2021-04-21 16:49:55 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 20120886 |
| 4/21/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| WITH ADDITIONAL NOTES IN CAPS. |
| |
| 1) COVER SHEET: PROVIDE A LIST OF CODES AND STANDARDS |
| USED IN THE DESIGN OF THE PROJECT- SECTION 107.2.1 WPB. |
| REQUESTED CODE DATA NOT PROVIDED. |
| |
| 2) SHEETS 1 & 2: REFER TO SECTION 301.1 FBC EX: |
| ALTERATIONS TO EXISTING BUILDINGS SHALL COMPLY WITH ONE |
| OF THE METHODS LISTED IN SECTIONS 301.1.1- 301.1.3. |
| PLEASE INDICATE ON THE PLANS WHICH COMPLIANCE PATH WILL |
| BE USED. FOR THE PURPOSES OF REVIEW AT THIS POINT A |
| LEVEL II ALTERATION IS ASSUMED BASED ON SECTIONS |
| 301.1.2 AND 504.1 FBC EX. PLEASE SEE SECTION 806.1 |
| WHICH STATES ALTERATIONS SHALL COMPLY WITH THE FLORIDA |
| ACCESSIBILITY CODE. UNDER SECTION 202.3 FBC ACC, THE |
| ALTERED SPACE SHALL COMPLY WITH SECTIONS 213.2, |
| 213.3.2, & 213.3.4. IT APPEARS FROM THE DRAWINGS THAT |
| THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET |
| (SECTIONS 213.3.2 & 604) IS NOT IN COMPLIANCE. THE |
| REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET IS 60 |
| INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL. COMPLIANCE PATH NOT PROVIDED. WATER |
| CLOSET CLEAR FLOOR SPACE SHOWN IN THE DIGARAM ON SHEET |
| A-1 IS NOT IN COMPLIANCE WITH SECTION 604.3 FBC ACC |
| BECAUSE IT IS OVERLAPPING THE LAVATORY SINK. |
| |
| 3 A) FAILED. CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS |
| FOR THE WATER CLOSET- SECTION 604.3. WATER CLOSET CLEAR |
| FLOOR SPACE SHALL NOT OVERLAP THE LAVATORY SINK- |
| SECTION 604.3 FBC ACC. |
| |
| 3 G) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS |
| OF GRAB BARS FOR THE WATER CLOSET- SECTION 604.5 & |
| 609.4. THE GRAB BARS SHALL BE POSITIONED 33 INCHES |
| MINIMUM TO 36 INCHES MAXIMUM MEASURED FROM THE FINISH |
| FLOOR TO THE TOP OF THE GRIPPING SURFACE. |
| |
| 3 H) FAILED. LOCATION OF THE WATER CLOSET FLUSH CONTROL |
| - SECTION 604.6. NOT PROVIDED. |
| |
| 4) FAILED. SHEET 2: THE TOILET ROOM FINISHES SHALL BE |
| IN COMPLIANCE WITH SECTION 310.3 FBC P, AND SECTION |
| 1210.2.2 FBC B. PLEASE REVIEW AND CORRECT THE NOTE |
| SPECIFYING EPOXY PAINT FINISH. FINISH WALL AND FLOOR |
| MATERIALS NOT PROVIDED. PLEASE NOTE WALLS AND |
| PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND |
| WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE |
| FLOOR. EPOXY PAINTED DRYWALL DOES NOT MEET COMPLIANCE. |
| |
| 5) FAILED. PLEASE NOTE THAT PLUMBING RISER DRAWINGS ARE |
| REQUIRED FOR ALL ALTERATIONS MADE TO THE EXISTING WATER |
| SUPPLY AND SANITARY DRAINAGE SYSTEMS- SECTION |
| 107.3.5.1.3 WPB. A SLAB REPAIR DETAIL HAS BEEN PROVIDED |
| ON A-1. PLEASE CLARIFY IF NEW UNDERGROUND PIPING WILL |
| BE INSTALLED AND PROVIDE A SANITARY RISER IF |
| APPLICABLE. |
| |
| NEW COMMENT |
| |
| 1) SHOW THE SOURCE OF HOT WATER FOR THE NEW LAVATORY |
| AND INDICATE HOW TEMPERED WATER WILL BE PROVIDED- |
| SECTIONS 419.5 & 607.1.2 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |