2021-04-22 09:02:14 | 1) SHT. A-1.3.01 - ONE OF THE TREATMENT ROOMS AND ONE |
| OF THE COUPLE'S SUITES AT THE SPA SHALL COMPLY WITH |
| FBC-ACCESSIBILITY SEC. 201.1 AND THE SINK IN THESE |
| ROOMS SHALL COMPLY WITH FBC-ACCESSIBILITY SECS.212.3, |
| 606.1. |
| 2) SHT.A-1.3.01 - THE MEN'S AND WOMEN'S STEAM ROOMS |
| (M-1206 & W-1224) SHALL COMPLY WITH THE |
| FBC-ACCESSIBILITY SEC.241 & 612. CONTROLS FOR THE STEAM |
| ROOM SHALL COMPLY WITH FBC=ACCESS. SEC.309. |
| 3) SHT. A-1.3.0.7 - THE SIZING OF THE DOWNSPOUTS AND |
| GUTTERS IS BASED ON THE GALLONS PER MINUTE FLOW THROUGH |
| THE GUTTER AND DOWNSPOUT PER THE FBC-PLUMBING SECS. |
| 1106.3, 1106.6 AND TABLES 1106.3 & 1106.6. SUBMIT |
| SIZING CALLCULATIONS BASED ON THESE TABLES.THE |
| DOWNSPOUTS SHALL DISCHARGE A MINIMUM OF 1 FOOT FROM THE |
| EXTERIOR BUILDING WALL. FBC-BUILDING SEC. 1503.7. SHOW |
| THE DIMENSIONS OF THE GUTTERS & DOWNSPOUTS ON SHTS. |
| A-1.3.07 & A-4.4.0.3. |
| 4) THE PLUMBING SHEETS SHALL BEAR THE DIGITAL SIGNATURE |
| AND SEAL OF THE DESIGN PROFESSIONAL PER F.A.C. |
| 61G15-23.001, 61G15-23.004. |
| 5) SHT.P-1.1.00 - INDDICATE ON THE PLAN WHAT STANDARD |
| WAS USED FOR THE SIZING OF THE GREASE |
| INTERCEPTOR.FBC-PLUMBING SECS.1003.2, 1003.3.4, |
| 6) SHT. P-1.1.00 - SPECIFY ON THE PLAN THE SPECIFIC |
| CIVIL DRAWING FOR THE CCONTINUATION OF THE STORM AND |
| SANITARY LINES. WPB AMEND. TO FBC SEC. 107.2.1. |
| 7) SHT. P-1.3.01A - THERE IS A NOTE ON THE PLAN THAT |
| STATES "NOT FOR CONSTRUCTION.' CLARIFY. |
| 8) PLACE MATCHLINES ON THE PLUMBING DRAWINGS FOR THE |
| CONTINUATION OF THE PLUMBING SYSTEMS. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 9)) SHT. P-1.5.0.1 - ENLARGED GUESTROOM - DOUBLE 7 - |
| CLEAN UP THE DRAWING AS THERE ARE SSTRUCTURAL ELEMENT |
| OVERLAYS ON THE PLUMBING SYTEM AND IS DIFFICULT TO |
| REVIEW. WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) SHT.P-1.5.04 - DETAIL #2 - THERE ARE SECTIONS OF |
| PIPING MISSING FROM YHE SANITARY RISER. CLARIFY. |
| 11) SHT.P-1.5.05 - THE SANITARY RISER SHOWS THE HAND |
| SINKS DISCHARGING TO THE GREASE WASTE SYSTEM. THE HAND |
| SINKS SHALL DISCHARGE TO THE SANITARY SYSTEM |
| FBC-PLUMBING SEC. 1003.3.1. |
| 12) SHT. P-1.5.05 - A HOT WATER RECIRCULATION LINE IS |
| REQUIRED IN THE BANQUET KITCHEN. FFBC-PLUMBING |
| SEC.607.2. |
| 13) SHT.P-1.05.06 - DETAIL #4 SHOWS AN ISLAND VENT FOR |
| A FLLOR SINK. ISLAND VENTS ARE ONLY PERMITTED TO BE |
| USED ON SINKS AND LAVATORIES, NOT ON FLOOR |
| SINKS.ANOTHER METHOD OF VENTING SHALL BE USED. |
| FBC-PLUMBING SEC.916.1.THIS COMMENT APPLIES TO ALL |
| FLOOR SINKS WITH AN ISLAND VENT. |
| 14) SHT. P-1.5.06 - THE COFFEE/TEA BREWERS AND WATER |
| FILTER SHALL BE EQUIPPED WITH BACKFLOW DEVICES |
| COMPLYING WITH ASSE 1024. THE SODA DISPENSER SHALL BE |
| EQUIPPED WITH A BACFLOW PREVENTER COMPLYING WITH ASSE |
| 1022. |
| 15) SHT. P-1.5.07 - DETAIL #2 - ENLARGED 1129 KITCHEN - |
| THERE IS AN ARROW AT THE TOP LEFT CORNER OF THE PLAN |
| THAT STATES "2 INCH FORCE MAIN FROM SUMP PUMP" BUT |
| THERE IS NO PIPING SHOWN. CLARIFY. |
| 16) SHT. P-1.5.07 - DETAILS #2 & #3 - THE HAND SINKS |
| SHALL DISCHARGE TO THE SANITARY, NOT TO THE GREASE |
| WASTE SYSTEM.FBC-PLUMBING SEC. 1003.3.1. |
| 17) SHT. P-1.5.07 - DETAILL #4 - ITEM #304 IS NOT SHOWN |
| ON THE PRESSURE RISER DIAGRAM. CLARIFY. |
| 18) SHT. P-1.5.09 - DETAIL #4 - THERE AR SECTIONS OF |
| PIPING MISSING FROM THE GRAVITY RISER. REFER TO L-2, |
| FLOR DRAINS,SANITARY AND VENT PIPING FOR LAVATORIES. |
| CLARIFY. |
| 19) SHT. P-1.5.10 - DETAIL #4 - WHERE DOES THE DRAIN |
| FROM FIXTURE L-2 CONNECT O THE SYSTEM? |
| 20) SHT. P-1.5.06.1 - DETAIL #4 - ITEMS C202, C203 & |
| C204 ARE NOT SHOWN ON THE WATER DISTRIBUTION ISOMETRIC. |
| CLARIFY. |
| 21) SHT. P-1.5.06.1 - DETAIL #1 APPEARS TO SHOW A FLOOR |
| SINK IN THE CLUBROOM PANTRY DISCHARGING TO THE |
| SANITARY. CLARIFY. WHAT IS BEING DISCHARGED INTO THIS |
| FLOOR SINK? ALSO, HAND SINKS SHALL DISCHARGE TO THE |
| SANITARY, NOT THE GREASE WASTE SYSTEM. |
| 22) SHT. P-3.0.00 - SPECIFY THE SPECIFIC CIVIL DRAWING |
| ON THE PLAN FOR THE CONTINUATION OF THE 6 INCH SANITARY |
| LINE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 23) SHT. P-3.0.00 - THE RISER DIAGRAM DOES NOT SHOW THE |
| BRANCH DRAINS FOR ROOMS F-1108 & M-1107. CLARIFY. |
| 24) SHT.P-3.0.00 - ONE BRANCCH DRAIN IS SHOWN UPSTREAM |
| OF THE GREASE INTERCEPTORS ON THE RISER DIAGRAM BBUT |
| TWO ARE SHOWN ON SHT. P-1.3.01A. CLARIFY. |
| 25) SHT.P-3.0.01 - THE 3 INCH FLOOR SINK ON THE GREASE |
| WASTE AND FLOOR DRAIN IN WHAT APPEARS TO BE THE |
| DISPENSER AREAARE NOT SHOWN ON SHT. P-1.3.01B. CLARIFY. |
| 26) SHT. P-3.0.01 SHOWS A 3 INCH FLOOR DRAIN ON THE |
| EXTERIOR OF THE BUILDING BY STAIR 3 (#300) DISCHARGING |
| TO THE GREASE WASTE SYSTEM. THIS FLOOR DRAIN WILL |
| COLLLECT STORMWATER IF IT IS LOCATED ON THE EXTERIOR OF |
| THE BUILDING WHICH VIOLATES FBC-PLUMBING SEC.1101.3. |
| 27) SHT. P-3.0.09 - SPECIFY THE SPECIFIC CIVIL DRAWING |
| ON THE PLAN FOR THE CONTINUATION OF THE STORM DRAINS. |
| WPB AMEND. TO FBC SEC. 107.2.1. |
| 28) SHT. P-3.0.09 - THE PIPING IS MISSING FOR THE |
| TRENCH DRAINS. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |