Plan Review Details - Permit 20120984
Plan Review Stops For Permit 20120984
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By cpuell Date 2021-01-04 Time 10:27 Rev Time 0.00
Received By cpuell Date 2021-01-04 Time 10:27 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 12:21 Rev Time 0.00
Received By cpuell Date 2020-12-29 Time 12:21 Sent To  
Notes
2020-12-29 12:21:38IS THERE A SUITE NUMBER PLEASE REACH OUT TO
 [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By cthroop Date 2021-01-08 Time 08:44 Rev Time 0.00
Received By cthroop Date 2021-01-08 Time 06:33 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By cthroop Date 2020-12-28 Time 12:55 Rev Time 0.00
Received By cthroop Date 2020-12-28 Time 10:04 Sent To  
Notes
2020-12-28 13:00:58PLAN REVIEW - BUILDING ASBESTOS
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
  
 RE: ASBESTOS
  
 1. IF THE PROJECT IS NOT EXEMPT, OR THE REVIEWER CANNOT
 DETERMINE THAT IT IS EXEMPT, THE CONTRACTOR IS TO
 PROVIDE AN ACKNOWLEDGEMENT THAT THE REQUIRED
 NOTIFICATION PROCESS WILL BE FOLLOWED OR WILL PROVIDE A
 STATEMENT AS TO WHY THEY ARE EXEMPT.
  
 2. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT:
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By cthroop Date 2021-01-08 Time 08:44 Rev Time 0.00
Received By cthroop Date 2021-01-08 Time 06:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By cthroop Date 2020-12-28 Time 13:03 Rev Time 0.00
Received By cthroop Date 2020-12-28 Time 10:04 Sent To  
Notes
2020-12-28 13:05:02PLAN REVIEW / INTERIOR DEMO
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REMOVE PLAN PAGES NOT RELEVANT TO THIS SOW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By equinone Date 2021-01-08 Time 10:47 Rev Time 0.00
Received By equinone Date 2021-01-08 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-29 Cont ID  
Sent By equinone Date 2020-12-29 Time 10:16 Rev Time 0.00
Received By equinone Date 2020-12-29 Time 08:01 Sent To  
Notes
2020-12-29 10:16:33CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) SCOPE OF WORK IS NOT CLEAR. APPLICATION MENTIONS
 DEMOLITION WORK, BUT ELECTRICAL DRAWINGS E-105 AND
 E-205 SEEM TO INDICATE NEW ELECTRICAL WORK IS BEING
 DONE. PLEASE CLARIFY SOW AND PROVIDE NOTES ON DRAWINGS
 SHOWING WHAT IS NEW, EXISTING TO REMAIN, EXISTING TO BE
 REMOVED. FBC 107
 2) RISER DIAGRAM AND PANEL SCHEDULES: PLEASE PROVIDE
 PANEL SCHEDULE FOR LP1 AND SHOW PANEL H ON RISER
 DIAGRAM. FBC 107
 3) ELECTRICAL SUB PERMIT IS REQUIRED FBC 107
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By bdolan Date 2021-01-12 Time   Rev Time 0.00
Received By bdolan Date 2021-01-12 Time 12:57 Sent To  
Notes
2021-01-12 12:58:201. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 2. ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER
 SEPARATE PERMITS AND SHOP DRAWINGS.
  
 3. THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO.
  
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
 5. ANY AND ALL WORK INVOLVING ELECTRICAL INSTALLATIONS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS,
 COMPLIANT WITH NFPA 70, NATIONAL ELECTRIC CODE, 2014
 EDITION.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-15 Cont ID  
Sent By cpuell Date 2021-01-15 Time 15:35 Rev Time 0.00
Received By cpuell Date 2021-01-06 Time 10:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-04 Cont ID  
Sent By shill Date 2021-01-04 Time 10:19 Rev Time 0.00
Received By shill Date 2020-12-22 Time 09:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-01-08 Cont ID  
Sent By medwards Date 2021-01-08 Time 11:02 Rev Time 0.00
Received By medwards Date 2021-01-08 Time 11:02 Sent To  
Notes
2021-01-08 11:03:16MECHANICAL DEOM SHEET ONLY APPROVED. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By lcrespo Date 2021-01-08 Time 07:36 Rev Time 0.00
Received By lcrespo Date 2021-01-08 Time 07:34 Sent To  
Notes
2021-01-08 07:36:3301/08/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-12-29 Cont ID  
Sent By lcrespo Date 2020-12-29 Time 16:00 Rev Time 0.00
Received By lcrespo Date 2020-12-29 Time 16:00 Sent To  
Notes
2020-12-29 16:01:0212/29/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-11 Cont ID  
Sent By cthroop Date 2021-01-11 Time 16:00 Rev Time 0.00
Received By cthroop Date 2021-01-08 Time 06:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-28 Cont ID  
Sent By cthroop Date 2020-12-28 Time 13:01 Rev Time 0.00
Received By cthroop Date 2020-12-28 Time 10:04 Sent To  
Notes
2020-12-28 13:02:17PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  