Plan Review Stops For Permit 20120900 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-03-09 |
Time |
07:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-09 |
Time |
07:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-01-04 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-01-04 |
Time |
14:06 |
Sent To |
|
|
Notes |
2021-01-04 15:05:04 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE A SURVEY AND A SITE PLAN THAT HAS DIMENSIONS | | TO THE PROPERTY LINES AND TO THE BUILDING. 107.2.5 SITE | | PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE | | APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE | | PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW | | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE, | | FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD | | ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN | | ACCURATE BOUNDARY LINE SURVEY. | | | | 2) THE BOUNDARIES OF A SPECIAL FLOOD HAZARD AREA (SFHA) | | ENCROACH UPON THIS PROPERTY. SHOW THAT THE GENERATOR IS | | NOT LOCATED WITHIN THE BOUNDARIES OF THE SFHA OR SHOW | | HOW IT WILL MEET THE REQUIREMENTS OF EQUIPMENT LOCATED | | IN A SFHA. FBC 1612 AND CITY OF W.P.B. FLOOD ORDINANCE | | | | 3) FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN | | LOADS/DESIGN PRESSURES PURSUANT TO FBC-CHAPTER 16 FOR | | THE WALL AND THE GENERATOR. | | | | 4) THE STRUCTURAL CONNECTION DETAILS ARE NOT SPECIFIC | | AS TO QUANTITY AND SPACING OF THE CONNECTORS THAT | | ANCHOR THE GENERATOR AND BELLY TANK TO THE SLAB. FBC | | 1609 | | | | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-03-05 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-03-05 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2021-03-05 |
Time |
13:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2021-01-07 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-01-07 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2021-01-06 |
Time |
10:55 |
Sent To |
|
|
Notes |
2021-01-07 10:56:41 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. | | | | 1) PLEASE PROVIDE CUT SHEETS (SPECS) FOR ATS AND | | EMERGENCY GENERATOR. FBC 107 | | 2) PLEASE SEE SIGNATURE COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2021-03-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2021-03-04 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2021-03-04 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2020-12-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2020-12-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2020-12-22 |
Time |
12:37 |
Sent To |
|
|
Notes |
2020-12-22 13:12:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET -SITE PLAN - THERE IS AN INDICATION OF A | | GENRAL LOCATION OF THE PROPOSED GENERATOR; HOWEVER, | | THERE ARE NO DETAILS. | | | | PER NFPA 37, INSTALLATION AND USE OF STATIONARY | | COMBUSTION ENGINES AND GAS TURBINES | | | | 8.2.3 EXHAUST SYSTEM TERMINATION. | | 8.2.3.1* EXHAUST SYSTEMS SHALL TERMINATE OUTSIDE THE | | STRUCTURE | | AT A POINT WHERE HOT GASES, SPARKS, OR PRODUCTS OF | | COMBUSTION | | WILL DISCHARGE TO A SAFE LOCATION. | | 8.2.3.2 EXHAUST SYSTEM TERMINATIONS SHALL NOT BE | | DIRECTED TOWARD | | COMBUSTIBLE MATERIAL OR STRUCTURES OR INTO ATMOSPHERES | | CONTAINING FLAMMABLE GASES, FLAMMABLE VAPORS, OR | | COMBUSTIBLE | | DUSTS. | | | | PLEASE PROVIDE DIMENSIONS FROM EACH PART OF THE | | BUILDING INCLUDING THE NEAEEST WINDOWS, DOORS OR VENTS | | AS WELL AS THE PROPERTY LINE. | | | | | | | | 2) SHEET - SITE PLAN - THERE ARE NO DIMENSIONS OF THE | | SIZE OF THE CMU ENCLOSURE | | | | PLEASE PROVIDE DETAILS | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-03-15 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-03-15 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-03-02 |
Time |
10:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-01-07 |
|
|
Cont ID |
|
Sent By |
equinone |
Date |
2021-01-07 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
equinone |
Date |
2020-12-21 |
Time |
12:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-09 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-09 |
Time |
08:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2021-01-06 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-01-06 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-01-06 |
Time |
15:39 |
Sent To |
|
|
Notes |
2021-01-06 15:40:17 | PLEASE SEE BUILDING REVIEWERS COMMENTS. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-03-16 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-16 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-16 |
Time |
15:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-03-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-03-09 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-03-09 |
Time |
09:20 |
Sent To |
|
|
Notes |
2021-03-09 09:23:53 | PLEASE SEE ORIGINAL REVIEWERS COMMENTS. PLEASE SUBMIT | | SIGNED AND SEALED DIGITAL SHEETS. | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2021-01-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-01-04 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-01-04 |
Time |
15:05 |
Sent To |
|
|
Notes |
2021-01-04 15:05:43 | THE PLANS HAVE NOT BEEN DIGITALLY SIGNED BY THE | | ENGINEER. ELECTRONICALLY SUBMITTED DRAWINGS ARE | | REQUIRED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE ON | | THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | TO BE VERIFIED. THE ENGINEER'S ORIGINAL HANDWRITTEN | | SIGNATURE AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. | | NO PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | ACCEPTABLE. FS 471 & 61G15 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-03-15 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2021-03-15 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2021-03-15 |
Time |
14:59 |
Sent To |
|
|
Notes |
2021-03-15 15:00:26 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 03.15.2021 | | PERMIT NO.: 20120900 | | ________________________________________ | | | | REVIEW STATUS: PASSED WITH PROVISOS | | ________________________________________ | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | PROVISOS: | | | | 1. THIS PERMIT REVIEW IS LIMITED TO THE GENERATOR ONLY. | | | | 2. THE GENERATOR SHALL BE ENTIRELY SCREENED FROM VIEW | | BY AN OPAQUE WALL OR FENCE CONSTRUCTED OF BRICK, | | DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR | | COMPARABLY DURABLE WOOD AND STEEL. SHRUBS/HEDGES SHALL | | BE PLANTED AT 2-FOOT INTERVALS. | | | | 3. THE CENTREPARK COMMERCIAL PLANNED DEVELOPMENT SHALL | | BE SUBJECT TO ALL DEVELOPMENT ORDER CONDITIONS, AS | | OUTLINED IN RESOLUTION NO. 16-21, APPROVED ON FEBRUARY | | 8, 2021, AND AS MAY BE AMENDED. | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-03-15 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2021-03-15 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2021-03-15 |
Time |
14:33 |
Sent To |
|
|
Notes |
2021-03-15 14:41:24 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 12.30.2020 | | PERMIT NO.: 20120900 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. [ NOT SATISFIED ] - A CURRENT AND ACCURATE SURVEY OF | | THE PROPERTY SHALL BE PROVIDED. | | | | 1.1 [ NEW COMMENT ] - A SIGNED/SEALED SURVEY PREPARED | | BY A LICENSED SURVEYOR SHALL BE PROVIDED. | | | | 2. [ SATISFIED ] - A DETAILED SITE PLAN SHALL BE | | PROVIDED SHOWING ALL EXISTING IMPROVEMENTS ON THE | | PROPERTY, THE LOCATION OF THE PROPOSED GENERATOR, | | PROPERTY LINES, SETBACK DIMENSIONS FROM THE PROPERTY | | LINE TO THE PROPOSED GENERATOR, ETC. | | | | 3. [ SATISFIED ] - THE HEIGHT OF THE WALL SURROUNDING | | THE GENERATOR SHALL BE PROVIDED, AND SHALL BE OF | | SUFFICIENT HEIGHT TO SCREEN THE GENERATOR FROM VIEW. | | | | 4. [ SATISFIED ] - THE ENCLOSURE SHALL PROVIDE AN | | OBSCURING GATE. | | | | 5. [ SATISFIED ] - THE ENCLOSURE SHALL BE LANDSCAPED | | WITH SHRUBS/HEDGES PLANTED AT TWO (2) FOOT INTERVALS | | (MINIMUM). | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-12-30 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2020-12-30 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2020-12-30 |
Time |
10:14 |
Sent To |
|
|
Notes |
2020-12-30 10:14:47 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 12.30.2020 | | PERMIT NO.: 20120900 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. A CURRENT AND ACCURATE SURVEY OF THE PROPERTY SHALL | | BE PROVIDED. | | | | 2. A DETAILED SITE PLAN SHALL BE PROVIDED SHOWING ALL | | EXISTING IMPROVEMENTS ON THE PROPERTY, THE LOCATION OF | | THE PROPOSED GENERATOR, PROPERTY LINES, SETBACK | | DIMENSIONS FROM THE PROPERTY LINE TO THE PROPOSED | | GENERATOR, ETC. | | | | 3. THE HEIGHT OF THE WALL SURROUNDING THE GENERATOR | | SHALL BE PROVIDED, AND SHALL BE OF SUFFICIENT HEIGHT TO | | SCREEN THE GENERATOR FROM VIEW. | | | | 4. THE ENCLOSURE SHALL PROVIDE AN OBSCURING GATE. | | | | 5. THE ENCLOSURE SHALL BE LANDSCAPED WITH SHRUBS/HEDGES | | PLANTED AT TWO (2) FOOT INTERVALS (MINIMUM). | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|