERENCE SHEET. 2ND
 REQUEST.
 5) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS
 REQUIRED IN THE BANQUET KITCHEN. THERE IS NO HOT WATER
 RECIRCULATION LINE SHOWN ON THE FLOOR PRESSURE PLAN FOR
 THE BANQUET KITCHEN ON SHT.P-1.401A. FBC-PLUMBING
 SEC.607.2. 2ND REQUEST.
 6) SHT. P-1.5.06 - THE COFFEE AND TEA BREWERS, WATER
 FILTERS AND ICE MAKER SHALL BE EQUIPPED WITH INDIVIDUAL
 BACKFLOW PREVENTION DEVICES COMPLYING WITH ASSE 1024
 PER FBC-PLUMBING SEC. 608.3.THE SODA DISPENSER SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER COMPLYING WITH ASSE
 1022. THE DISHWASHER SHALL BE EQUIPPED WITH A BACKFLOW
 PREVENTION DEVICE COMPLYING WITH ASSE 1020. 2ND
 REQUEST.
 7)SHT. P-1.5.07 - DETAIL #1 - SHOW THE CONTINUATION
 POINT OF THE GAS LINE ON THE ENLARGED KITCHEN PRESSURE
 PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 8) SHT.P-3.0.01 - A RISER TAG ON THE PLAN CALLS OUT
 SAN. RISERS 26 - 28 BUT THERE IS NO RISER SHOWN.
 CLARIFY.
 9) SHT. P-3.0.09 - THERE ARE SOME DOWNSPOUTS THAT ARE
 NOT SIZED, PART OF THE RISER IS CUT OFF ON THE LEFT
 SIDE AND RIGHT SIDE OF THE DRAWING. OF THE DRAWING,
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-04-22 Cont ID  
Sent By tklarge Date 2021-04-22 Time 12:48 Rev Time 0.00
Received By tklarge Date 2021-04-12 Time 07:22 Sent To  
Notes
2021-04-22 09:02:141) SHT. A-1.3.01 - ONE OF THE TREATMENT ROOMS AND ONE
 OF THE COUPLE'S SUITES AT THE SPA SHALL COMPLY WITH
 FBC-ACCESSIBILITY SEC. 201.1 AND THE SINK IN THESE
 ROOMS SHALL COMPLY WITH FBC-ACCESSIBILITY SECS.212.3,
 606.1.
 2) SHT.A-1.3.01 - THE MEN'S AND WOMEN'S STEAM ROOMS
 (M-1206 & W-1224) SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.241 & 612. CONTROLS FOR THE STEAM
 ROOM SHALL COMPLY WITH FBC=ACCESS. SEC.309.
 3) SHT. A-1.3.0.7 - THE SIZING OF THE DOWNSPOUTS AND
 GUTTERS IS BASED ON THE GALLONS PER MINUTE FLOW THROUGH
 THE GUTTER AND DOWNSPOUT PER THE FBC-PLUMBING SECS.
 1106.3, 1106.6 AND TABLES 1106.3 & 1106.6. SUBMIT
 SIZING CALLCULATIONS BASED ON THESE TABLES.THE
 DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM THE
 EXTERIOR BUILDING WALL. FBC-BUILDING SEC. 1503.7. SHOW
 THE DIMENSIONS OF THE GUTTERS & DOWNSPOUTS ON SHTS.
 A-1.3.07 & A-4.4.0.3.
 4) THE PLUMBING SHEETS SHALL BEAR THE DIGITAL SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL PER F.A.C.
 61G15-23.001, 61G15-23.004.
 5) SHT.P-1.1.00 - INDDICATE ON THE PLAN WHAT STANDARD
 WAS USED FOR THE SIZING OF THE GREASE
 INTERCEPTOR.FBC-PLUMBING SECS.1003.2, 1003.3.4,
 6) SHT. P-1.1.00 - SPECIFY ON THE PLAN THE SPECIFIC
 CIVIL DRAWING FOR THE CCONTINUATION OF THE STORM AND
 SANITARY LINES. WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P-1.3.01A - THERE IS A NOTE ON THE PLAN THAT
 STATES "NOT FOR CONSTRUCTION.' CLARIFY.
 8) PLACE MATCHLINES ON THE PLUMBING DRAWINGS FOR THE
 CONTINUATION OF THE PLUMBING SYSTEMS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9)) SHT. P-1.5.0.1 - ENLARGED GUESTROOM - DOUBLE 7 -
 CLEAN UP THE DRAWING AS THERE ARE SSTRUCTURAL ELEMENT
 OVERLAYS ON THE PLUMBING SYTEM AND IS DIFFICULT TO
 REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT.P-1.5.04 - DETAIL #2 - THERE ARE SECTIONS OF
 PIPING MISSING FROM YHE SANITARY RISER. CLARIFY.
 11) SHT.P-1.5.05 - THE SANITARY RISER SHOWS THE HAND
 SINKS DISCHARGING TO THE GREASE WASTE SYSTEM. THE HAND
 SINKS SHALL DISCHARGE TO THE SANITARY SYSTEM
 FBC-PLUMBING SEC. 1003.3.1.
 12) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS
 REQUIRED IN THE BANQUET KITCHEN. FFBC-PLUMBING
 SEC.607.2.
 13) SHT.P-1.05.06 - DETAIL #4 SHOWS AN ISLAND VENT FOR
 A FLLOR SINK. ISLAND VENTS ARE ONLY PERMITTED TO BE
 USED ON SINKS AND LAVATORIES, NOT ON FLOOR
 SINKS.ANOTHER METHOD OF VENTING SHALL BE USED.
 FBC-PLUMBING SEC.916.1.THIS COMMENT APPLIES TO ALL
 FLOOR SINKS WITH AN ISLAND VENT.
 14) SHT. P-1.5.06 - THE COFFEE/TEA BREWERS AND WATER
 FILTER SHALL BE EQUIPPED WITH BACKFLOW DEVICES
 COMPLYING WITH ASSE 1024. THE SODA DISPENSER SHALL BE
 EQUIPPED WITH A BACFLOW PREVENTER COMPLYING WITH ASSE
 1022.
 15) SHT. P-1.5.07 - DETAIL #2 - ENLARGED 1129 KITCHEN -
 THERE IS AN ARROW AT THE TOP LEFT CORNER OF THE PLAN
 THAT STATES "2 INCH FORCE MAIN FROM SUMP PUMP" BUT
 THERE IS NO PIPING SHOWN. CLARIFY.
 16) SHT. P-1.5.07 - DETAILS #2 & #3 - THE HAND SINKS
 SHALL DISCHARGE TO THE SANITARY, NOT TO THE GREASE
 WASTE SYSTEM.FBC-PLUMBING SEC. 1003.3.1.
 17) SHT. P-1.5.07 - DETAILL #4 - ITEM #304 IS NOT SHOWN
 ON THE PRESSURE RISER DIAGRAM. CLARIFY.
 18) SHT. P-1.5.09 - DETAIL #4 - THERE AR SECTIONS OF
 PIPING MISSING FROM THE GRAVITY RISER. REFER TO L-2,
 FLOR DRAINS,SANITARY AND VENT PIPING FOR LAVATORIES.
 CLARIFY.
 19) SHT. P-1.5.10 - DETAIL #4 - WHERE DOES THE DRAIN
 FROM FIXTURE L-2 CONNECT O THE SYSTEM?
 20) SHT. P-1.5.06.1 - DETAIL #4 - ITEMS C202, C203 &
 C204 ARE NOT SHOWN ON THE WATER DISTRIBUTION ISOMETRIC.
 CLARIFY.
 21) SHT. P-1.5.06.1 - DETAIL #1 APPEARS TO SHOW A FLOOR
 SINK IN THE CLUBROOM PANTRY DISCHARGING TO THE
 SANITARY. CLARIFY. WHAT IS BEING DISCHARGED INTO THIS
 FLOOR SINK? ALSO, HAND SINKS SHALL DISCHARGE TO THE
 SANITARY, NOT THE GREASE WASTE SYSTEM.
 22) SHT. P-3.0.00 - SPECIFY THE SPECIFIC CIVIL DRAWING
 ON THE PLAN FOR THE CONTINUATION OF THE 6 INCH SANITARY
 LINE. WPB AMEND. TO FBC SEC. 107.2.1.
 23) SHT. P-3.0.00 - THE RISER DIAGRAM DOES NOT SHOW THE
 BRANCH DRAINS FOR ROOMS F-1108 & M-1107. CLARIFY.
 24) SHT.P-3.0.00 - ONE BRANCCH DRAIN IS SHOWN UPSTREAM
 OF THE GREASE INTERCEPTORS ON THE RISER DIAGRAM BBUT
 TWO ARE SHOWN ON SHT. P-1.3.01A. CLARIFY.
 25) SHT.P-3.0.01 - THE 3 INCH FLOOR SINK ON THE GREASE
 WASTE AND FLOOR DRAIN IN WHAT APPEARS TO BE THE
 DISPENSER AREAARE NOT SHOWN ON SHT. P-1.3.01B. CLARIFY.
 26) SHT. P-3.0.01 SHOWS A 3 INCH FLOOR DRAIN ON THE
 EXTERIOR OF THE BUILDING BY STAIR 3 (#300) DISCHARGING
 TO THE GREASE WASTE SYSTEM. THIS FLOOR DRAIN WILL
 COLLLECT STORMWATER IF IT IS LOCATED ON THE EXTERIOR OF
 THE BUILDING WHICH VIOLATES FBC-PLUMBING SEC.1101.3.
 27) SHT. P-3.0.09 - SPECIFY THE SPECIFIC CIVIL DRAWING
 ON THE PLAN FOR THE CONTINUATION OF THE STORM DRAINS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 28) SHT. P-3.0.09 - THE PIPING IS MISSING FOR THE
 TRENCH DRAINS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-15 Cont ID  
Sent By rmcphers Date 2021-10-15 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2021-10-15 Time 12:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-07-02 Cont ID  
Sent By rmcphers Date 2021-07-02 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2021-07-02 Time 15:26 Sent To  
Notes
2021-07-02 15:28:35SIGNATURE REVIEW
 PLUMBING DRAWINGS ADDED TO PROJECTDOX ON 3/4/2021 NEED
 TO BE SIGNED AND SEALED BY THE DESIGNER. THE SAME
 DRAWINGS DO NOT SHOW AS ELECTRONICALLY SIGNED IN ADOBE
 READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED
 TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER
 OR ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR
 - IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-03-24 Cont ID  
Sent By rmcphers Date 2021-03-24 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2021-03-24 Time 15:55 Sent To  
Notes
2021-03-24 15:56:56PLUMBING DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2023-02-21 Cont ID  
Sent By jroach Date 2023-02-21 Time 13:30 Rev Time 0.00
Received By jroach Date 2023-02-21 Time 13:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-09-08 Cont ID  
Sent By jroach Date 2021-09-08 Time 16:35 Rev Time 0.00
Received By jroach Date 2021-09-08 Time 16:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-05-25 Cont ID  
Sent By jroach Date 2021-05-25 Time 10:37 Rev Time 0.00
Received By jroach Date 2021-05-25 Time 10:36 Sent To  
Notes
2021-05-25 10:39:57THERE APPEAR TO BE NO ZONING ISSUES, HOWEVER, FINAL
 REVIEW WILL OCCUR AT TIME OF RESUBMITTAL OF THE
 REVISIONS.
  
 UPON RESUBMITTAL, PLEASE BE SURE TO INCLUDE A NARRATIVE
 THAT OUTLINES ALL OF THE REVISIONS THAT ARE INCLUDED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved