Plan Review Details - Permit 20121077
Plan Review Stops For Permit 20121077
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-01-20 Cont ID  
Sent By cpuell Date 2021-01-20 Time 12:21 Rev Time 0.00
Received By cpuell Date 2021-01-20 Time 12:21 Sent To  
Notes
2021-01-20 12:22:18BACK UNIT HAS A LEGAL ADDRESS OF 839 4TH ST. UPDATED
 PERMIT ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 18:12 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 17:02 Sent To  
Notes
2023-07-21 18:12:25NEW SINGLE FAMILY RESIDENCE(R3) SEVEN BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
 839 4TH ST
  
 ****NOTE:
 ACCORDING TO THE DEPARTMENT OF BUSINESS & PROFESSIONAL
 REGULATION, THE CONTRACTOR'S LICENSE IS SUSPENDED.
 CONTRACTOR TO UPDATE LICENSE STATUS WITH DBPR PRIOR TO
 OBTAINING THE PERMIT OR PROVIDE CHANGE OF CONTRACTOR
 FORM AND A NEW PERMIT APPLICATION.
  
 PROVISO NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY (EXCEPT FOR
 PRODUCT APPROVALS DEFERRED SUBMITTAL).
  
 ***IMPORTANT
 ****CONTRACTOR TO ADVICE IF PROVISO OPTION IS PREFERRED
 AT THIS TIME OR IF RE-SUBMITTING REQUIRED INFORMATION
 BEFORE PERMIT ISSUANCE.
  
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)OK. ROOF SHINGLES FL31588-R2.
  
 PREVIOUS COMMENT:
 D)HARDIE BOARD SIDING.
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 14:06 Rev Time 0.00
Received By jgomez Date 2023-03-03 Time 12:57 Sent To  
Notes
2023-03-03 14:09:16NEW SINGLE FAMILY RESIDENCE(R3)SIXTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
 839 4TH ST
  
 ****NOTE:
 ACCORDING TO THE DEPARTMENT OF BUSINESS & PROFESSIONAL
 REGULATION, THE CONTRACTOR'S LICENSE IS SUSPENDED.
 CONTRACTOR TO UPDATE LICENSE STATUS WITH DBPR PRIOR TO
 OBTAINING THE PERMIT.
  
  
 NOTE:
 ENGINEER OF RECORD TO PAY $4728.72 FEE OF FOUR TIMES
 THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLANS REVIEW (LAST REVIEW AND THIS ONE).
 FLORIDA STATUTE 553.80(2)(B
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 3-ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF
 FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T
 SEEM TO PROVIDE THE HEADROOM CLEARANCE REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED BETWEEN
 TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2 ON SHEET
 S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT PART OF
 THE HOUSE AND THE REAR PART OF THE HOUSE. THEREFORE,
 THERE IS NOT ACCESS TO OTHER ROOF AREAS. EACH ROOF AREA
 NEEDS AN ATTIC ACCESS. REVISE AS REQUIRED.
  
 PREVIOUS COMMENT:
 3- ATTIC ACCESS WAS NOT REVISED ON THE ROOF FRAMING
 PLAN TO MATCH LOCATIONS SHOWN ON SHEET A-1.
 SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 A)ROOF FRAMING PLAN ON SHEET S2 SHOWS ATTIC ACCESS BY
 THE KITCHEN AREA BEING BLOCKED BY THE TRUSS GIRDER
 ABOVE. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)BEDROOM #3 ATTIC ACCESS LOCATION SHOWN ON SHEET A1
 DOESN'T MATCH LOCATION AND ORIENTATION SHOWN ON THE
 ROOF FRAMING PLAN ON SHEET S2. REVISE TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS.
  
 6-SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN
 THE FRONT PART OF THE HOUSE AND THE REAR PART OF THE
 HOUSE. ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY
 THE BEAM SUPPORTING THE MASONRY WALL.
 ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE
 END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH
 ROOFS.
 FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE
 SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM
 SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH.
 SECTION 2 ON SHEET S-3 SHOWS OUT LOOKERS IN THE MIDDLE
 MASONRY WALL. THE OUT LOOKERS ARE ON THE OTHER SIDE OF
 THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL
 SECTION AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 D)NEW C1 COLUMN IS NOT SHOWN ON THE FLOOR PLAN ON SHEET
 A-1.
  
 RESPONSE:
 PROPOSED FLOOR PLAN ON SHEET A1 SHOWS NEW COLUMN C1
 BLOCKING THE HALLWAY LEADING TO BEDROOM #2 AND BEDROOM
 #3. REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 E)BEAM SUPPORTING THE TWO GABLE END TRUSSES IS NOT
 SPECIFIED ON THE
 BEAM SCHEDULE.
  
 RESPONSE:
 REPEAT COMMENT. ROOF FRAMING PLAN DOESN'T SPECIFY THIS
 BEAM. SEE SECTION-1 ON SHEET S3. THE BEAM IN QUESTION
 IS THE CENTER BEAM SUPPORTING THE TWO GABLE END
 TRUSSES. SEC. 107.2.1 CITY AMENDMENTS.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A)OK. ROOF SHINGLES FL31588-R2.
  
 PREVIOUS COMMENT:
 D)HARDIE BOARD SIDING.
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT:
 12- ENGINEER'S SELF CERTIFIED DIGITAL SIGNATURE
 1- REVISED DRAWINGS A1, S1, S2, S3 AND S5 HAVE
 ENGINEER'S SELF-CERTIFIED SIGNATURE. BOARD OF
 ENGINEER'S DON'T ALLOW SELF-CERTIFICATION. A THIRD
 PARTY CERTIFICATION IS REQUIRED.
 FAC 61G15-23.004.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-12-22 Cont ID  
Sent By jgomez Date 2022-12-22 Time 17:05 Rev Time 0.00
Received By jgomez Date 2022-12-21 Time 16:10 Sent To  
Notes
2022-12-27 16:46:34NEW SINGLE FAMILY RESIDENCE (R3) FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
 839 4TH ST
  
 NOTE:
 ENGINEER OF RECORD TO PAY $4728.72 FEE OF FOUR TIMES
 THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLANS REVIEW (LAST REVIEW AND THIS ONE).
 FLORIDA STATUTE 553.80(2)(B
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 3-ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF
 FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T
 SEEM TO PROVIDE THE HEADROOM CLEARANCE REQUIRED BY SEC.
 R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED BETWEEN
 TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2 ON SHEET
 S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT PART OF
 THE HOUSE AND THE REAR PART OF THE HOUSE. THEREFORE,
 THERE IS NOT ACCESS TO OTHER ROOF AREAS. EACH ROOF AREA
 NEEDS AN ATTIC ACCESS. REVISE AS REQUIRED.
  
 RESPONSE:
 ATTIC ACCESS WAS NOT REVISED ON THE ROOF FRAMING PLAN
 TO MATCH LOCATIONS SHOWN ON SHEET A-1.
 SEC. R807 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 PREVIOUS COMMENT:
 SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN THE
 FRONT PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY THE BEAM
 SUPPORTING THE MASONRY WALL.
 ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE
 END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH
 ROOFS.
 FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE
 SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM
 SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH.
 SECTION 2 ON SHEET S-3 SHOWS OUT LOOKERS IN THE MIDDLE
 MASONRY WALL. THE OUT LOOKERS ARE ON THE OTHER SIDE OF
 THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL
 SECTION AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 A)ROOF FRAMING PLAN ON SHEET S2 SHOWS B-1 BEAM
 SUPPORTING THE MASONRY WALL AND RAKE BEAM RB-1.
 FOUNDATION PLAN WAS REVISED SHOWING COLUMN C1 AND
 FOOTING CF-16 IN THE MIDDLE OF THE FLOOR SLAB. ENGINEER
 TO CLARIFY WHY SPECIFYING A CONTINUOUS SPREAD FOOTING
 INSTEAD OF A CONCRETE PAD IF THE LOAD IS THE ECCENTRIC
 LOAD FROM THE COLUMN?. SEC. R301.1 FBC-RESIDENTIAL.
  
 B)FOUNDATION PLANS WAS ALSO REVISED SHOWING NEW C1
 COLUMNS ON THE PERIMETER WALL BUT THERE IS NOT COLUMN
 SUPPORTING BEAM B-1 ON THE LEFT HAND SIDE.
  
 C) SIZE OF BEAM B-1 SPECIFIED ON SECTION 2 OF SHEET S-3
 DOESN'T MATCH SIZE SPECIFIED ON THE BEAM SCHEDULE.
  
 D)NEW C1 COLUMN IS NOT SHOWN ON THE FLOOR PLAN ON SHEET
 A-1.
  
 E)BEAM SUPPORTING THE TWO GABLE END TRUSSES IS NOT
 SPECIFIED ON THE
 BEAM SCHEDULE.
  
 F)PORCH WOOD JOIST SIZE SPECIFIED ON SECTION 2 OF SHEET
 S-3 DOESN'T MATCH ROOF FRAMING PLAN.
  
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 INFORMATION SHOWN ON THE TYPICAL WALL SECTION ON SHEET
 A-1 DOESN'T MATCH INFORMATION SHOWN ON OTHER PLANS AND
 SECTIONS. REVISE AS REQUIRED TO MATCH TO AVOID MORE
 CONFLICTS/DELAYS. ROOF SHEATHING SPECIFICATIONS DON'T
 MATCH SPECIFICATIONS SHOWN ON SHEET S-5. FOOTING SIZE
 DOESN'T MATCH FOUNDATION PLAN. ATTIC INSULATION DOESN'T
 MATCH. ETC.
 NOTE: ENGINEER TO COORDINATE ALL PLANS, SECTIONS AND
 SPECIFICATIONS TO AVOID MORE CONFLICTS AND DELAYS.
  
 RESPONSE:
 ROOF SHEATHING SPECIFICATIONS DON'T MATCH SECTION
 R803.2.3.1 FBC-RESIDENTIAL AND FIGURE R803.2.3.1
 FBC-RESIDENTIAL. NEED TO SPECIFY NAILS AT 4" O.C. ON
 ROOF ZONE #3 AND NEED TO SPECIFY RING SHANK NAILS. (OR
 PROVIDE CALCULATIONS SHOWING THAT 10D NAIL MATCHES OR
 EXCEEDS 8D RING SHANK NAILS AS REQUIRED BY SEC.
 R803.2.3.1 FBC-RESIDENTIAL).
  
 ALSO, ROOF SHEATHING SPECIFICATIONS DON'T COMPLY WITH
 GABLE ROOF NAILING REQUIREMENTS OF FIGURE R803.2.3.1
 FBC-RESIDENTIAL. ROOF ZONE 3 IS 5 FEET NOT 48".
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 PREVIOUS COMMENT:
 SECTION 2 ON SHEET S-3 SHOWS STEEL COLUMNS BELOW GRADE.
 THIS INFORMATION DOESN'T MATCH INFORMATION SHOWN ON THE
 FOUNDATION PLAN. FOUNDATION PLAN SHOWS A KNEE WALL.
 ALSO, THERE ARE NO DETAIL/SPECIFICATIONS SHOWING HOW
 THE STEEL COLUMNS AND CONNECTIONS ARE PROTECTED AGAINST
 RUST/DETERIORATION.
  
 RESPONSE:
 SECTION 2 ON SHEET S3 STILL DOESN'T MATCH FOUNDATION
 PLAN. IT DOESN'T SHOW THE KNEE WALL AND IT IS NOT CLEAR
 WHAT IS THE PURPOSE OF THE CONCRETE PEDESTAL. THE
 CONCRETE PEDESTAL IS COVERING THE STEEL COLUMN. WHY?.
 WHAT IS THE PURPOSE OF COVERING THE STEEL COLUMN WITH A
 PEDESTAL. ALSO NO SPECS FOR STEEL COLUMN, PLATE AND
 BOLTS PROTECTION FOR RUST.
  
 9-OK.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
  
 A)OK. ROOF SHINGLES FL31588-R2.
  
 PREVIOUS COMMENT:
 D)HARDIE BOARD SIDING.
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-12 Cont ID  
Sent By jgomez Date 2022-07-12 Time 16:50 Rev Time 0.00
Received By jgomez Date 2022-07-11 Time 17:46 Sent To  
Notes
2022-07-12 16:52:59NEW SINGLE FAMILY RESIDENCE (R3) FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
  
 NOTE:
 ENGINEER OF RECORD TO PAY $2364.36 FEE OF FOUR TIMES
 THE AMOUNT OF THE PROPORTION OF THE PERMIT FEE
 ATTRIBUTED TO PLANS REVIEW.
 FLORIDA STATUTE 553.80(2)(B
  
  
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
  
 ORIGINAL COMMENT:
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 A)DRAINAGE PLAN SHOWS A 6 INCH SWALE IMMEDIATELY
 ADJACENT TO THE EXISTING RESIDENCE #837. THE PROPOSED
 SWALE AFFECTS THE FOUNDATION. ENGINEER OF RECORD TO
 PROVIDE DETAILS SPECIFICATIONS SHOWING HOW PROTECTING
 THE FOOTING AS REQUIRED BY SEC. R401.3 BC-RESIDENTIAL.
  
 B)DRAINAGE PLAN SHOWS A PERMANENT TRENCH AND SILT FENCE
 TO CONTAIN THE SURFACE DRAINAGE. NEED TO APPLY FOR A
 SEPARATE FENCE PERMIT FOR ZONING APPROVAL. SEC. 105.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 ATTIC ACCESS WAS RELOCATED, BUT BASED ON THE ROOF
 FRAMING PLAN, THE LOCATION OF THE ATTIC ACCESS DOESN'T
 SEEM TO PROVIDE PROVIDE THE HEADROOM CLEARANCE REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL. ATTIC ACCESS IS LOCATED
 BETWEEN TWO GABLE END ROOFS. ALSO, BASED ON SECTION 2
 ON SHEET S-3, THERE IS A MASONRY WALL BETWEEN THE FRONT
 PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 THEREFORE, THERE IS NOT ACCESS TO OTHER ROOF AREAS.
 EACH ROOF AREA NEEDS AN ATTIC ACCESS. REVISE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 SECTION 2 ON SHEET S-3 SHOWS A MASONRY WALL BETWEEN THE
 FRONT PART OF THE HOUSE AND THE REAR PART OF THE HOUSE.
 ROOF FRAMING PLAN ON SHEET S-2 DOESN'T SPECIFY THE BEAM
 SUPPORTING THE MASONRY WALL.
 ROOF FRAMING PLAN DOESN'T SHOW HOW THE TWO REAR GABLE
 END ROOFS ARE SUPPORTED AT THE INTERSECTION OF BOTH
 ROOFS.
 FRONT PORCH WOOD BEAM SIZE AND ROOF RAFTERS SIZE
 SPECIFIED ON THE ROOF FRAMING PLAN AND WOOD BEAM
 SPECIFIED ON SECTION 2 ON SHEET S-3 DON'T MATCH.
 SECTION 2 ON SHEET S-3 SHOWS OUTLOOKERS IN THE MIDDLE
 MASONRY WALL. THE OUTLOOKERS ARE ON THE OTHER SIDE OF
 THE SECTION BY THE GABLE END AREA. REVISE/CLARIFY WALL
 SECTION AS REQUIRED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 INFORMATION SHOWN ON THE TYPICAL WALL SECTION ON SHEET
 A-1 DOESN'T MATCH INFORMATION SHOWN ON OTHER PLANS AND
 SECTIONS. REVISE AS REQUIRED TO MATCH TO AVOID MORE
 CONFLICTS/DELAYS. ROOF SHEATHING SPECIFICATIONS DON'T
 MATCH SPECIFICATIONS SHOWN ON SHEET S-5. FOOTING SIZE
 DOESN'T MATCH FOUNDATION PLAN. ATTIC INSULATION DOESN'T
 MATCH. ETC.
 NOTE: ENGINEER TO COORDINATE ALL PLANS, SECTIONS AND
 SPECIFICATIONS TO AVOID MORE CONFLICTS AND DELAYS.
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SECTION 2 ON SHEET S-3 SHOWS STEEL COLUMNS BELOW GRADE.
 THIS INFORMATION DOESN'T MATCH INFORMATION SHOWN ON THE
 FOUNDATION PLAN. FOUNDATION PLAN SHOWS A KNEE WALL.
 ALSO, THERE ARE NO DETAIL/SPECIFICATIONS SHOWING HOW
 THE STEEL COLUMNS AND CONNECTIONS ARE PROTECTED AGAINST
 RUST/DETERIORATION.
  
 ORIGINAL COMMENT:
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 BUCK DETAIL ON SHEET A1 DOESN'T PROVIDE THE STRUCTURAL
 BUCK SPECIFICATIONS AS REQUESTED AND DOESN'T SEEM TO
 APPLY TO THIS JOB.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 A)OK. ROOF SHINGLES FL31588-R2.
  
 ORIGINAL COMMENT:
 D)HARDIEBOARD SIDING. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL. NEED MIAMI DADE NOA OR COMPLETE
 FLORIDA PRODUCT APPROVAL.
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL NUMBER UPLOADED TO PROJECTDOX
 DOESN'T MATCH FLORIDA PRODUCT APPROVAL NUMBER NAMED IN
 PROJECTDOX SUPPORTING DOCUMENTS. ONE OF THEM IS
 FL13223-R7 AND THE OTHER ONE IS FL13192.2. REVISE AS
 REQUIRED TO MATCH.
 NOTE: WHEN RESUBMITTING PLEASE UPLOAD THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND INSTALLATION
 INSTRUCTION ON THE SAME FILE. DON'T SPLIT THEM INTO TWO
 SEPARATE FILES.
  
 ORIGINAL COMMENT:
 E) SINGLE HUNG WINDOWS. NEW COMMENT BASED ON REVISED
 PLANS. PROVIDE PRODUCT APPROVAL FOR SINGLE HUNG WINDOW
 SIZE SPECIFIED ON PLANS FO WINDOW A. NEW 72"W X 52"H
 SINGLE HUNG WINDOW.
  
 RESPONSE:
 REPEAT COMMENT. NOA SUBMITTED DOESN'T COVER 72" WIDE
 WINDOW. NEED TO PROVIDE PRODUCT APPROVAL THAT COVERS
 THIS WINDOW SIZE AS SPECIFIED ON PLANS.
  
 F) PROVIDE PRODUCT APPROVAL FOR SHINGLES UNDERLAYMENT
 SPECIFIED ON TYPICAL WALL SECTION ON SHEET A-1.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 14- PROVIDE COMPLETE WALL SECTION FROM FOUNDATION
 THROUGH ROOF AS REQUIRED BY SEC. 107.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISE NEW TYPICAL WALL SECTION ON SHEET A1:
 A) FOOTING SIZE DOESN'T MATCH SIZE SPECIFIED ON THE
 FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C)ROOF SHEATHING NAILING SPECIFICATIONS ARE NOT CLEAR.
 NOTE: SEE SECTION R803.2.3.1 FBC-RESIDENTIAL AND FIGURE
 R803.2.3.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ROOD SHEATHING SPECIFICATIONS ON TYPICAL WALL SECTION
 AND SPECIFICATIONS ON SHEET S-5 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH. NOTE: SEE SECTION R803.2.3.1
 FBC-RESIDENTIAL AND FIGURE R803.2.3.1 FBC-RESIDENTIAL.
  
 D) ROOF INSULATION ON TYPICAL WALL SECTION AND
 SPECIFICATIONS ON SHEET S-3 DON'T MATCH. REVISE AS
 REQUIRED TO MATCH.
  
  
 ORIGINAL COMMENT:
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FRONT AND BACK GUARDRAILS SHOWING
 COMPLIANCE WITH SEC. R312.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. DESIGN INFORMATION NEEDS
 TO BE SHOWN ON PLANS BY THE DESIGNER OF RECORD. PRODUCT
 APPROVALS OR SHOP DRAWINGS ARE DEFERRED SUBMITTALS JUST
 TO CONFIRM THE DESIGN INTENT OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-10-21 Cont ID  
Sent By jgomez Date 2021-10-21 Time 15:16 Rev Time 0.00
Received By jgomez Date 2021-10-21 Time 09:29 Sent To  
Notes
2021-10-21 15:18:16NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORRCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
 ORIGINAL COMMENT:
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 A) PROVIDE DIMENSIONS ON TYPICAL WET SWALE CROSS
 SECTION. SPECIFY DEPTH OF SWALE, DISTANCE FROM
 BUILDING, ETC. SEC. 1072.1 CITY AMENDMENTS.
 B) PROVIDE TRENCH WITH GRAVEL DETAIL #1 AS SHOWN ON
 DRAINAGE PLAN ALONG PERIMETER OF LOT. DETAIL WAS NOT
 GIVEN. SEC. 107.2.1 CITY AMENDMENTS.
  
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 BASED ON THE ROOF FRAMING PLAN, THE LOCATION OF THE
 ATTIC ACCESS DOESN'T PROVIDE THE CLEARANCE REQUIRED BY
 SEC. R807 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISED ROOF FRAMING PLAN IS INCOMPLETE. IT IS MISSING
 THE ROOF AT THE ENTRY PORCH. THERE IS NOT CORRELATION
 BETWEEN THE WOOD BEAM SCHEDULES AND THE ROOF FRAMING
 PLAN. THERE IS NOT TRUSS CONNECTOR SCHEDULE. THERE IS
 NOT INFORMATION ABOUT THE GABLE END BEAMS. ARE THESE
 CONCRETE RAKED BEAMS?. THERE IS NOT INFORMATION FOR
 PORCH BEAMS, COLUMNS, ALL STRUCTURAL CONNECTORS OF ALL
 STRUCTURAL MEMBERS (ROOF TRUSSES, BEAMS AND COLUMNS).
 NEW ROOF FRAMING PLAN SHOWS TWO GABLE END ROOFS
 INTERSECTING ON THE REAR OF THE HOUSE. SEE REAR
 ELEVATION ON SHEET A-2. NEED TO PROVIDE DETAILS AND
 SPECIFICATIONS FOR CRICKET CONSTRUCTION IN THIS AREA.
 NEED TO PROVIDE COMPLETE ROOF FRAMING PLAN WITH ALL THE
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ENGINEER'S RESPONSE SAID SEE REVISED SHEET S-3.
 SECTIONS 1 AND 2 ON SHEET S-3 DON'T MATCH REVISED ROOF
 FRAMING PLAN. SEE NEW ROOF PROFILE. THERE ARE NO
 SPECIFICATIONS FOR THE ROOF SHEATHING. PORCH
 CONSTRUCTION DOESN'T MATCH PORCH SHOWN ON THE EXTERIOR
 ELEVATIONS AND NEEDS MORE INFORMATION. FRAMING AT GABLE
 ENDS IS NOT CLEAR. HOW THE GABLE END IS GOING TO BE
 BUILT. SPECIFY ALL GABLE FRAMING MEMBERS AND
 CONNECTORS. NEED COLUMNS CONNECTOR AT TOP AND BOTTOM,
 WOOD BEAM SHOWN DON'T REFLECT (2)2X12 WOOD BEAM. DETAIL
 SHOWS FOUR 2X12'S. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: ENGINEER OF RECORD TO COORDINATE ALL PLANS,
 DETAILS AND SPECIFICATIONS TO AVOID MORE CONFLICTS AND
 DELAYS.
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. SEE RESPONSE TO ITEM #6 ABOVE.
  
 ORIGINAL COMMENT:
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 ORIGINAL COMMENT:
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NOA 19-0617.05 SUBMITTED NOW IS NOT FOR SHINGLES. WRONG
 NOA AGAIN.
  
 ORIGINAL COMMENT:
 D)HARDIEBOARD SIDING. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL. NEED MIAMI DADE NOA OR COMPLETE
 FLORIDA PRODUCT APPROVAL.
  
 RESPONSE:
 NOA 20-0730.05 SUBMITTED IS FOR INSTALLATION TO WOOD
 FRAMED BUILDINGS. THIS HOUSE IS CONCRETE BLOCK. NEED
 PRODUCT APPROVAL FOR INSTALLATION ON CONCRETE BLOCK
 CONSTRUCTION.
  
 E) SINGLE HUNG WINDOWS. NEW COMMENT BASED ON REVISED
 PLANS. PROVIDE PRODUCT APPROVAL FOR SINGLE HUNG WINDOW
 SIZE SPECIFIED ON PLANS FO WINDOW A. NEW 72"W X 52"H
 SINGLE HUNG WINDOW.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS
 (INCLUDING THE HARDIEBOARD SIDING) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 14- PROVIDE COMPLETE WALL SECTION FROM FOUNDATION
 THROUGH ROOF AS REQUIRED BY SEC. 107.5.3 CITY
 AMENDMENTS.
  
 RESPONSE:
 REVISE NEW TYPICAL WALL SECTION ON SHEET A1:
 A) FOOTING SIZE DOESN'T MATCH SIZE SPECIFIED ON THE
 FOUNDATION PLAN. SEC. 107.2.1 CITY AMENDMENTS.
  
 B)ROOFING COVER AND UNDERLAYMENT SPECIFIED IS NOT
 CLEAR. THESE SPECIFICATIONS ARE NOT FOR SHINGLES.
 COORDINATE WITH PRODUCT APPROVAL COMMENT ABOVE. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C)ROOF SHEATHING NAILING SPECIFICATIONS ARE NOT CLEAR.
 COORDINATE WITH ITEM #7 ABOVE. NOTE: SEE TABLE
 R803.2.3.1 FBC-RESIDENTIAL FOR MINIMUM ROOF SHEATHING
 ATTACHMENT.
  
 NEW COMMENTS:
 16- FOUNDATION PLAN ON SHEET S1:
 A)MISSING THE FOOTING FOR THE FRONT AND REAR PORCHES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 B)FOUNDATION PLANS DOESN'T SHOW THE FOOTINGS SHOWN ON
 THE FOOTING SCHEDULE. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF FRONT AND REAR STAIRWAYS SHOWING
 COMPLIANCE WITH SEC. R311.7 FBC-RESIDENTIAL.
  
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FRONT AND BACK GUARDRAILS SHOWING
 COMPLIANCE WITH SEC. R312.1 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By jgomez Date 2021-08-17 Time 13:09 Rev Time 0.00
Received By jgomez Date 2021-08-17 Time 10:40 Sent To  
Notes
2021-08-17 13:10:40NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
 NOTE:
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
  
 ORIGINAL COMMENT:
 1-ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 C)PROVIDE CORRECT AND COMPLETE INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 839 4TH STREET NOT 837 4TH
 STREET. PROVIDE OWNER'S NAME. PROVIDE BUILDER'S NAME.
 PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 D)ITEM #8(A) ON PAGE 1 OF 4 SPECIFIES R-5 SLAB-ON-GRADE
 EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE
 INSULATION. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 E)ITEM #9(A) ON PAGE 1 OF 4 SPECIFIES R-4.5 EXTERIOR
 INSULATION ON CONCRETE BLOCK. PLANS DON'T SPECIFY
 EXTERIOR INSULATION ON THE CONCRETE BLOCK. THE
 INSULATION IS ON THE INTERIOR SIDE. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING R-VALUE
 SPECIFIED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 F)ITEM #10(A) ON PAGE 1 OF 4 SPECIFIES R-19 UNDER ATTIC
 INSULATION. THIS DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 G)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 NEEDS TO BE
 COORDINATED WITH PLANS. PLANS ARE NOT CLEAR ON WHAT
 ROOFING MATERIAL IS GOING TO BE INSTALLED BUT IT
 DOESN'T SPECIFY FLAT TILE OR SLATE. COORDINATE WITH
 ENGINEER PLANS AND REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 H)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. PLANS
 DON'T SHOW ANY 1/300 VENT RATIO. TYPICALLY, THE RATIO
 IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. NOTE: ENGINEER OF RECORD NEEDS TO
 REVIEW/APPROVE THEM PRIOR TO SUBMITTAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 I)DOOR TYPE INFORMATION SPECIFIED ON PAGE 3 OF 4 IS
 INCORRECT. ACCORDING TO PLANS AND PRODUCT APPROVALS
 SUBMITTED THE ENTRY DOOR AND THE BEDROOM #3 DOORS ARE
 ALUMINUM DOORS WITH GLAZING. GLASS IN THESE DOORS NEED
 TO BE INCLUDED ON THE GLASS CALCULATIONS AS REQUIRED BY
 SEC. R405.5.3.1 AND SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT.
  
 J)WINDOWS INFORMATION SPECIFIED ON 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOW AREA AND WINDOW OVERHANG DEPTH
 AND SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT.
  
 NEW COMMENT:
 K)FLOOR PLAN WAS REVISED. NEW ENERGY CALCULATIONS NEED
 TO BE DONE BASED ON THE NEW FLOOR PLAN. COORDINATE ALL
 THE INFORMATION ACCORDINGLY.
  
 ORIGINAL COMMENT:
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 4-PLANS SUBMITTED DON'T SPECIFY WHAT IS THE ROOFING
 MATERIAL. IS IT SHINGLES?, TILE?. IF USING SHINGLES ,
 THEN A ROOF PITCH OF 2:12 TO LESS THAN 4:12 REQUIRES
 TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS FOR
 THE TWO LAYERS OF UNDERLAYMENT. ALSO, PROVIDE
 SPECIFICATIONS FOR THE FLAT ROOF.
  
 RESPONSE:
 PLANS SUBMITTED STILL DON'T SPECIFY THE ROOF PITCH.
 SPECIFY THE ROOF SLOPE ON ALL ROOF AREAS SHOWN ON THE
 REVISED PLANS.
  
  
 5- OK. NO FLAT ROOFS ON REVISED PLANS.
  
 ORIGINAL COMMENT:
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 ARCHITECTURAL PLANS WERE REVISED. NEW FLOOR
 PLANS/ELEVATIONS WERE SUBMITTED BUT NONE OF THE
 STRUCTURAL PLANS WERE REVISED. REVISE ALL STRUCTURAL
 PLANS AND COORDINATE ACCORDINGLY.
  
 ORIGINAL COMMENT:
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 10- REVISE THE ADDRESS INFORMATION ON ALL DRAWINGS,
 CALCULATIONS, ENERGY CALCULATIONS, ETC. SUBMITTED TO
 AVOID CONFLICTS/DELAYS. THERE ARE TWO STRUCTURES IN
 THIS LOT. 839 4TH STREET IS THE ADDRESS FOR THE REAR
 STRUCTURE. THIS PERMIT APPLICATION IS FOR THE REAR
 STRUCTURE ONLY. 837 4TH STREET IS THE MAIN HOUSE. THIS
 WILL FACILITATE INSPECTIONS AND RECORDS KEEPING.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT.
  
 ORIGINAL COMMENT:
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NOA 19-0313.03 SUBMITTED IS FOR FLAT ROOFS OVER
 LIGHTWEIGHT CONCRETE DECKS. THIS IS INCORRECT. PROVIDE
 CORRECT SHINGLES PRODUCT APPROVAL.
  
 B)OK. REVISED PLANS DON'T SHOW FLAT ROOFS NOW.
  
 C)SINGLE HUNG WINDOWS A SPECIFIED ON REVISED PLANS.
  
 D)HARDIEBOARD SIDING. INFORMATION SUBMITTED IS NOT A
 PRODUCT APPROVAL. NEED MIAMI DADE NOA OR COMPLETE
 FLORIDA PRODUCT APPROVAL.
  
 NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 HORIZONTAL SLIDER WINDOWS IF THEY ARE NOT SPECIFIED ON
 THE REVISED PLANS?
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS
 (INCLUDING THE HARDIEBOARD SIDING) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 NEW COMMENTS BASED ON REVISED PLANS.
 13- SINGLE HUNG WINDOW SIZE SPECIFIED FOR BEDROOM #3
 DOESN'T COMPLY WITH THE MINIMUM CLEAR OPENING HEIGHT
 REQUIRED BY SEC. R310.2.1 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 14- PROVIDE COMPLETE WALL SECTION FROM FOUNDATION
 THROUGH ROOF AS REQUIRED BY SEC. 107.5.3 CITY
 AMENDMENTS.
  
 15- REVISED ELEVATIONS SHOW WHAT LOOKS LIKE CRAWL SPACE
 VENTILATION. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS. NOTE: STRUCTURAL PLANS WERE NOT
 REVISED. IT IS NOT KNOW IF THE FLOOR IS GOING TO BE
 WOOD OR CONCRETE SLAB.
 CRAWL SPACE VENTILATION WITH FLOOR JOISTS NEED TO
 COMPLY WITH SEC. R409 FBC-RESIDENTIAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By jgomez Date 2021-02-17 Time 13:20 Rev Time 0.00
Received By jgomez Date 2021-02-17 Time 13:20 Sent To  
Notes
2021-02-17 13:22:11NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20121077
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A) THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 C)PROVIDE CORRECT AND COMPLETE INFORMATION ON TOP OF
 FORM. CORRECT ADDRESS IS 839 4TH STREET NOT 837 4TH
 STREET. PROVIDE OWNER'S NAME. PROVIDE BUILDER'S NAME.
 PERMITTING OFFICE IS WEST PALM BEACH NOT PALM BEACH.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D)ITEM #8(A) ON PAGE 1 OF 4 SPECIFIES R-5 SLAB-ON-GRADE
 EDGE INSULATION. PLANS DON'T SPECIFY ANY SLAB EDGE
 INSULATION. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #9(A) ON PAGE 1 OF 4 SPECIFIES R-4.5 EXTERIOR
 INSULATION ON CONCRETE BLOCK. PLANS DON'T SPECIFY
 EXTERIOR INSULATION ON THE CONCRETE BLOCK. THE
 INSULATION IS ON THE INTERIOR SIDE. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING R-VALUE
 SPECIFIED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)ITEM #10(A) ON PAGE 1 OF 4 SPECIFIES R-19 UNDER ATTIC
 INSULATION. THIS DOESN'T MATCH PLANS. SEE PLANS AND
 REVISE AS REQUIRED TO MATCH, INCLUDING.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 NEEDS TO BE
 COORDINATED WITH PLANS. PLANS ARE NOT CLEAR ON WHAT
 ROOFING MATERIAL IS GOING TO BE INSTALLED BUT IT
 DOESN'T SPECIFY FLAT TILE OR SLATE. COORDINATE WITH
 ENGINEER PLANS AND REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 4. PLANS
 DON'T SHOW ANY 1/300 VENT RATIO. TYPICALLY, THE RATIO
 IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. OR
 PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. NOTE: ENGINEER OF RECORD NEEDS TO
 REVIEW/APPROVE THEM PRIOR TO SUBMITTAL.
  
 I)DOOR TYPE INFORMATION SPECIFIED ON PAGE 3 OF 4 IS
 INCORRECT. ACCORDING TO PLANS AND PRODUCT APPROVALS
 SUBMITTED THE ENTRY DOOR AND THE BEDROOM #3 DOORS ARE
 ALUMINUM DOORS WITH GLAZING. GLASS IN THESE DOORS NEED
 TO BE INCLUDED ON THE GLASS CALCULATIONS AS REQUIRED BY
 SEC. R405.5.3.1 AND SEC. R405.5.3.3 FBC-ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 J)WINDOWS INFORMATION SPECIFIED ON 3 OF 4 DOESN'T MATCH
 PLANS. REVISE THE WINDOW AREA AND WINDOW OVERHANG DEPTH
 AND SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 2-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3-SPECIFY ATTIC ACCESS SIZE AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 4-PLANS SUBMITTED DON'T SPECIFY WHAT IS THE ROOFING
 MATERIAL. IS IT SHINGLES?, TILE?. IF USING SHINGLES ,
 THEN A ROOF PITCH OF 2:12 TO LESS THAN 4:12 REQUIRES
 TWO LAYERS OF UNDERLAYMENT AS REQUIRED BY SEC. R905.2.2
 FBC-RESIDENTIAL. PROVIDE SPECIFICATIONS ON PLANS FOR
 THE TWO LAYERS OF UNDERLAYMENT. ALSO, PROVIDE
 SPECIFICATIONS FOR THE FLAT ROOF.
  
 5- SPECIFY ROOF PITCH OF THE FLAT ROOF ON THE FRONT
 PORCH. SEE SEC. R905.9.1 OR 905.11.1 FBC RESIDENTIAL.
  
 6- BEAM SCHEDULE ON SHEET S-2 ONLY SPECIFIES B-1 BEAM.
 IT DOESN'T SPECIFY THE RAKE BEAM SHOWN ON SHEET S-4.
 REVISE AS REQUIRED TO CLARIFY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PLANS DON'T PROVIDE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE, THICKNESS AND ROOF SHEATHING
 FASTENING AS REQUIRED BY SEC. R803.2.3.1
 FBC-RESIDENTIAL.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STEEL COLUMNS SHOWN ON THE FRONT PORCH. SPECIFY TOP AND
 BOTTOM CONNECTORS AND FURRING DETAILS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAIL.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 10- REVISE THE ADDRESS INFORMATION ON ALL DRAWINGS,
 CALCULATIONS, ENERGY CALCULATIONS, ETC. SUBMITTED TO
 AVOID CONFLICTS/DELAYS. THERE ARE TWO STRUCTURES IN
 THIS LOT. 839 4TH STREET IS THE ADDRESS FOR THE REAR
 STRUCTURE. THIS PERMIT APPLICATION IS FOR THE REAR
 STRUCTURE ONLY. 837 4TH STREET IS THE MAIN HOUSE. THIS
 WILL FACILITATE INSPECTIONS AND RECORDS KEEPING.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 B) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13-VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $120,957. THE PERMIT FEE BALANCE IS
 $2456.00.
  
 14- ENGINEER TO FOLLOW UP WITH THE FLORIDA BUILDING
 CODE TRAINING REQUIREMENT. SEE BELOW:
  
 FLORIDA BUILDING CODE TRAINING FOR ENGINEERS(471.0195
 F.S.)
  
 471.0195 FLORIDA BUILDING CODE TRAINING FOR ENGINEERS.
 ALL LICENSEES ACTIVELY PARTICIPATING IN THE DESIGN OF
 ENGINEERING WORKS OR SYSTEMS IN CONNECTION WITH
 BUILDINGS, STRUCTURES, OR FACILITIES AND SYSTEMS
 COVERED BY THE FLORIDA BUILDING CODE SHALL TAKE
 CONTINUING EDUCATION COURSES AND SUBMIT PROOF TO THE
 BOARD, AT SUCH TIMES AND IN SUCH MANNER AS ESTABLISHED
 BY THE BOARD BY RULE, THAT THE LICENSEE HAS COMPLETED
 ANY SPECIALIZED OR ADVANCED COURSES ON ANY PORTION OF
 THE FLORIDA BUILDING CODE APPLICABLE TO THE LICENSEE'S
 AREA OF PRACTICE. THE BOARD SHALL RECORD REPORTED
 CONTINUING EDUCATION COURSES ON A SYSTEM EASILY
 ACCESSED BY CODE ENFORCEMENT JURISDICTIONS FOR
 EVALUATION WHEN DETERMINING LICENSE STATUS FOR PURPOSES
 OF PROCESSING DESIGN DOCUMENTS. LOCAL JURISDICTIONS
 SHALL BE RESPONSIBLE FOR NOTIFYING THE BOARD WHEN
 DESIGN DOCUMENTS ARE SUBMITTED FOR BUILDING
 CONSTRUCTION PERMITS BY PERSONS WHO ARE NOT IN
 COMPLIANCE WITH THIS SECTION. THE BOARD SHALL TAKE
 APPROPRIATE ACTION AS PROVIDED BY ITS RULES WHEN SUCH
 NONCOMPLIANCE IS DETERMINED TO EXIST.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-26 Cont ID  
Sent By jleahy Date 2021-10-26 Time 14:03 Rev Time 0.00
Received By jleahy Date 2021-10-26 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-06 Cont ID  
Sent By jleahy Date 2021-08-06 Time 08:11 Rev Time 0.00
Received By jleahy Date 2021-08-06 Time 07:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-02-01 Cont ID  
Sent By equinone Date 2021-02-01 Time 16:03 Rev Time 0.00
Received By equinone Date 2021-02-01 Time 14:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2022-12-28 Cont ID  
Sent By fmittner Date 2022-12-28 Time 12:11 Rev Time 0.00
Received By fmittner Date 2022-12-28 Time 12:11 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2022-06-06 Cont ID  
Sent By amhamilt Date 2022-06-06 Time 16:32 Rev Time 0.00
Received By amhamilt Date 2022-06-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2021-10-21 Cont ID  
Sent By amhamilt Date 2021-10-21 Time 08:42 Rev Time 0.00
Received By amhamilt Date 2021-10-21 Time 08:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-09-02 Cont ID  
Sent By fmittner Date 2021-09-02 Time 12:02 Rev Time 0.00
Received By fmittner Date 2021-09-02 Time 12:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-01-28 Cont ID  
Sent By aborngra Date 2021-01-28 Time 12:37 Rev Time 0.00
Received By aborngra Date 2021-01-27 Time 16:54 Sent To  
Notes
2021-01-28 12:37:21THIS PROJECT HAS TWO AVENUES TO PROCEED:
 OPTION A:
 1. A CERTIFICATE OF APPROPRIATENESS (COA) APPLICATION
 IS REQUIRED FOR NEW CONSTRUCTION WITHIN THE NORTHWEST
 HISTORIC DISTRICT. PLEASE EMAIL STAFF AT
 [email protected] TO REQUEST A COPY OF THE
 APPLICATION. INCLUDE ALL APPLICATION MATERIALS REQUIRED
 UNDER ?NEW CONSTRUCTION?. THE NEXT APPLICATION DEADLINE
 IS FEBRUARY 17, 2021 FOR THE MARCH 23, 2021 HISTORIC
 PRESERVATION BOARD MEETING.
  
 THE APPLICATION FEE IS $350.00 + $0.01 PER SQUARE FOOT.
 STAFF RECOMMENDS ADDRESSING THE FOLLOWING COMMENTS
 BEFORE SUBMITTING A COA APPLICATION. ADDITIONAL
 COMMENTS DURING STAFF?S REPORT OR BY THE HISTORIC
 PRESERVATION MAY NEED TO BE ADDRESSED PRIOR TO A PERMIT
 BEING ISSUED.
  
 1. THE TOTAL FLOOR AREA OF ALL ROOFED ACCESSORY
 BUILDINGS ON A PROPERTY SHALL NOT EXCEED 75 PERCENT OF
 THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A
 MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET. (SEC.
 94-304(B)(1)). SEE SEC. 94-86 FOR HISTORIC RESIDENTIAL
 DISTRICT DEFINITIONS FOR HOW TO CALCULATE LOT COVERAGE.
 2. REVISE ALL WINDOWS TO BE A SASH WINDOW WITH
 TRADITIONAL WINDOW OPENINGS.
 3. REVISE ALL DOOR OPENINGS TO BE A TRADITIONAL SINGLE
 OR PAIRED FRENCH DOOR.
 4. REVISE RAILINGS TO BE VERTICAL TO EMPHASIZE A
 TRADITIONAL RAILING.
 5. REVISE STUCCO EXTERIOR TO HAVE SIDING. THE SIDING
 MAY BE WOOD, BORAL TRUEXTERIOR, OR HARDIEBOARD SMOOTH
 IN A CHANNEL BEVEL PROFILE TO MATCH THE PREVIOUS
 CONTRIBUTING ACCESSORY STRUCTURE.
 6. REVISE ALL WINDOW FRAMES TO HAVE WHITE FRAMES AND
 CLEAR GLASS OR CLEAR GLASS WITH LOW-E COATING.
 7. REVISE THE FRONT PORCH POST TO BE WOOD OR WOOD
 ALTERNATE PRODUCT SUCH AS TREX.
 8. REVISE THE REAR PORCH TO HAVE A WOOD LIKE MASSING
 FOR THE COLUMNS.
 9. INDICATE ROOFING MATERIAL.
  
 OPTION B:
  
 STAFF RECOMMENDS THIS OPTION.
  
 REVISE THE PLANS TO BUILD A MODIFIED RECONSTRUCTION OF
 THE STRUCTURE THAT WAS PREVIOUSLY CONTRIBUTING. A
 MODIFIED RECONSTRUCTION MAY BE BUILT WITH CMU BLOCKS
 AND HAVE SIDING WITH BORAL TRUEXTERIOR OR HARDIEBOARD
 SMOOTH. THE ENTIRE FRONT PORCH MAY BE A WOOD ALTERNATE
 PRODUCT SUCH AS TREX.
  
 IF THIS APPROACH IS SELECTED, STAFF WILL SUPPORT AN AD
 VALOREM TAX EXEMPTION. THE AD VALOREM TAX EXEMPTION
 PROGRAM:
 THE CITY OF WEST PALM BEACH AND PALM BEACH COUNTY HAVE
 PASSED PROPERTY TAX ABATEMENT EXEMPTION ORDINANCES,
 WHICH AUTHORIZE GRANTING AN EXEMPTION FROM INCREASES TO
 AD VALOREM TAXES FOR QUALIFIED IMPROVEMENTS TO
 PROPERTIES LISTED IN THE WEST PALM BEACH REGISTER OF
 HISTORIC PLACES. THIS EXEMPTION DOES NOT APPLY TO
 ASSESSED LAND VALUE, ONLY TO THE VALUE OF THE
 IMPROVEMENTS.
  
 THE CITY AND THE COUNTY WILL PROCESS THE APPLICATION
 FOLLOWING MUTUALLY ESTABLISHED PROCEDURES THROUGH BOTH
 THE CITY AND COUNTY COMMISSIONS. ONCE THE HISTORIC
 PRESERVATION BOARD HAS APPROVED THE WORK, THE OWNER HAS
 TWO (2) YEARS TO COMPLETE THE IMPROVEMENTS.
  
 THIS PROGRAM PROVIDES AN ABATEMENT OF TAX INCREASES ON
 THE IMPROVEMENTS TO THE PROPERTY FOR A TEN (10) YEAR
 PERIOD. THE ABATEMENT IS CONVEYED THROUGH A COVENANT
 THAT ACCOMPANIES THE DEED OF THE PROPERTY AND MAY BE
 TRANSFERRED TO FUTURE OWNERS DURING THE ABATEMENT TIME
 PERIOD.
  
 A CERTIFICATE OF APPROPRIATENESS (COA) APPLICATION WILL
 BE REQUIRED IN ADDITION TO AN AD VALOREM
 PRECONSTRUCTION APPLICATION. ALL MATERIALS REQUIRED
 UNDER THE ?AD VALOREM TAX EXEMPTION? WILL BE REQUIRED
 IN ADDITION TO ROOF PLAN, SECTIONS, PROJECT DATA TABLE,
 AND NOTIFICATION. THE APPLICATION FEE IS $250.00. THE
 NEXT APPLICATION DEADLINE IS FEBRUARY 17, 2021 FOR THE
 MARCH 23, 2021 HISTORIC PRESERVATION BOARD MEETING.
  
 AN AD VALOREM APPLICATION CAN BE COMBINED FOR ONE (1)
 APPLICATION FOR BOTH STRUCTURES ON THE PROPERTY ONLY IF
 DOING THE MODIFIED RECONSTRUCTION OPTION. IF NOT, A
 SEPARATE APPLICATION WILL BE REQUIRED FOR THE NEW
 CONSTRUCTION ACCESSORY STRUCTURE AND THE AD VALOREM TAX
 EXEMPTION ON THE PRIMARY STRUCTURE.
  
 AARON BORNGRABER
 HISTORIC PRESERVATION PLANNER | DEVELOPMENT SERVICES
 PLANNING DIVISION
 [email protected] | OFFICE: 561.822.1428 | TTY:
 800.955.8771
 401 CLEMATIS STREET | P.O BOX 3147 | WEST PALM BEACH,
 FL 33402
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 18:13 Rev Time 0.00
Received By jgomez Date 2023-06-28 Time 09:06 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 14:09 Rev Time 0.00
Received By jgomez Date 2023-02-16 Time 16:24 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-29 Cont ID  
Sent By aoliver Date 2022-12-29 Time 09:07 Rev Time 0.00
Received By aoliver Date 2022-11-22 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-12 Cont ID  
Sent By jgomez Date 2022-07-12 Time 17:40 Rev Time 0.00
Received By jgomez Date 2022-05-25 Time 08:37 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-26 Cont ID  
Sent By jleahy Date 2021-10-26 Time 14:03 Rev Time 0.00
Received By jleahy Date 2021-10-01 Time 06:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-02 Cont ID  
Sent By lmarchan Date 2021-09-02 Time 16:54 Rev Time 0.00
Received By lmarchan Date 2021-07-28 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-17 Cont ID  
Sent By jgomez Date 2021-02-17 Time 13:26 Rev Time 0.00
Received By jgomez Date 2021-01-20 Time 12:05 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 17:17 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 17:17 Sent To  
Notes
2023-07-21 17:17:38PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 14:14 Rev Time 0.00
Received By jgomez Date 2023-03-03 Time 14:14 Sent To  
Notes
2023-03-03 14:15:03PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 16:49 Rev Time 0.00
Received By jgomez Date 2022-12-27 Time 16:49 Sent To  
Notes
2022-12-27 16:49:52PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By jgomez Date 2021-02-17 Time 10:49 Rev Time 0.00
Received By jgomez Date 2021-02-17 Time 10:48 Sent To  
Notes
2021-02-17 10:50:09PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-10-04 Cont ID  
Sent By medwards Date 2021-10-04 Time 10:00 Rev Time 0.00
Received By medwards Date 2021-10-04 Time 10:00 Sent To  
Notes
2021-10-04 10:01:04APPROVED WITH PRIVISO:
 THE DRYER EXHAUST MUST MEET FBC RES M1502
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-04 Cont ID  
Sent By hmoser Date 2021-08-04 Time 14:57 Rev Time 0.00
Received By hmoser Date 2021-08-04 Time 13:59 Sent To  
Notes
2021-08-04 14:57:27PLAN DENIED
 REFER TO SECTION M1401.3 EQUIPMENT AND APPLIANCE
 SIZING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-27 Cont ID  
Sent By hmoser Date 2021-01-27 Time 10:18 Rev Time 0.00
Received By hmoser Date 2021-01-27 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-10-18 Cont ID  
Sent By abelisle Date 2021-10-18 Time 06:05 Rev Time 0.00
Received By abelisle Date 2021-10-18 Time 05:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-03 Cont ID  
Sent By lcrespo Date 2021-08-03 Time 18:20 Rev Time 0.00
Received By lcrespo Date 2021-08-03 Time 18:20 Sent To  
Notes
2021-08-03 18:21:1108/03/21 2ND REQUEST PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL PLUMBING.
  
 2. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 3. ON SHEET P-1 THE DRAIN ON THE STACK LOOKS LIKE A
 COMBINATION FITTING, AND IT IS NOT ALLOWED ON A
 HORIZONTAL DRAIN. YOU CAN PUT A NOT OR CHANGE THE
 FITTING TO REFLECT A SANITARY FITTING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-21 Cont ID  
Sent By lcrespo Date 2021-01-21 Time 17:40 Rev Time 0.00
Received By lcrespo Date 2021-01-21 Time 17:40 Sent To  
Notes
2021-01-21 17:40:4501/21/21 PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL PLUMBING.
  
 2. THIS IS A MULTI-FAMILY DWELLING, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE NEEDED FOR THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM.
  
 3. ON SHEET P-1 THE DRAIN ON THE STACK LOOKS LIKE A
 COMBINATION FITTING, AND IT IS NOT ALLOWED ON A
 HORIZONTAL DRAIN. YOU CAN PUT A NOT OR CHANGE THE
 FITTING TO REFLECT A SANITARY FITTING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 16:53 Rev Time 0.00
Received By jgomez Date 2022-12-27 Time 16:51 Sent To  
Notes
2022-12-27 16:54:041-ROOF SHINGLES FL31588-R2.
  
 2- SHINGLES UNDERLAYMENT NOA 21-1130.01

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2022-07-12 Cont ID  
Sent By jgomez Date 2022-07-12 Time 17:37 Rev Time 0.00
Received By jgomez Date 2022-07-12 Time 17:35 Sent To  
Notes
2022-07-12 17:37:29ROOFING REVIEW:
  
 1 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 ORIGINAL COMMENT:
 A)OK. ROOF SHINGLES FL31588-R2.
  
 B) PROVIDE PRODUCT APPROVAL FOR SHINGLES UNDERLAYMENT
 SPECIFIED ON TYPICAL WALL SECTION ON SHEET A-1.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS
 (INCLUDING THE HARDIEBOARD SIDING) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2021-10-21 Cont ID  
Sent By jgomez Date 2021-10-21 Time 15:29 Rev Time 0.00
Received By jgomez Date 2021-10-21 Time 15:29 Sent To  
Notes
2021-10-21 15:30:10ROOFING REVIEW:
  
 1 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
  
 ORIGINAL COMMENT:
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NOA 19-0617.05 SUBMITTED NOW IS NOT FOR SHINGLES. WRONG
 NOA AGAIN.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS
 (INCLUDING THE HARDIEBOARD SIDING) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-08-17 Cont ID  
Sent By jgomez Date 2021-08-17 Time 13:24 Rev Time 0.00
Received By jgomez Date 2021-08-17 Time 13:24 Sent To  
Notes
2021-08-17 13:24:31ROOFING SECOND REVIEW:
  
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NOA 19-0313.03 SUBMITTED IS FOR FLAT ROOFS OVER
 LIGHTWEIGHT CONCRETE DECKS. THIS IS INCORRECT. PROVIDE
 CORRECT SHINGLES PRODUCT APPROVAL.
  
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-02-17 Cont ID  
Sent By jgomez Date 2021-02-17 Time 13:22 Rev Time 0.00
Received By jgomez Date 2021-02-17 Time 13:22 Sent To  
Notes
2021-02-17 13:23:301- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ROOF MATERIAL FOR PITCHED ROOF AS SPECIFIED ON PLANS.
  
 B) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status P Date 2023-07-21 Cont ID  
Sent By jgomez Date 2023-07-21 Time 18:12 Rev Time 0.00
Received By jgomez Date 2023-07-21 Time 18:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2023-03-03 Cont ID  
Sent By jgomez Date 2023-03-03 Time 10:33 Rev Time 0.00
Received By jgomez Date 2023-03-03 Time 10:27 Sent To  
Notes
2023-03-03 10:28:12ENGINEER'S SELF CERTIFIED DIGITAL SIGNATURE
 1- DRAWINGS A1, S1, S2, S3 AND S5 HAVE ENGINEER'S
 SELF-CERTIFIED SIGNATURE. A THIRD PARTY CERTIFICATION
 IS REQUIRED.
 FAC 61G15-23.004.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-12-27 Cont ID  
Sent By jgomez Date 2022-12-27 Time 16:51 Rev Time 0.00
Received By jgomez Date 2022-12-27 Time 16:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-12 Cont ID  
Sent By jgomez Date 2022-07-12 Time 17:40 Rev Time 0.00
Received By jgomez Date 2022-07-12 Time 17:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-21 Cont ID  
Sent By jgomez Date 2021-10-21 Time 15:37 Rev Time 0.00
Received By jgomez Date 2021-10-21 Time 15:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-17 Cont ID  
Sent By jgomez Date 2021-08-17 Time 13:47 Rev Time 0.00
Received By jgomez Date 2021-08-17 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-17 Cont ID  
Sent By elevesqu Date 2021-02-17 Time 13:24 Rev Time 0.00
Received By jgomez Date 2021-02-17 Time 13:23 Sent To  
Notes
2021-02-01 16:47:27PLEASE SEE HISTORIC COMMENTS REGARDING ARCHITECTURE AND
 NECESSARY ACTIONS FOR APPROVAL
  
 LOT COVERAGE FOR THIS LOT IS MAXIMUM 30 PERCENT. PLEASE
 CLARIFY THE LOT COVERAGE BASED ON HISTORIC CALCULATIONS
 BELOW AND INCLUDE A TABLE BREAKING DOWN WHAT IS BEING
 COUNTED:
  
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE INCLUDES 100 PERCENT OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 ACCESSORY STRUCTURES SUCH AS SHEDS, GUEST HOUSES AND
 SECOND UNITS THAT ARE ROOFED AND ENCLOSED ON MORE THAN
 TWO SIDES WHETHER OR NOT THEY INCLUDE HABITABLE SPACE;
 ATTACHED AND DETACHED GARAGES;
 STAIRWAYS: THE GROUND FLOOR OF INTERIOR AND ROOFED
 EXTERIOR STAIRWAYS, ELEVATORS, ESCALATORS AND SIMILAR
 FEATURES. THE GROUND FLOOR AREA OF USABLE SPACES HAVING
 A 5' MINIMUM HEIGHT UNDER A RUN OF STAIRS SHALL BE
 COUNTED;
 UTILITY AREAS: THE GROUND FLOOR AREA OF LAUNDRY ROOMS,
 MECHANICAL ROOMS, CLOSETS, STORAGE ROOMS AND BUILT-IN
 CABINETS.
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE INCLUDES 50 PERCENT OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 ROOFED BUT OPEN CARPORTS THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES;
 ROOFED BUT OPEN PORCHES THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES;
 ROOFED BUT OPEN BREEZEWAYS THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES.
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE DOES NOT INCLUDE ANY OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 FREE-STANDING PATIOS, DECKS AND GAZEBOS THAT ARE ROOFED
 BUT NOT ENCLOSED BY SOLID WALLS ON MORE THAN ONE SIDE
 AND NOT ATTACHED TO A PRINCIPAL OR ACCESSORY STRUCTURE.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT MEETING
 REQUIREMENTS OF SECTION 94-113
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 6 Status P Date 2023-07-14 Cont ID  
Sent By cibaven Date 2023-07-14 Time 16:42 Rev Time 0.00
Received By cibaven Date 2023-07-14 Time 16:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2022-12-28 Cont ID  
Sent By fmittner Date 2022-12-28 Time 12:13 Rev Time 0.00
Received By fmittner Date 2022-12-28 Time 12:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-06-06 Cont ID  
Sent By ckimmerl Date 2022-06-06 Time 16:30 Rev Time 0.00
Received By amhamilt Date 2022-06-06 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-10-12 Cont ID  
Sent By ckimmerl Date 2021-10-12 Time 15:37 Rev Time 0.00
Received By ckimmerl Date 2021-10-12 Time 15:37 Sent To  
Notes
2021-10-12 15:37:16REPEAT COMMENTS:
  
 1. PLEASE PROVIDE A COPY OF A CURRENT SURVEY FOR THE
 PROPERTY.
  
 2. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT MEETING
 THE REQUIREMENTS OF SECTION 94-113.
  
 - THE VALUE OF THE CONSTRUCTION ($120,957) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($40,990) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-05 Cont ID  
Sent By ckimmerl Date 2021-08-05 Time 14:42 Rev Time 0.00
Received By ckimmerl Date 2021-08-05 Time 14:41 Sent To  
Notes
2021-08-05 14:42:15PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY,
 WHICH INCLUDES THE PROPERTY'S ADDRESS AND LEGAL
 DESCRIPTION.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT MEETING THE
 REQUIREMENTS OF SECTION 94-113.
 - THE VALUE OF THE CONSTRUCTION ($120,957) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($40,990) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By elevesqu Date 2021-02-01 Time 16:47 Rev Time 0.00
Received By elevesqu Date 2021-02-01 Time 16:47 Sent To  
Notes
2021-02-01 16:47:51PLEASE SEE HISTORIC COMMENTS REGARDING ARCHITECTURE AND
 NECESSARY ACTIONS FOR APPROVAL
  
 LOT COVERAGE FOR THIS LOT IS MAXIMUM 30 PERCENT. PLEASE
 CLARIFY THE LOT COVERAGE BASED ON HISTORIC CALCULATIONS
 BELOW AND INCLUDE A TABLE BREAKING DOWN WHAT IS BEING
 COUNTED:
  
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE INCLUDES 100 PERCENT OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 ACCESSORY STRUCTURES SUCH AS SHEDS, GUEST HOUSES AND
 SECOND UNITS THAT ARE ROOFED AND ENCLOSED ON MORE THAN
 TWO SIDES WHETHER OR NOT THEY INCLUDE HABITABLE SPACE;
 ATTACHED AND DETACHED GARAGES;
 STAIRWAYS: THE GROUND FLOOR OF INTERIOR AND ROOFED
 EXTERIOR STAIRWAYS, ELEVATORS, ESCALATORS AND SIMILAR
 FEATURES. THE GROUND FLOOR AREA OF USABLE SPACES HAVING
 A 5' MINIMUM HEIGHT UNDER A RUN OF STAIRS SHALL BE
 COUNTED;
 UTILITY AREAS: THE GROUND FLOOR AREA OF LAUNDRY ROOMS,
 MECHANICAL ROOMS, CLOSETS, STORAGE ROOMS AND BUILT-IN
 CABINETS.
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE INCLUDES 50 PERCENT OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 ROOFED BUT OPEN CARPORTS THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES;
 ROOFED BUT OPEN PORCHES THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES;
 ROOFED BUT OPEN BREEZEWAYS THAT ARE ATTACHED TO A
 PRINCIPAL OR ACCESSORY STRUCTURE BUT NOT ENCLOSED BY
 SOLID WALLS ON MORE THAN TWO SIDES.
 BUILDING FOOTPRINT CALCULATED USING THE ASSIGNED LOT
 COVERAGE DOES NOT INCLUDE ANY OF THE GROUND FLOOR AREA
 OF THE FOLLOWING STRUCTURES AND BUILDING ELEMENTS:
  
 FREE-STANDING PATIOS, DECKS AND GAZEBOS THAT ARE ROOFED
 BUT NOT ENCLOSED BY SOLID WALLS ON MORE THAN ONE SIDE
 AND NOT ATTACHED TO A PRINCIPAL OR ACCESSORY STRUCTURE.
  
 PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT MEETING
 REQUIREMENTS OF SECTION 94-113
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]