Plan Review Details - Permit 20120803
Plan Review Stops For Permit 20120803
Review Stop AD ADDRESSING
Rev No 5 Status P Date 2022-09-13 Cont ID  
Sent By cpuell Date 2022-09-13 Time 09:44 Rev Time 0.00
Received By cpuell Date 2022-09-13 Time 09:44 Sent To  
Notes
2022-09-13 09:45:29APT ADDRESSES ESTABLISHED

Review Stop AD ADDRESSING
Rev No 4 Status P Date 2021-09-09 Cont ID  
Sent By cpuell Date 2021-09-09 Time 15:37 Rev Time 0.00
Received By cpuell Date 2021-09-09 Time 15:37 Sent To  
Notes
2021-09-09 15:38:22PRIMARY ADDRESS ESTABLISHED, WORKING ON APT ADDRESSES.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-05-06 Cont ID  
Sent By cpuell Date 2021-05-06 Time 10:17 Rev Time 0.00
Received By cpuell Date 2021-05-06 Time 10:17 Sent To  
Notes
2021-05-06 10:18:17PLEASE EMAIL [email protected] A LIST OF THE UNIT NUMBERS
 ALONG WITH A FLOOR PLANS SHOWING THE UNIT LOCATIONS.
  

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-03-03 Cont ID  
Sent By cpuell Date 2021-03-03 Time 16:15 Rev Time 0.00
Received By cpuell Date   Time   Sent To  
Notes
2021-03-09 13:05:23PLEASE EMAIL [email protected] A LIST OF THE UNIT NUMBERS
 ALONG WITH A FLOOR PLANS SHOWING THE UNIT LOCATIONS.
2021-03-03 16:15:41PARCEL SUBDIVIDED, PCN CHANGES, PERMIT UPDATED.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By cpuell Date 2021-01-07 Time 11:09 Rev Time 0.00
Received By cpuell Date 2021-01-07 Time 11:09 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 5 Status P Date 2021-12-13 Cont ID  
Sent By scwelter Date 2021-12-13 Time 11:15 Rev Time 0.00
Received By scwelter Date 2022-03-11 Time 17:03 Sent To  
Notes
2021-12-13 11:35:503.11.2022 PROJECT COMPLETED PUBLIC ART REQUIREMENT
  
 PARADISE RIVERSTONE 374 PALM BEACH, LLC PERMIT
 #20120803
 OKAY TO PRINT PERMIT.
 12.13.2021 RECEIVED THE FOLLOWING FROM DEVELOPER:
 O ART ASSESSMENT APPLICATION OPTION
 1/SIGNED/DATED/NOTARIZED
 O ESCROW LETTER FROM SHUTTS CONFIRMING DEPOSIT OF 1%
 ART REQUIREMENT
 AS PER MY DISCUSSION WITH THE DEVELOPERS ART CONSULTANT
 LINDA OLIVER THE PERMIT IS CONDITIONAL ON THE
 FOLLOWING:
 DOCUMENTS FOR APPROVAL PROCESS (PAGE TWO OF THE ART
 ASSESSMENT APPLICATION) MUST BE SUBMITTED TO MY
 ATTENTION IN JANUARY OF 2022 BUT NO LATER THAN FEBRUARY
 2022. ARTLIFE COMMITTEE MEETS THE FIRST WEDNESDAY OF
 THE MONTH UNLESS OTHERWISE STATED. NEXT MEETING IS
 FEBRUARY 3, 2022. DOCUMENTS MUST BE SUBMITTED TWO WEEKS
 PRIOR TO BE APPROVED FOR REVIEW BY THE COMMITTEE.
 COMPLETED PUBLIC ART APPLICATION, ON THE CITY'S FORMS,
 COMPLETED AND SIGNED.
 COMPLETED CONSTRUCTION COST VALUATION OF THE PROJECT.
 COMPLETED COPY OF THE ESCROW AGREEMENT.
 COMPLETED DOCUMENTATION SHOWING THAT A DEPOSIT FOR
 PUBLIC ART WAS MADE INTO AN ESCROW ACCOUNT.
 1. ART BUDGET, ITEMIZED.
 2. VALUE OF PROPOSED ARTWORK. (IF PURCHASING)
 3. ARTIST'S QUALIFICATIONS, INCLUDING RESUME AND
 PORTFOLIO ESTABLISHING THE ARTIST'S CREDENTIALS.
 4. DETAILED DESCRIPTION AND DEPICTION OF THE ARTWORK,
 INCLUDING CONCEPTUAL APPROACH AND RELEVANT DESIGN
 INFORMATION.
 5. DRAWINGS AND RENDERINGS OF THE PROPOSED ARTWORK, IN
 TERMS OF SIZE, SCALE, COLOR, SHAPE, AND MATERIALS IN
 SUFFICIENT DETAIL TO PROVIDE A CLEAR UNDERSTANDING OF
 THE ART OR ELEMENTS PROPOSED. A DIGITAL COLOR
 RENDERING. DRAWINGS AND RENDERINGS SHALL BE TO SCALE,
 AT THE PROPOSED LOCATION AND SHOW SURROUNDING
 LANDSCAPING, BUILDINGS, LIGHTING, PUBLIC RIGHT-OF-WAY,
 PLAQUE PLACEMENT, PARKING, FRONTAGE, AND ANY OTHER
 INFORMATION RELEVANT TO THE SITE AND PLACEMENT.
 6. MATERIALS AND METHOD DESCRIPTION INCLUDING ALL
 PROPOSED MATERIALS AND INSTALLATION METHODS AND MUST
 INCLUDE SAMPLES OR PHOTO DOCUMENTATION.
 7. COPIES OF THE ARTIST CONTRACT AND RELEVANT
 SUBCONTRACTS.
 8. MAINTENANCE PROGRAM REQUIRED FOR THE ARTWORK OR
 ELEMENTS. INCLUDE MAINTENANCE MILESTONES AND IDENTIFY
 THE PARTY RESPONSIBLE FOR MAINTENANCE. A FINAL
 MAINTENANCE PLAN IS DUE UPON PROJECT COMPLETION.
 9. COMMUNITY OUTREACH. DESCRIBE COMMUNITY OUTREACH
 COMMUNICATION AND PLANS.
 10. SCHEDULE. DESCRIBE PROPOSED PROJECT SCHEDULE AND
 PROJECT DEVELOPMENT TIMELINESS, INCLUDING CITY REVIEWS
 AND ARTWORK INSTALLATION SCHEDULE.
 11. COMPLIANCE WITH PUBLIC ACCESSIBILITY (ADA)
 REQUIREMENTS.
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 4 Status F Date 2021-12-09 Cont ID  
Sent By lmarchan Date 2021-12-09 Time 13:29 Rev Time 0.00
Received By lmarchan Date 2021-12-09 Time 13:29 Sent To  
Notes
2021-12-09 13:29:24PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status F Date 2021-10-13 Cont ID  
Sent By scwelter Date 2021-10-13 Time 14:34 Rev Time 0.00
Received By scwelter Date 2021-10-13 Time 14:34 Sent To  
Notes
***NONE***

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By scwelter Date 2021-05-11 Time 15:30 Rev Time 0.00
Received By scwelter Date 2021-09-03 Time 11:04 Sent To  
Notes
2021-05-11 15:30:543.13.2021 PUBLIC ART REQUIREMENT ENTERED FOR ART REVIEW
 (SEE BELOW)
 7.27.2021 EMAILED LARRY ZABIK ART ASSESSMENT
 APPLICATION
 8.17.2021 RICHARD GATHRIGHT EMAIL ERICK HIMMEL
 REQUESTING CONTACT INFORMATION
  
 AS OF 9.03.2021 DEVELOPER HAS NOT RESPONDED TO MY
 EMAILS. SUBMITTED BUILDING APPLICATION 12.16.2020
  
  
 PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By shill Date 2021-03-16 Time 10:10 Rev Time 0.00
Received By shill Date 2021-03-16 Time 10:10 Sent To  
Notes
2021-03-16 10:11:01PUBLIC ART REQUIREMENT:
 IF TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE
 OVER $500,000 IT WILL BE SUBJECT TO THE PUBLIC ART
 REQUIREMENT AS PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 09:44 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-12-06 Cont ID  
Sent By rmcphers Date 2021-12-06 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2021-12-06 Time 14:20 Sent To  
Notes
2021-12-06 14:47:49NEW 8 STORY APT AND 6 STORY PARKING GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) ALL FLOORS - CORRIDOR CEILING HEIGHT (MIN.7'6") -
 FBC 1208.2 MINIMUM CEILING HEIGHTS.
 OCCUPIABLE SPACES, HABITABLE SPACES AND CORRIDORS SHALL
 HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES
 (2286 MM) ABOVE THE FINISHED FLOOR.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-09-30 Cont ID  
Sent By rmcphers Date 2021-09-30 Time 13:57 Rev Time 0.00
Received By rmcphers Date 2021-09-29 Time 14:10 Sent To  
Notes
2021-09-30 12:32:02NEW 8 STORY APT AND 6 STORY PARKING GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ROOM "USE" FOR THE ROOMS MARKED
 G105, G104, G102, 167 ON THE FLOOR PLAN.
  
 2) PLEASE REVISE THE LIFE SAFETY PLANS - TO MATCH THE
 REVISED FLOOR PLANS PROVIDED.
  
 3) BUILDING IS NOT CONSIDERED A HIGHRISE - UNIT MARKED
 ST-1 AND ST-1 MOD - THE SLEEPING ROOM REQUIRES AN
 EMERGENCY EXIT. FBC 1030.1
  
 4) CAR CHARGING STATIONS FOR THE PARKING ARE SHOWN ON
 THE ELECTRICAL DRAWINGS BUT NOT ON THE ARCHITECTURAL
 FLOOR PLAN. ELECTRIC VEHICLE CHARGING STATIONS ARE
 BEING INSTALLED - PLEASE SHOW THAT AT LEAST 1 OF THE
 CHARGING STATIONS IS A MARKED ACCESSIBLE PARKING SPACE,
 ACCESS AISLE, SIGNAGE ETC. ALLOWING ACCESS TO THE
 CHARGER - PER FBC 502
  
 5) ARCHITECT NEEDS TO SPECIFY HOW THE WALLS BETWEEN
 UNITS AND SERVICE OR CORRIDOR AREA MEET THE
 REQUIREMENTS OF FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. PENETRATIONS OR
 OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING;
 ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS;
 SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL
 BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO
 MAINTAIN THE REQUIRED RATINGS.
  
 6) THE ONLY CALCULATIONS FOR THE OPEN GARAGE
 VENTILATION PROVIDE ARE FOR THE 1ST FLOOR - THE
 PERCENTAGES ARE NOT SHOWN. PLEASE PROVIDE THE
 CALCULATIONS FOR THE OPEN GARAGE PER FBC 406.5.2 FOR
 NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF THE
 STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS ON
 TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 7) DRAWING A-4.8 - THE FINISH SCHEDULE NEEDS TO SHOW
 THE COMMON RESTROOM WALL FINISH TO COMPLY WITH (DRYWALL
 IS NOT CONSIDERED A HARD SURFACE) 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 8) DRAWING A-4.8 CANNOT HAVE A WOOD BASEBOARD IN THE
 COMMON RESTROOMS - FBC 1210.2.1 FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2021-06-10 Time 08:27 Sent To  
Notes
2021-06-15 12:22:49NEW 8 STORY APT AND 6 STORY PARKING GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE ACCESSIBLE SEATING AND COUNTER TOP
 ELEVATIONS AT THE BISTOR BAR AND DEMO. KITCHEN TO
 COMPLY WITH FBC ACCESSIBILITY FAIR HOUSING GUIDE LINES
 SECTION 5.GUIDELINES - REQUIREMENT 2 - NUMBER (12).
 2) PLEASE SHOW THE FIRE RATING DETAILS FOR THE STEEL
 ANGLE SHOWN ON DETAIL DRAWING P/S-3.3 - FBC TABLE 601
 3) PLEASE SHOW THE FIRE RATING DETAILS FOR THE STEEL
 COLUMNS PER FBC TABLE 601
 4) PLEASE SHOW THE GARAGE AS OPEN OR ENCLOSED AND
 PROVIDE THE CALCULATIONS FOR THE OPEN GARAGE PER FBC
 406.5.2 OR VENTILATION REQUIREMENTS FOR ENCLOSED GARAGE
 PER FBC 406.6.2
 5) DRAWING A-4.8 - THE FINISH SCHEDULE IS BLANK -
 PLEASE CORRECT.
 6) PLEASE PROVIDE A SOIL REPORT AS NOTED ON THE
 DRAWINGS. ("SOIL REPORT HAS BEEN PROVIDED" 8/23/2021-
 COMMENT WILL BE REMOVED ON THE NEXT REVIEW)
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:50 Rev Time 0.00
Received By rmcphers Date 2021-02-08 Time 08:17 Sent To  
Notes
2021-02-10 10:39:02NEW 8 STORY APT AND 6 STORY PARKING GARAGE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE CLARIFY ROOF TRUSS DESIGN - ARCHITECTURAL
 SHOWS METAL TRUSS - STRUCTURAL DRAWINGS SHOW WOOD
 TRUSS.
 2) PLEASE SHOW WALL TO TRUSS STRAPPING DETAILS TO METAL
 OR WOOD TRUSSES.
 3) PLEASE SHOW PLYWOOD ATTACHMENT DETAILS TO METAL
 TRUSSES.
 4) PLEASE SHOW WOOD TRUSSES AS FIRE RETARDANT PER FBC
 603.1
 5) PLEASE SHOW CLEARLY THE REQUIREMENT OF FIRE
 RETARDANT ROOF SHEATHING FBC 603.1
 6) PLEASE SHOW THE FIRE RATING DETAILS FOR THE STEEL
 COLUMNS PER FBC TABLE 601 (2 HRS)
 7) PLEASE SHOW THE GARAGE AS OPEN OR ENCLOSED AND
 PROVIDE THE CALCULATIONS FOR THE OPEN GARAGE PER FBC
 406.5.2 OR VENTILATION REQUIREMENTS FOR ENCLOSED GARAGE
 PER FBC 406.6.2
 8) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE TO OPEN
 THE DOOR FROM THE INSIDE OF ALL DOORS - TO EXIT THE
 UNIT, BATHROOM ETC (18' CLEARANCE BESIDE THE DOOR). FBC
 ACCESSIBILITY FHA REQUIREMENT 3.USABLE DOORS.
 SECTION 100.205(C)(2) PROVIDES THAT COVERED MULTIFAMILY
 DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT ALL THE
 DOORS DESIGNED TO ALLOW PASSAGE BY HANDICAPPED PERSONS
 IN WHEELCHAIRS. ANSI 4.3 ANSI 4.13.6
 9) DRAWING A-4.9 "UNISEX AND POWDER ROOM" KEY NOTES DO
 NOT MATCH THE LEGEND ON THE SAME DRAWING - PLEASE
 CORRECT.
 10) DRAWING A-4.8 - THE FINISH SCHEDULE IS BLANK -
 PLEASE CORRECT.
 11) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS. DOORS AND
 ROOFING SYSTEMS. ALL PRODUCT APPROVALS AND SHOP
 DRAWINGS NEED TO BE REVIEWED AND MARKED APPROVED BY THE
 BUILDING DESIGNER OF RECORD OR LISTED BY PRODUCT
 APPROVAL NUMBER ON THE DRAWINGS.
 12) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT AS
 NOTED ON THE DRAWINGS.
 13) PLEASE PROVIDE THE FLOOR/CEILING ACOUSTICAL TEST
 REPORTS - THE FOLLOWING ACOUSTICAL TEST REPORTS ARE
 REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 14) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - PLEASE PROVIDE A CONTRACT, COST
 BREAKDOWN ETC TO VERIFY THE JOB VALUE SHOWN ON THE
 BUILDING PERMIT APPLICATION - FBC WPB AMENDMENTS ? FOR
 PERMITTING PURPOSES THE VALUE OF ALL LABOR AND
 MATERIALS REQUIRED TO COMPLETE THE PROJECT ARE REQUIRED
 TO BE INCLUDED IN THE COST. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL ? SWIFT,
 MEANS, ETC.) AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
 15) PLEASE FILL OUT THE THRESHOLD INSPECTOR FORMS AND
 PROVIDE THE REQUIRED DOCUMENTS - SEE THE "GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS AND RESIDENT INSPECTORS" - YOU CAN EMAIL
 ([email protected]) FOR A COPY OF THE GUIDELINES.
 16) ROOFING SYSTEMS, WINDOW / DOOR PRODUCT APPROVALS
 AND FLOOR/CEILING ASSEMBLY ACOUSTICAL TEST REPORTS MAY
 BE DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED
 ON THE CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 22:43 Rev Time 0.00
Received By fgiaquin Date 2021-12-08 Time 21:31 Sent To  
Notes
2021-12-08 22:43:18PASSED BY JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-10-01 Cont ID  
Sent By jleahy Date 2021-10-01 Time 16:46 Rev Time 0.00
Received By jleahy Date 2021-10-01 Time 09:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-05-26 Cont ID  
Sent By jleahy Date 2021-05-26 Time 09:06 Rev Time 0.00
Received By jleahy Date 2021-05-26 Time 09:06 Sent To  
Notes
2021-05-26 09:07:24NO NEW PAGES INSERTED INTO ELECTRICAL SET OF PLANS, SEE
 COMMENTS FROM PRIOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-09 Cont ID  
Sent By jleahy Date 2021-02-09 Time 15:31 Rev Time 0.00
Received By jleahy Date 2021-02-04 Time 07:44 Sent To  
Notes
2021-02-09 15:43:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SHOW A ONLINE DIAGRAM OF THE SERVICES AND
 HOW THIS WILL WORK IN THE BUILDING.
  
 2) I DON'T SEE AN EMERGENCY SYSTEM? LIGHTS, FIRE PUMP,
 ELEVATORS???
  
 3) PLEASE PROVIDE AN ELECTRICAL ROOM LAYOUT FOR EACH
 ELECTRICAL ROOM.
  
 4) SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM. PAGE E-5.2
  
 5) MOST SERVICE MAINS WILL BE REQUIRED TO COMPLY WITH
 240.87 PLEASE INDICATE HOW THIS WILL BE ACOMPLISHED.
  
 6) NEED TO SHOW FAULT CURRENT CALCULATIONS FOR THE
 MAINS AND SUB PANELS PER 110.9, 110.10 PAGES E-5.1,
 E-5.2, AND NOTED ON THE PLAN FOR THE SIGNAGE NEEDED PER
 110.24.
  
 7) HOW ARE THE GOUPING OF THE SERVICE MAINS THAT DON'T
 MEET EXCEPTIONS HP1A, HP3B, AMENITY, FIRE PUMP.
  
 8) FIRE PUMP SHOWS ONLY FPL FPL IS NOT A RELIABLE
 SOURCE OF POWER PER 695.3
  
 9) GARAGE CIRCUITS SHALL COME FROM ONE SOURCE ONLY
 CAN'T TELL IF ALL CIRCUITS COME FROM SAME SOURCE PAGES
 E-2.1--E-2.6
  
 10) IF YOU ARE SUPPLYING SHUNT TRIPS TO THE FIRE COMAND
 CENTER HOW ARE THE OTHER NON-SHUNTED SREVICES GOING TO
 COMPLY WITH A SAFE SYSTEM?
  
 11) SMOKE ALARMS IN UNITS NEED TO BE ADJUSTED TO MEET
 THE REQUIREMENTS OF NFPA 72 WITH REFERENCE TO LOCATION
 TO BATHROOMS, AND KITCHEN COOKING APPLIANCES.
  
 12) SIGNAGE AND DIRECTORIES NEEDED TO BE INSTALLED FOR
 THE SERVICE LOCATIONS THROUGHOUT THE BUILDING WILL NEED
 TO BE SUBMITTED FOR REVIEW BY THE FIRE DEPTARTMENT.
 PLEASE INSERT A PAGE INTO THE ELECTRICAL DRAWINGS FOR
 REVIEW.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-05-12 Cont ID  
Sent By rrossano Date 2021-05-12 Time   Rev Time 0.00
Received By rrossano Date 2021-05-12 Time   Sent To  
Notes
2021-05-12 17:47:39REVIEWED UNDER FORMAL ENG SUBMITAL E20090024.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-02-01 Cont ID  
Sent By RROSSANO Date 2021-02-01 Time   Rev Time  
Received By rrossano Date 2021-02-01 Time   Sent To  
Notes
2021-02-01 13:40:33PLEASE ADDRESS ZONING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-11-17 Cont ID  
Sent By pleduc Date 2021-11-17 Time   Rev Time 0.00
Received By pleduc Date 2021-11-17 Time 16:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-09-10 Cont ID  
Sent By pleduc Date 2021-09-10 Time   Rev Time 0.00
Received By pleduc Date 2021-09-10 Time 16:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-05-14 Cont ID  
Sent By pleduc Date 2021-05-14 Time   Rev Time 0.00
Received By pleduc Date 2021-05-06 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-01-25 Cont ID  
Sent By pleduc Date 2021-01-25 Time   Rev Time 0.00
Received By pleduc Date 2021-01-19 Time 15:28 Sent To  
Notes
2021-01-19 16:31:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET C 07 - THERE IS AN INDICATION OF A FDC ON THE
 EAST SIDE OF A GATED FENCE AND A FIRE HYDRANT ON THE
 WEST SIDE.
  
 THESE NEED TO BE ON THE SAME SIDE OF FENCE WITHIN 100'
 OF EACH OTHER.
  
 PLEASE CORRECT AND SEE 1A BELOW.
  
  
 1A) SHEET C 07 - A PROJECT OF THIS SIZE IS RECOMMENDED
 TO HAVE 2 FDC'S AND 2 FIRE HYDRANT FOR FIRE GROUND
 OPERATIONAL TACTIC'S AND STRATEGIES .
  
 ONE SET IS RECOMMENDED TO BE ON THE WEST SIDE OF THE
 GATED FENCE NEAR THE THE PARKING GARAGE WITH THE FDC
 LOCATED ON THE SAME ISLAND AS THE FIRE HYDRANT.
  
 THE SECOND SET IS RECOMMENED TO BE ON THE EAST SIDE OF
 GATED FENCE LOCATED AT THE ROUND ABOUT ALONG THE EAST
 ORDER (SIMILAR SIDE AS THE PROPOSED HOTEL)
  
 PLEASE REVIEW AND CORRECT
  
  
 1B) SHEET C 07 & F 0.1 - THERE ARE INDICATIONS OF FIRE
 LINE UNDERGROUND WORK INCLUDING FIRE HYDRANTS AND FDC
 LINES.
  
 ALL FIRE LINE WORK SHALL BE INSTALLED UNDER SEPARATE
 PERMITS AND SHOP DRAWINGS, INCLUDING MANUFACTURERS
 SPECIFICATION SHEETS.
  
 PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE
 NOTE OF ACKNOWLEDGEMENT.
  
  
 1C) C 07 & FP SHEETS - A WATER SUPPLY SHALL BE PROVIDED
 PRIOR TO VERITICAL CONSTRUCTION AND FIRE PROTECTION
 STANDPIPES PER NFPA 241
  
 7.5.8 HYDRANTS.
 7.5.8.1 FREE ACCESS FROM THE STREET TO FIRE HYDRANTS
 AND TO
 OUTSIDE CONNECTIONS FOR STANDPIPES, SPRINKLERS, OR
 OTHER FIRE
 EXTINGUISHING EQUIPMENT, WHETHER PERMANENT OR
 TEMPORARY,
 SHALL BE PROVIDED AND MAINTAINED AT ALL TIMES.
  
 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER
 CONSTRUCTION.
 WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN
 BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM,
 EITHER TEMPORARY
 OR PERMANENT IN NATURE, SHALL BE INSTALLED IN
 ACCORDANCE
 WITH 8.7.4.2.1 THROUGH 8.7.4.2.10.
  
 STANDPIPE CONNECTIONS, AT LEASET ONE FOR THE APT BLDG
 AND ONE FOR THE GARAGE, WITH FDC'S SHALL BE INSTALLED
 BEGINNING WITH THE 4 FLOOR
  
 PLEAE REVIEW AND PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 2) SHEET LS 0.1 - THERE ARE INDICATIONS OF EXIT SIGNS
 AT DOUBLE SWING CORRIDOR DOORS. THE EXIT SIGN IS
 INDICATED AT THE CENTER OF THOSE DOORS.
  
 THE EXIT SIGN SHOULD BE LOCATED OVER THE CENTER OF THE
 DOOR IN THE PATH OF EXIT TRAVEL.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10.1.9 MOUNTING LOCATION. THE BOTTOM OF NEW EGRESS
 MARKINGS SHALL BE LOCATED AT A VERTICAL DISTANCE OF NOT
 MORE THAN 6
 FT 8 IN. (2030 MM) ABOVE THE TOP EDGE OF THE EGRESS
 OPENING
 INTENDED FOR DESIGNATION BY THAT MARKING. EGRESS
 MARKINGS SHALL
 BE LOCATED AT A HORIZONTAL DISTANCE OF NOT MORE THAN
 THE REQUIRED
 WIDTH OF THE EGRESS OPENING, AS MEASURED FROM THE EDGE
 OF THE
 EGRESS OPENING INTENDED FOR DESIGNATION BY THAT MARKING
 TO THE
 NEAREST EDGE OF THE MARKING.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET LS 0.2 - THERE ARE INDICATIONS OF EXIT SIGNS
 ON EACH SIDE OF THE DOUBLE SWING CORRIDOR DOORS AT THE
 SIDES OF THE BRIDGE.
  
 EXIT TRAVEL PATHS SHALL BE IN ONLY ONE DIRECTION UNLESS
 THERE IS A HORIZONTAL EXIT OR ARE THESE SMOKE DOORS.
  
 IS IT INTENDED FOR THESE DOUBLE DOORS TO FUNCTION AS
 HORIZONTAL EXITS.
  
 PLEASE REVIEW AND PROVIDE DETAILS, CORRECT AND MOVE THE
 EXIT SIGNS OVER THE APPLICABLE DOOR.
  
  
  
 4) SHEET LS .02 - THERE ARE INDICATIONS OF DIMENSIONS
 BETWEEN THE STAIRWELLS; HOWEVER, THERE ARE NO
 INDICATIONS OF HOW IT IS MEASURED.
  
 PER NFPA 14
  
 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NONSPRINKLERED
 FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M)
 OF TRAVEL
 DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A
 REQUIRED
 EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR
 OR STORY
 IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL
 DISTANCE FROM A
 HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT,
 ADDITIONAL
 HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED
 LOCATIONS,
 WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ.
  
 THE MEAASUREMENT NEEDS TO BE FROM THE HOSE CONNECTION
 TO THE MOST REMOTE PORTION WITHIN A LIVING UNIT OR
 OTHER APPLICABLE REMOTE AREA.
  
 PLEASE REVIEW AND PROVIDE GREATER DETAILED
 MEASURERMENTS AND CORRECT AS APPLICABLE.
  
  
 5) FP SHEETS - THERE ARE NO INDICATION OF FIRE
 SPRINKLER PROTECTION WITHIN THE WASTE CHUTE.
  
 PER NFPA 101, CH 30 , NFPA 13 & 82
  
 30.5.4 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES.
 WASTE CHUTES, INCINERATORS, AND LAUNDRY CHUTES SHALL
 COMPLY WITH
 THE PROVISIONS OF SECTION 9.5.
  
 9.5.2 INSTALLATION AND MAINTENANCE. WASTE CHUTES,
 LAUNDRY
 CHUTES, AND INCINERATORS SHALL BE INSTALLED AND
 MAINTAINED IN
 ACCORDANCE WITH NFPA 82, STANDARD ON INCINERATORS AND
 WASTE
 AND LINEN HANDLING SYSTEMS AND EQUIPMENT, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 22.15.2.2.1 GRAVITY WASTE OR LINEN CHUTES. [82:5.2]
 22.15.2.2.1.1 GRAVITY CHUTES SHALL BE PROTECTED
 INTERNALLY BY
 AUTOMATIC SPRINKLERS UNLESS THEY ARE LINED IN
 ACCORDANCE WITH
 5.2.2.6.1 IN NFPA 82. [82:5.2.2.6.2; 82:5.2.6.1.1]
 22.15.2.2.1.2 THIS PROTECTION REQUIRES THAT A SPRINKLER
 BE INSTALLED
 AT OR ABOVE THE TOP SERVICE OPENING OF THE CHUTE.
 [82:5.2.6.1.2]
  
 PLEASE REVIEW AND CORRECT AND PROVIDE AN APPLICABLE
 NOTE OF ACKNOWLEDGEMENT.
  
  
 6) SHEET F 2.1 THRU 2.7 - THERE ARE NO INDICATIONS OF
 FIRE SPRINKLER PROTECTION WITHIN THE PARKING GARAGE.
  
 IS THE PARKING GARAGE PROPOSED TO BE OPEN OR CLOSED?
  
 PER NFPA 101, CH 30
  
 30.3.5.7 OPEN PARKING STRUCTURES COMPLYING WITH NFPA
 88A,
 STANDARD FOR PARKING STRUCTURES, THAT ARE CONTIGUOUS
 WITH APARTMENT
 BUILDINGS SHALL BE EXEMPT FROM THE SPRINKLER
 REQUIREMENTS OF 30.3.5.1.
  
 PER NFPA 88A
  
 5.5 OPENING REQUIREMENTS FOR OPEN PARKING STRUCTURES.
 5.5.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS OPEN
 TO THE
 ATMOSPHERE, FOR AN AREA OF NOT LESS THAN 0.4 M2 FOR
 EACH LINEAR
 METER (1.4 FT2 FOR EACH LINEAR FOOT) OF ITS EXTERIOR
 PERIMETER.
 5.5.2 SUCH OPENINGS SHALL BE DISTRIBUTED OVER 40
 PERCENT OF
 THE BUILDING PERIMETER OR UNIFORMLY OVER TWO OPPOSING
 SIDES.
 5.5.3 INTERIOR WALL LINES AND COLUMN LINES SHALL BE AT
 LEAST 20 PERCENT
 OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE VENTILATION.
  
  
 PLEASE REVIEW AND PROVIDE APPLICABLE SPECIFIC DETAILS
 OR CORRECT. BE SURE TO INCLUDE SPECIFIC FIRE SEPARATION
 DETAILS BETWEEN THE GARAGE AND APARTMENT BUILDING PER
 NFPA 101, CH 6 OCCUPANCY CLASSIFICATIONS.
  
  
 7) THERE ARE NO INDICATIONS OF 2 - WAY EMERGENCY RADIO
 COMMUNICATIONS.
  
 PER NFPA 1 & 72
  
 NFPA 1
  
 11.10* TWO-WAY RADIO COMMUNICATION ENHANCEMENT SYSTEMS.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL
 STRENGTH FOR FIRE DEPARTMENT COMMUNICATIONS SHALL BE
 MAINTAINED AT A
 LEVEL DETERMINED BY THE AHJ.
 11.10.2 WHERE REQUIRED BY THE AHJ, TWO-WAY RADIO
 COMMUNICATION
 ENHANCEMENT SYSTEMS SHALL COMPLY WITH NFPA 72.
  
 NFPA 72
  
 24.5.2* TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
  
 24.5.2.1.2 APPROVAL AND PERMIT. PLANS SHALL BE
 SUBMITTED FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED
 THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA
 AS SPECIFIED
 IN 24.5.2.2.1 THROUGH 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 FIRE COMMAND
 CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT
 PASSAGEWAYS,
 ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER
 SECTIONAL
 VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT
 FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS
 SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO
 COVERAGE.
 24.5.2.2.3 AMPLIFICATION COMPONENTS. BUILDINGS AND
 STRUCTURES
 THAT CANNOT SUPPORT THE REQUIRED LEVEL OF RADIO
 COVERAGE
 SHALL BE EQUIPPED WITH A RADIATING CABLE SYSTEM OR A
 DISTRIBUTED
 ANTENNA SYSTEM (DAS) WITH FCC-CERTIFIED SIGNAL
 BOOSTERS,
 OR BOTH, OR WITH A SYSTEM THAT IS OTHERWISE APPROVED,
 IN ORDER
 TO ACHIEVE THE REQUIRED ADEQUATE RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF
 ?95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY
 HAVING JURISDICTION, SHALL BE PROVIDED THROUGHOUT THE
 COVERAGE
 AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF ?95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED
 BY THE AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 FROM THE COVERAGE AREA.
 24.5.2.3.3 ISOLATION. IF A DONOR ANTENNA EXISTS,
 ISOLATION SHALL
 BE MAINTAINED BETWEEN THE DONOR ANTENNA AND ALL INSIDE
 ANTENNAS
 AND SHALL BE A MINIMUM OF 15 DB ABOVE THE SIGNAL
 BOOSTER GAIN UNDER ALL OPERATING CONDITIONS.
  
 ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE AND
 A NOTE OF ACKNOWLEDGEMENT TO PROVIDE
  
  
 8) ROOF FP SHEETS - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLER PROTECTION WITHIN THE CONCEALED ROOF SPACES.
  
 PER NFPA 72
  
 8.15.1 CONCEALED SPACES.
 8.15.1.1 CONCEALED SPACES REQUIRING SPRINKLER
 PROTECTION.
 CONCEALED SPACES OF EXPOSED COMBUSTIBLE CONSTRUCTION
 SHALL
 BE PROTECTED BY SPRINKLERS EXCEPT IN CONCEALED SPACES
 WHERE
 SPRINKLERS ARE NOT REQUIRED TO BE INSTALLED BY
 8.15.1.2.1
 THROUGH 8.15.1.2.18 AND 8.15.6.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE CODE AND
 A NOTE OF ACKNOWLEDGEMENT TO PROVIDE
  
  
  
 9) FIRE ALARM/ELECTICAL SHEETS- ALL FIRE ALARM WORK
 SHALL BE INSTALLED UNDER SEPARATE PERMIT AND SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
 9A) FIRE ALARM/ELECTICAL SHEETS- THERE ARE INDICATIONS
 OF PULL STATIONS THROUGHOUT THE OCCUPANCY.
  
 TO REDUCE THE POTENTIAL FOR ACCIDENTAL/INTENTIONAL
 FALSE ALARMS THE NUMBER OF PULL STATIONS CAN BE
 REDUCE/ELIMINATED WHERE NOT REQUIRED BY THE CODE.
  
 PER NFPA 101 CH 30 & CH 9
  
 30.3.4.2 INITIATION.
  
 30.3.4.2.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 30.3.5,
 REQUIRED FIRE ALARM SYSTEMS SHALL BE INITIATED UPON
 OPERATION OF
 THE AUTOMATIC SPRINKLER SYSTEM.
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 PULL STATION ON UPPER FLOORS CAN BE REMOVED.
  
 PULL STATIONS ON THE 1ST FLOOR CAN BE REDUCED.
  
 PLEASE REVIEW AND REDUCE LOCATIONS IN CONSULTATION WITH
 OF OFFICE OF THE FIRE MARSHAL AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT UNLESS THE OWNER/EOR SPECIFCALLY
 REQUEST THESE LOCATIONS.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-11-20 Cont ID  
Sent By abelisle Date 2021-11-20 Time 13:14 Rev Time 0.00
Received By abelisle Date 2021-11-16 Time 17:30 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-07 Cont ID  
Sent By abelisle Date 2021-10-07 Time 08:40 Rev Time 0.00
Received By abelisle Date 2021-10-07 Time 05:57 Sent To  
Notes
2021-10-07 08:11:361ST REVIEW FBC-2017 GAS
 PERMIT-20120803
 10/7/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE IS GAS ON PLAN PAGE P-8.3 INDICATING THAT
 THERE WILL BE 12 GAS TANKLESS WATERHEATERS. PLEASE
 INDICATE ON THE PLANS WHERE THESE WILL BE LOCATED? WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 2) ON PLAN PAGE P-8.1 THERE IS A GAS DIAGRAM SHOWN,
 PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS
 THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC
 FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS
 RES SECS. G2413.4.1, G2413.4.2.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
 5) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS
 SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1)
 THROUGH 402.4 (37) OR 2017 FBC FUEL GAS RES. SEC.
 G2413.
 6) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017
 FBC FUEL GAS RES. SEC. G2413.2.
 7) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
 8) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 9) INDICATE ON THE PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATERS AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATERS. THE LOCATION OF THE WATER HEATERS SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 10) REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
 11) SUBMIT A COPY OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 08:21 Rev Time 0.00
Received By medwards Date 2021-12-13 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-09 Cont ID  
Sent By lmarchan Date 2021-12-09 Time 13:29 Rev Time 0.00
Received By lmarchan Date 2021-11-15 Time 15:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-04 Cont ID  
Sent By shill Date 2021-10-04 Time 14:52 Rev Time 0.00
Received By shill Date 2021-09-07 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-06-17 Cont ID  
Sent By lmarchan Date 2021-06-17 Time 08:41 Rev Time 0.00
Received By lmarchan Date 2021-05-05 Time 13:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-16 Cont ID  
Sent By shill Date 2021-03-16 Time 10:11 Rev Time 0.00
Received By shill Date 2021-01-04 Time 08:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By lmarchan Date 2021-09-27 Time 14:44 Rev Time 0.00
Received By lmarchan Date 2021-09-02 Time 15:12 Sent To  
Notes
2021-09-27 14:16:09RECEIPT MU-2021-040653 - $1,809,587.28 PAID
2021-09-02 15:12:139/2/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:50 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 14:50 Sent To  
Notes
2021-02-10 14:51:02PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 08:19 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 08:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2021-11-30 Cont ID  
Sent By medwards Date 2021-11-30 Time 14:06 Rev Time 0.00
Received By medwards Date 2021-11-30 Time 11:49 Sent To  
Notes
2021-11-30 14:07:265TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M7.1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATIONS
 FROM 2020FBC M TABLE 403.3.1.1 AND CODE SECTION
 403.3.1.1. THE VENTILATION CALCULATIONS SEEM TO BE A
 MIX BETWEEN FBC M TABLE 403.3.1.1 AND ASHRAE 62.1-2013.
 PLEASE REMOVE ALL PARTS NOT ASSOCIATED WITH FBC M
 403.3.1.1 AS YOU CANNOT MIX BOTH CALCULATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-09-21 Cont ID  
Sent By medwards Date 2021-09-21 Time 07:09 Rev Time 0.00
Received By medwards Date 2021-09-21 Time 07:08 Sent To  
Notes
2021-09-21 07:09:104TH REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 THE MECHANICAL REVIEW COULD NOT BE COMPLETED AS THE
 REVISED SHEETS BELOW WERE NOT SUBMITTED.
  
 1) THE REVISED SHEET LOADED UNDER SHEET M2.1.1 IS
 ACTUALLY SHEET M2.1. PLEASE SUBMIT A REVISED SHEET
 M2.1.1.
  
 2) REVISED SHEET M7.1 HAS NOT BEEN SUBMITTED TO SHOW
 THE VENTILATION CALCULATIONS THAT WERE REQUESTED.
  
 3) REVISED SHEET M8.1 WAS NOT SUBMITTED TO SHOW THE
 DETAIL FOR THE INTAKE AIR.
  
 4) REVISED SHEETS M4.1, M4.2 WERE NOT SUBMITTED IN THIS
 CYCLE.
  
 5) THERE IS NO SHEET M4.3
  
  
 PLAN REVIEW RESULTS: DENIED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-09-08 Cont ID  
Sent By medwards Date 2021-09-08 Time 11:02 Rev Time 0.00
Received By medwards Date 2021-09-08 Time 11:02 Sent To  
Notes
2021-09-08 11:05:58THE LETTER SUBMITTED FROM MSA ARCHITECTS, INC. TITLED "
 1915PBRS COVER LETTER REVD 2021.08.10 UPDATED DOES NOT
 CONTAING THE ATTACHMENT STATED. PLEASE PROVIDE A SCOPE
 OF WORK FOR THE MECHANICAL REVISIONS. I CANNOT REVIEW
 THE DRAWINGS UNTIL A REVISION NARRATIVE HAS BEEN
 SUBMITTED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-05-26 Cont ID  
Sent By medwards Date 2021-05-26 Time 09:33 Rev Time 0.00
Received By medwards Date 2021-05-26 Time 09:03 Sent To  
Notes
2021-05-26 09:33:571ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THE MECHANICAL REVISIONS WERE NOT
 INCLUDED IN THIS RESUBMITTAL. PLEASE SEND REVISED
 DRAWINGS AND A RESPONSE LETTER FOR EACH COMMENT FROM
 THE FIRST REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-01-29 Cont ID  
Sent By medwards Date 2021-01-29 Time 07:43 Rev Time 0.00
Received By medwards Date 2021-01-28 Time 10:46 Sent To  
Notes
2021-01-29 07:43:301ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20120803
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE DEMO KITCHEN WILL NEED TO HAVE A
 SEPARATE PERMIT AND REVIEW FOR THE HOOD SYSTEM ALONG
 WITH AN AIR BALANCE REPORT. FBC M 508.1.2
  
 2) SHEET M2.1: PLEASE SHOW HOW THE LOUNGE/LOBBY WILL BE
 CONDITIONED. FBC 107.2.1
  
 3) SHEET M2.1.1: PLEASE SHOW VENTILATION FOR THE
 LOADING ZONE. FBC M TABLE 403.3.1.1
  
 4) SHEET M2.1.1: PLEASE SHOW HOW THE BIKE STORAGE WILL
 BE VENTILATED. FBC M TABLE 403.3.1.1
  
 5) PLEASE SHOW CONDENSATION DRAINAGE FOR THE MECHANICAL
 SYSTEMS AND WHERE THEY DRAIN. FBC M 307.2.1
  
 6) SHEET M2.2: PLEASE EXPLAIN WHY THE MECHANICAL CLOSET
 FOR AHU-1 DOES NOT HAVE RATED WALLS. FBC 107.2.1
  
 7) SHEET M2.1: IT APPEARS THAT AHU-7 IS LOCATED IN THE
 CORRIDOR WITHOUT A MECHANICAL CLOSET. HOW ARE YOU
 PROVIDING SEPARATION OF THE UNIT FROM THE CORRIDOR? FBC
 107.2.1
  
 8) SHEET M7.1: PLEASE PROVIDE OUTDOOR AIR AND
 VENTILATION CALCULATIONS FOR ALL SPACES IN THIS
 BUILDING. FBC M TABLE 403.3.1.1
  
 9) PLEASE PROVIDE DETAILS FOR THE AIR INTAKE AND
 EXHAUST TERMINATIONS FOR THE UNITS. FBC 107.2.1
  
 10) SHEETS M4.1, M4.2: PLEASE SHOW DRYER DUCT LENGTHS
 FOR EACH UNIT. IF THE DUCT EXTENDS BEYOND THE LENGTH
 ALLOWED BY THE CODE PLEASE PROVIDE THE MAKE MODEL AND
 ALLOWABLE DUCT LENGTHS OF THE DRYERS SPECIFIED. FBC M
 504.8.4.2
  
 11) SHEETS M4.1, M4.2: PLEASE SHOW THAT THE DRYER DUCT
 MEETS LENGTH IDENTIFICATION. FBC M 504.8.5
  
 12) SHEET M4.2: AHU-B FOR UNIT B AND UNIT B1-MOD
 INDICATES AHU-B IS SUPPLYING 840 CFM BUT SHEET M7.1
 INDICATES THAT AHU-B WILL ONLY SUPPLY 800 CFM. PLEASE
 CORRECT THIS. FBC EC C403
  
 13) SHEET M4.2: INDICATES THAT AHU-B IS SUPPLYING 860
 CFM BUT SHEET M7.1 INDICATES THAT AHU-B?S MAXIMUM
 SUPPLY IS 800 CFM. PLEASE CORRECT THIS. FBC EC C403
  
 14) PLEASE SHOW THAT THE PARKING GARAGE MEETS
 VENTILATION REQUIREMENTS OF FBC M 404
  
 15) THE PERMIT APPLICATION INDICATES WORK DESCRIPTION
 AS A 374 UNIT APARTMENT BUILDING BUT PAGE 22 OF 48 IN
 THE ENERGY GAUGE CALCULATIONS UNDER SPACES THE UNITS
 ARE LISTED AS SERVING ?GUEST ROOMS (HOTEL)? PLEASE BE
 CONSISTENT, IF THIS IS AN APARTMENT BUILDING THE ENERGY
 GAUGE SHOULD REFLECT THIS. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-11-20 Cont ID  
Sent By abelisle Date 2021-11-20 Time 12:37 Rev Time 0.00
Received By abelisle Date 2021-11-16 Time 17:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-10-04 Cont ID  
Sent By abelisle Date 2021-10-04 Time 06:56 Rev Time 0.00
Received By abelisle Date 2021-10-02 Time 07:34 Sent To  
Notes
2021-10-04 06:44:293RD REVIEW FBC-2017 PLUMBING
 PERMIT-20120803
 10/4/2021
  
 CODES IN EFFECT:
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE
 PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 2) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY
 WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE
 WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25
 FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL
 COMPLY WITH SEC, 4.19.2.2.
 4) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY
 DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON
 AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER
 TABLE 403.1 OF THE FBC-PLUMBING.
 5) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL THE
 TOILET STALLS IN THE COMMON AREA TOILET ROOMS. COMPLY
 WITH FBC-PLUMBING SEC.405.3.1.
 6) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S
 RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING
 SEC.403.6 & TABLE 403.6.
 7) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI
 A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER
 TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1
 SEC.4.25.
 8) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE
 DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO
 THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI
 A117.1 SEC. 4.16, 4.17 & FIGURE 228.
 9) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN.
 COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF
 ANSI A117.1 SEC.4.16.2.
 10) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 11) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE
 DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS
 PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29.
 12) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE
 PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER
 FBC-PLUMBING SEC.417.5.2.
 13) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR
 EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS
 USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 14) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES
 THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A
 MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43.
 15) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS
 WILL COMPLY WITH ANSI A117.1 - 1986.
 16) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND
 A-10.4. CLARIFY.
 17) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A
 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING
 OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM
 PER FHADM PAGE 7.39.
 18) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET
 AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME.
 CLARIFY.
 19) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO
 SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN
 SUBMITTED WITH THESE PLANS. CLARIFY.
 20) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL
 DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 21) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL
 ROOM.CLARIFY.
 22) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2.
 THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5.
 CLARIFY.
 23) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND
 LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION
 OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 24) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A
 RISER IN STAIR #2. THIS IS NOT PERMITTED PER
 FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO
 OCCUR ON ALL LEVELS. CLARIFY.
 25) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 26) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3
 AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON
 SHT. A-2.1. CLARIFY.
 27) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO
 MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2
 INCH WATER SUPPLY BRANCH. CLARIFY.
 28) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD
 NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY.
 29) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS
 ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1,
 NOT P-4.2. CLARIFY.
 30) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 31) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 32) SHT. P-5.2 - SANITARY AND WATER RISERS -
 IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM
 NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1.
 33) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY
 DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE
 MANUFACTURER'S INFORMATION AND THE APPROVED LISTING
 NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1.
 34) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A
 RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE
 FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL
 723.
 35) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE
 DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY
 SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE
 SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5)
 UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING.
 36) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND
 TABLE 308.5.
 37) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL
 SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS,
 ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 38) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED
 PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED
 ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING
 608.13.2.
 39) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE
 PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE
 LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC.
 606.3.
 40) SUBMIT SANITARY AND WATER RISERS FOR ALL THE COMMON
 AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB AMEND. TO
 FBC SEC. 107.3.5.1.3.
 41) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS SHALL
 BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING
 SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE
 1024.
 42) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER
 SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER
 SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 43) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER
 DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A
 BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING
 VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER
 PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL
 BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR
 REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR
 REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER
 FBC SECS.604.8, 604.8.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-06-17 Cont ID  
Sent By tklarge Date 2021-06-17 Time 08:31 Rev Time 0.00
Received By tklarge Date 2021-05-27 Time 14:41 Sent To  
Notes
2021-06-14 09:31:221) SHT. C.07 - PLACE A NOTE ON THE PLANS THAT SEPARATE
 PERMITS WILL BE REQUIRE FOR THE BACKFLOW PREVENTERS PER
 THE CITY OF WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL.
 2) THIS BUILDING WAS DESIGNED UNDER THE FAIR HOUSING
 ACT DESIGN MANUAL-1998. INDICATE ON THE PLANS FOR EACH
 UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS USED
 IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 3) THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A-2.1.2 - THE B1 UNITS DO NOT SHOW ANY
 LAVATORIES OR WATER CLOSETS ON THE FLOOR PLAN. THIS
 SEEMS TO APPEAR ON ALL LEVELS.CLARIFY.
 5) SHT. A-2.1.2 - THE LAUNDRY ROOM #169 SHALL COMPLY
 WITH ANSI A117.1- 1986 FOR FAIR HOUSING COMPLIANCE.THE
 WASHER AND DRYER SHALL COMPLY WITH ANSI A117.1 SEC.4.25
 FOR CONTROLS AND OPERATING MECHANISMS.THE SINK SHALL
 COMPLY WITH SEC, 4.19.2.2.
 6) PROVIDE A PLUMBING FIXTURE COUNT TABLE AND OCCUPANCY
 DESIGNATION AND OCCUPANT LOAD FOR EACH OF THE COMMON
 AREAS BASED ON THE OCCUPANCY AND OCCUPANT LOAD PER
 TABLE 403.1 OF THE FBC-PLUMBING.
 7) SHT. A-2.1.2 - THE NOTE AT THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.1.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.1.2. CLARIFY.
 8) SUBMIT ENLARGED TOILET ROOM FLOOR PLANS FOR ALL THE
 COMMON AREA TOILET ROOMS SHOWING THE REQUIRED CLEAR
 FLOOR SPACES FOR ALL HANDICAPPED FIXTURES. ALSO, SHOW
 THE CLEAR INSIDE DIMENSONS (L X W) OF EACH TOILET
 ROOM.CLEARANCES FOR WATER CLOSETS SHALL COMPLY WITH
 ANSI A117.1 SEC.4.16.COMPLY WITH ANSI A117.1-1986.
 9) SHT. SHT. A-2.2.2 - THE DOORS TO TOILET ROOMS A-109
 & A-110 APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR
 THE LAVATORIES. COMPLY WITH ANSI A117.1-1986
 SEC.4.22.2.
 10) SHT. A-2.1.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.1.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.1.1. CLARIFY.
 11) SHT. A-2.1.2. - SHOW THE LENGTH AND WIDTH OF ALL
 THE TOILET STALLS IN THE COMMON AREA TOILET ROOMS.
 COMPLY WITH FBC-PLUMBING SEC.405.3.1.
 12) SHT. A-2.1.2 - THE WALL SURFACE AROUND THE MOP
 SINKS SHALL COMPLY WITH FBC-BUILDING SEC. 1210.2.2.
 13) A MINIMUM OF 2 DRINKING FOUNTAINS WILL BE REQUIRED
 FOR THE FITNESS CENTER PER AND POSSIBLY OTHER AMENITY
 AREAS.FBC-PLUMBING TABLE 403.1 & SEC.410.3.
 14) SHT. A-2.1.2 - A URINAL IS REQUIRED IN THE MEN'S
 RESTROOM #151 AT THE POOL AREA PER FBC-PLUMBING
 SEC.403.6 & TABLE 403.6.
 15) SHT. A-2.1.2 - ALL SINKS LOCATED IN THE COMMON
 AREAS SHALL COMPLY WITH ANSI A117.1 SEC.4.19.2.2,
 4.19.3, 4.19.4, 4.19.5.
 16) SHT.A-2.2.1- THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.2.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.2.1. CLARIFY.
 17) THE DOOR IN THE C1 UNIT HALL BATH APPEARS TO SWING
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY IF THAT IS
 DESIGNED AS THE ADAPTABLE BATHROOM. COMPLY WITH FHADM
 (FAIR HOUSING ACT DESIGN MANUAL) PAGE 7.39.THIS APPLIES
 TO ALL LEVELS. CLARIFY.
 18) UNIT C1 - THE SHOWER DOOR IN THE MASTER BATH SWINGS
 INTO THE CLEAR FLOOR SPACE FOR THE SHOWER AND APPEARS
 TO PREVENT THE ACCESS TO THE CONTROLS IF THIS IS THE
 ADAPTABLE/USABLE BATHROOM. COMPLY WITH FHADM PAGE
 7.56.THIS APPLIES TO ALL LEVELS.
 19) UNIT C1 - THE HALL BATH IS MISSING THE WATER
 CLOSET, LAVATORY AND SHOWER ON THE FLOOR PLANS. THIS
 APPEARS TO OCCUR ON ALL LEVELS.CLARIFY.
 20) UNIT ST1 & ST1 MOD - THE DOORS IN THE BATHROOMS
 APPEAR TO SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORY.COMPLY WITH FHADM PAGE 7.39.
 21) UNITS B1 & B1 MOD - IF THE MASTER BATH IS THE FHA
 COMPLIANT BATHROOM, THE LENGTH OF THE SHOWER WALL
 ADJACENT TO THE WATER CLOSET SHALL NOT EXCEED 24 INCHES
 IN LENGTH AND MUST BE AT LEAST 33 INCHES FROM THE
 OPPOSITE WALL PER THE FHADM PAGE 7.43 & 7.44.
 22) UNIT B2 - IF THE MASTER BATH IS THE FHA COMPLIANT
 BATHROOM, THE LENGTH OF THE WALLS ADJACENT TO THE WATER
 CLOSET SHALL NOT EXCEED 24 INCHES PER THE FHADM PAGE
 7.43 & 7.44.ALSO, SHOW THE CLEAR FLOOR PACE FOR THE
 WATER CLOSET PER THE FHADM PAGE 7.43.
 23) SHT. A-4.8 - THE ROOM FINISH SCHEDULE FOR THE
 COMMON AREAS IS BLANK. CLARIFY.
 24) SHT. A-2.3 - THE NAMING CONVENTION FOR THE PLAN
 NOTES THAT IT IS FOR LEVELS 3 TO 5 BUT THE PLAN STATES
 IT IS FOR LEVEL 3 ONLY. CLARIFY.
 25) SHT. A-2.3.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 26) SHT.A-2.3.2 - THE NOTE AT THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.2. CLARIFY.
 27) SHT. A-2.4.1 - THE NOTE AT THE BOTTOM OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 28) SHT. A-2.4.2 - THE NOTE ON THE TOP OF THE SHEET
 STATES " REFER TO PARTIAL PLAN SHEET A-2.3.2 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 SHEET A2.3.2. CLARIFY.
 29) SHT. A-2.5.1- THE NOTE ON THE BOTTOM OF THE SHEET
 STATES "" REFER TO PARTIAL PLAN SHEET A-2.3.1 FOR
 INFORMATION ON THIS AREA." THERE IS NO PARTIAL PLAN ON
 A-2.3.1. CLARIFY.
 30) SHT .A-2.5.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.3.2. THERE IS NO
 PARTIAL PLAN ON A-2.3.2. CLARIFY.
 31) SHT. A-2.6.1 - THE NOTE ON THE BOTTOM OF THE PAGE
 REFERS TO PARTIAL PLAN SHEET A-2.4.1.SHT A-2.4.1 IS FOR
 LEVEL 4 AND SHT. A-2.6.1 IS FOR LEVEL 6. CLARIFY.
 32) SHT. A-2.6.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.4.2. THERE IS NO
 PARTIAL PLAN ON A-2.4.2. ALSO, SHT. A-2.6.2 IS FOR
 LEVEL 6 AND SHT. A-2.4.2 IS FOR LEVEL 4.CLARIFY.
 33) SHT. A-2.7.1 - THE NOTE ON THE BOTTOM OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT.A-2.5.1.THERE IS NO
 PARTIAL PLAN ON SHT. A-2.5.1. ALSO, SHT. A-2.5.1 IS FOR
 LEVEL 5 AND SHT. A-2.7.1 IS FOR LEVEL 7. CLARIFY.
 34) SHT. A-2.8.1 - THE NOTE ON THE BOTTOM OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT.A-2.6.1.THERE IS NO
 PARTIAL PLAN ON SHT. A-2.6.1. ALSO, SHT. A-2.6.1 IS FOR
 LEVEL 6 AND SHT. A-2.8.1 IS FOR LEVEL 8. CLARIFY.
 35) SHT. A-2.8.2 - THE NOTE ON THE TOP OF THE PLAN
 REFERS TO A PARTIAL PLAN ON SHT. A-2.6.2. THERE IS NO
 PARTIAL PLAN ON SHT. A-2.6.2. ALSO, SHT. A-2.6.2 IS FOR
 LEVEL 6 AND SHT. A-2.8.2 IS FOR LEVEL 8. CLARIFY.
 36) SHT. A-2.9.1 - THE NOTE ON THE TOP OF THHE SHEET
 REFERS TO A PARTIAL PLANON SHT. A-2.7.2. THERRE IS NO
 PARTIAL PLAN ON A-2.7.2. ALSO, SHT. A-2.7.2 IS FOR
 LEVEL 7 AND SHT. A-2.9.1 IS FOR THE ROOF LEVEL.
 CLARIFY.
 37) SUBMIT THE INTERIOR ELEVATION DESIGNATIONS FOR THE
 DWELLING UNITS AS SHOWN ON THE FLOOR PLANS FOR THE
 UNITS ON SHEETS A-4.1, A-4.2, A-4.3 & A-4.4. SHOW THE
 HEIGHT DIMENSIONS OF THE KITCHEN AND BATHROOM CABINETS
 FROM THE FLOOR TO THE TOP OF THE COUNTER.WPB AMEND. TO
 FBC SEC. 107.2.1, FHADM PAGE 7.15 & 7.52.
 38) SHT. A-5.1 - POWDER ROOM #A-111 - SHOW THE REQUIRED
 CLEAR FLOOR SPACES FOR THE WATER CLOSET AND THE
 LAVATORY. COMPLY WITH ANSI A117.1-86 SECTIONS 4.16.2 &
 4.19.3.
 39) SHT. A-5.1- POWDER ROOM #A-111 - THE DOOR TO THE
 TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR SPACE
 FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM CANNOT
 SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN THE
 ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND CLOSE
 THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND EXIT.
 CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE INSIDE THE
 TOILET ROOM.ANSI A117.1 SEC.4.22.2.
 40) SHT. A-5.1 - TOILET ROOMS # 109 & 110 - THE DOOR TO
 THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET ROOM
 CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE WITHIN
 THE ROOM FOR A PERSON USING A WHEELCHAIR TO ENTER AND
 CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE DOOR, AND
 EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING SPACE
 INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2.
 41) SHT. A-5.1 - TOILET ROOMS #109 & 110 SHALL BE
 GENDER SPECIFIC (MALE & FEMALE) PER FBC-PLUMBING SEC.
 403.2.
 42) SHT. A-5.1 - DETAILS #1, #2, & #3 STATES THE GRAB
 BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE
 BOTTOM OF THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4
 AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO
 THE CENTERLINE OF THE BAR.
 43) SHT. A-5.3 - STAFF TOILET ROOMS #170 & 111- THE
 DOOR TO THE TOILET ROOM APPEARS TO SWING INTO THE CLEAR
 FLOOR SPACE FOR THE LAVATORY.THE DOOR TO THE TOILET
 ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING SPACE
 WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR TO
 ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN THE
 DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED MANEUVERING
 SPACE INSIDE THE TOILET ROOM. ANSI A117.1 SEC.4.22.2.
 44) SHT. A-5.3 - DETAILS #2 & #4 STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 45) SHT. A-5.3 - DETAIL #1 - THE SINK AT THE DOG SPA
 SHALL BE A MAXIMUM OF 6-1/2 INCHES DEEP PER ANSI A117.1
 SEC. 4.19.2.2. A CLEAR FLOOR SPACE 30 INCHES BY 48
 INCHES COMPLYING WITH ANSI A117.1 SEC. 4.2.4 SHALL BE
 PROVIDED IN FRONT OF THE SINK TO ALLOW A FORWARD
 APPROACH.SHOW THE CLEAR FLOOR SPACE ON THE PLANS.
 46) A-5.3 - THE TUB IN THE DOG SPA SHALL COMPLY WITH
 ANSI A117.1 SEC. 4.20.2 FOR CLEAR FLOOR SPACE. THE
 DRYER HEIGHT SHALL COMPLY WITH ANSI A117.1 SEC.
 4.25.3.CONTROLS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST.ANSI A117.1 SEC.4.25.4.
 47) A-5.4 - DETAIL #1 - WOMEN'S RESTROOM #152 & DETAIL
 #2, WOMEN'S RESTROOM #A-119 - SHOW THE DIMENSION FROM
 THE CENTERLINE OF THE WATER CLOSET IN THE ACCESSIBLE
 TOILET STALL TO THE WALL ADJACENT TO THE WATER CLOSET.
 COMPLY WITH ANSI A117.1 SEC. 4.16, 4.17 & FIGURE 28.
 48) SHT. A-5.4 - DETAIL #1 - SHOW THE REQUIRED CLEAR
 FLOOR SPACE FOR THE WATER CLOSET IN THE ACCESSIBLE
 STALL. COMPLY WITH ANSI A117.1 SEC.4.16.2 & FIGURE 28.
 49) SHT. A-5.4 - DETAIL #1 - A URINAL IS REQUIRED IN
 THE MEN'S RESTROOM #151 PER FBC-PLUMBING TABLE 403.6.
 50) SHT. A-5.4 - DETAILS #3, 4, 5, 6, SHOW THE HEIGHT
 OF THE LAVATORY RIM AT 32 INCHES. THIS HEIGHT MAY NOT
 PROVIDE THE REQUIRED 27 INCHES UNDER THE LAVATORY FOR
 THE CLEAR FLOOR SPACE PER ANSI SEC. 4.19.3 AND ALSO THE
 CLEARANCE OF AT LEAST 29 INCHES FROM THE FLOOR TO THE
 BOTTOM OF THE APRON.REFER TO FIGURE 31 OF ANSI A117.1.
 51) SHT. A-5.4 - DETAILS #1 & #2 - BOTH DETAILS ARE
 LABELED AS "POOL ACESS/PAVILLION LEVEL 1". WHICH ONE IS
 FOR THE POOL? CLARIFY.
 52) SHT. A-5.4 - DETAILS # 3, 4, 5, 6, 7, & 8 STATES
 THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE BUT THE ELEVATION HEIGHT LINE IS SHOWN
 AT THE BOTTOM OF THE GRAB BAR. ANSI A117.1 SEC. 4.16.4
 AND FIGURE 29 REQUIRES THE GRAB BARS TO BE MEASURED TO
 THE CENTERLINE OF THE BAR.
 53) SHT. A-5.4 - SHOW THE LENGTH OF THE SIDE AND REAR
 GRAB BARS FOR THE WATER CLOSETS ON THE ELEVATION
 DETAILS.SHOW THE DISTANCES OF THE GRAB BARS FROM THE
 SIDE AND REAR WALLS PER ANSI A 117.1 SEC.4.16.4 &
 FIGURE 29.
 54) TOILET PAPER DISPENSERS SHALL COMPLY WITH ANSI
 A117.1 SEC.4.16.6 AND FIGURE 29 (B). SOAP AND PAPER
 TOWEL DISPENSERS SHALL COMPLY WITH ANSI A117.1
 SEC.4.25.
 55) SHT. A-5.5 - POWDER ROOM # A-802 - SHOW THE
 DIMENSION FROM THE CENTERLINE OF THE WATER CLOSET TO
 THE WALL ADJACENT TO THE WATER CLOSET. COMPLY WITH ANSI
 A117.1 SEC. 4.16, 4.17 & FIGURE 228.
 56) SHT. A-5.5 - POWDER ROOM #A-802 - SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET ON THE PLAN.
 COMPLY WITH ONE OF THE CONFIGURATIONS IN FIGURE 28 OF
 ANSI A117.1 SEC.4.16.2.
 57) SHT. A-5.5 - POWDER ROOM #A-802 - THE DOOR SWINGS
 INTO THE CLEAR FLOOR SPACE FOR THE LAVATORY.THE DOOR TO
 THE TOILET ROOM CANNOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE UNLESS SUFFICIENT MANEUVERING
 SPACE WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR
 TO ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN
 THE DOOR, AND EXIT. CLEARLY SHOW THIS REQUIRED
 MANEUVERING SPACE INSIDE THE TOILET ROOM. ANSI A117.1
 SEC.4.22.2.
 58) SHT. A-5.5 - POWDER ROOM # A-803 - THE CLEAR FLOOR
 SPACES FOR THE FIXTURES ARE CONFUSING AND DO NOT MAKE
 SENSE. CLEAN THIS FLOOR PLAN UP AND CLEARLY SHOW THE
 REQUIRED CLEAR FLOOR SPACES FOR THE FIXTURES.THE CLEAR
 FLOOR SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL
 APPROACH WHICH IS NOT ALLOWED.A 30 INCH BY 48 INCH
 CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1
 SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2,
 FIGURE 28, AND SEC. 4.19.3 & FIG. 32.
 59) SHT. A-5.5 - DETAILS #1 & #3 - STATES THE GRAB BARS
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 BUT THE ELEVATION HEIGHT LINE IS SHOWN AT THE BOTTOM OF
 THE GRAB BAR. ALSO, ANSI A117.1 SEC. 4.16.4 AND FIGURE
 29 REQUIRES THE GRAB BARS TO BE MEASURED TO THE
 CENTERLINE OF THE BAR.
 60) SHT. A-5.5 - .ELEVATION DETAILS - SHOW THE
 DISTANCES OF THE GRAB BARS FROM THE SIDE AND REAR WALLS
 PER ANSI A 117.1 SEC.4.16.4 & FIGURE 29.
 61) SHT. A-5.5 - DETAIL #2 - THE WALL ADJACENT TO THE
 WATER CLOSET DOES NOT SHOW THE REQUIRED GRAB BAR.
 CLARIFY.
 62) SHT. A-5.5 - SUBMIT A KEYNOTE LEGEND OR PLACE A
 NOTE ON THE PLAN REFERENCING THE SPECIFIC SHEET WHERE
 THE KEYNOTES CAN BE FOUND.
 63) SHT. A-5.5 -POWDER ROOM #A-802 - THE CLEAR FLOOR
 SPACE FOR THE LAVATORY APPEARS TO SHOW A PARALLEL
 APPROACH WHICH IS NOT ALLOWED. A 30 INCH BY 48 INCH
 CLEAR FLOOR SPACE SHALL BE PROVIDED IN FRONT OF A
 LAVATORY TO ALLOW A FORWARD APPROACH PER ANSI A117.1
 SEC.4.19.3. COMPLY WITH ANSI A 117.1 SEC. 4.16.2,
 FIGURE 28, AND SEC. 4.19.3 & FIG. 32.
 64) SHT. A-8.3 - DETAIL #2 - THE SHOWER BASE SHALL BE
 PITCHED ONE-QUARTER INCH PER FOOT TOWARD THE DRAIN PER
 FBC-PLUMBING SEC.417.5.2.
 65) SHTS. A-10.1 & A-10.2 - INDICATE ON THE PLANS FOR
 EACH UNIT WHICH DESIGN SPECIFICATION ("A" OR "B") WAS
 USED IN THE DESIGN OF THE UNITS. WPB AMEND. TO FBC SEC.
 107.2.1.
 66) SHTS. A-10.1, A-10.2, A-10.3, A-10.4 - LAVATORIES
 THAT ARE LOCATED NEXT TO WATER CLOSETS SHALL HAVE A
 MAXIMUM DEPTH OF 24 INCHES PER THE FHADM PAGE 7.43.
 67) PLACE A NOTE ON THE PLANS THAT THE COMMON AREAS
 WILL COMPLY WITH ANSI A117.1 - 1986.
 68) THERE ARE DUPLICATE SHEETS LABELED A-10.3 AND
 A-10.4. CLARIFY.
 69) SHT. A-10.3 - UNIT B2 - THE DOOR SWINGS INTO THE
 CLEAR FLOOR SPACE FOR THE LAVATORY IN THE HALL BATH. A
 30 INCH BY 48 INCH CLEAR FLOOR SPACE OUTSIDE THE SWING
 OF THE DOOR AS IT IS CLOSED IS REQUIRED IN THE BATHOOM
 PER FHADM PAGE 7.39.
 70) SHT. A-10.4 - AMENITY AND LEASING ACCESSIBILITY
 DETAILS - ALL COMMON AREAS SHALL COMPLY WITH ANSI
 A117.1. REMOVE THE REFERENCES AND DETAILS FROM THE
 FBC-ACCESSIBILITY ON THIS SHEET AS THEY DO NOT APPLY.
 71) SHTS. A-10.3 & A-10.4 APPEAR TO BE THE SAME SHEET
 AND SHEETS A-10.4 & A-10.5 APPEAR TO BE THE SAME.
 CLARIFY.
 72) SHT. P-0.1 - GENERAL NOTE #1 REFERS TO
 SPECIFICATIONS. JOB SPECIFICATIONS HAVE NOT BEEN
 SUBMITTED WITH THESE PLANS. CLARIFY.
 73) SHT. P-2.0 - KEYNOTE #5 - LIST THE SPECIFIC CIVIL
 DRAWING WHERE THE CONTINUATION OF THE SANITARY SEWER
 CAN BE FOUND. WPB AMND.TO FBC SEC. 107.2.1.
 74) SHT. P-2.0 - KEYNOTE #9 - LIST THE SPECIFIC DRAWING
 WHERE THE FORCE MAIN DETAIL CAN BE REVIEWED. WPB
 AMND.TO FBC SEC. 107.2.1.
 75) SHT.P-2.1 - KEYNOTE #6 - LIST THE SPECIFIC CIVIL
 DRAWING NUMBER FOR THE CONTINUATION OF THE WATER MAIN.
 WPB AMEND. TO FBC SEC. 107.2.1.
 76) SHT. P-2.1 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 MEN'S RESTROOM #A-117, BISTRO BAR, AND MAIL
 ROOM.CLARIFY.
 77) SHT. P-2.1 APPEARS TO SHOW A RISER IN STAIR #2.
 THIS IS NOT PERMITTED PER FBC-BUILDING SEC.1023.5.
 CLARIFY.
 78) SHT. P-2.1.1 - PROVIDE MATCH LINES FOR THE PLAN AND
 LIST THE SPECIFIC CIVIL DRAWINGS FOR THE CONTINUATION
 OF THE STORM DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 79) SHT. P-2.2 - THERE ARE CIRCLES ON THE PLAN THAT
 APPEAR TO BE RISERS WITH NO RISER TAGS ATTACHED AND
 RISER TAGS WITH NO RISERS. REFER TO UNIT B1, B2, C1,
 B1- MOD, ND THE BRIDGE AREA. THERE APPEARS TO BE A
 RISER IN STAIR #2. THIS IS NOT PERMITTED PER
 FBC-BUILDING SEC.1023.5. CLARIFY.THESE ISSUES APPEAR TO
 OCCUR ON ALL LEVELS. CLARIFY.
 80) SHT. P-2.6 - IDENTIFY THE UNITS ON THE FLOOR
 PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 81) SHT. P-2.1 - SHOWS A JANITOR ROOM #167 BY STAIR #3
 AND THE SAME ROOM IS SHOWN AS STAFF TOILET ROOM #170 ON
 SHT. A-2.1. CLARIFY.
 82) SHT. P-4.1 - KEYNOTE #12 - LIST THE SPECIFIC
 BUILDING PLAN FOR THE CONTINUATION OF THE SANITARY
 LINES. WPB AMEND. TO FBC SEC. 107.2.1.
 83) SHT.P-2.1 SHOWS A 2 INCH WATER SUPPLY BRANCH TO
 MEN'S TOILET ROOM # A-117 & SHT. P-4.1 SHOWS A 1 1/2
 INCH WATER SUPPLY BRANCH. CLARIFY.
 84) SHT. P-4.2 SHOWS A FLOOR PLAN FOR UNIT C2. I COULD
 NOT FIND THIS UNIT ON ANY OF THE FLOOR PLANS. LARIFY.
 85) SHT. P-4.1 - CLEARLY IDENTIFY/ LABEL THE RESTROOMS
 ON DETAIL 1/P-4.2. NOTE: THIS DETAIL IS ON SHT. P-4.1,
 NOT P-4.2. CLARIFY.
 86) SHT. P-2.1 - THE LAYOUT OF THE PLUMBING FIXTURES
 AND NUMBER OF FIXTURE FOR THE MEN'S AND WOMEN'S TOILET
 ROOMS #151 & #152 DO NOT CORRELATE WITH THE LAYOUT AND
 NUBER OF FIXTURES ON SHT. A-2.1.
 87) SHT. P-2.1 - THE JANITOR ROOM #166 IS NOT SHOWN ON
 SHT. P-2.1. CLARIFY.
 88) SHT.P-5.1 - RISER 5/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 89) SHT. P-5.2 - RISER 10/S - AIR ADMITTANCE VALVES
 CANNOT BE USED WHERE THE HORIZONTAL BRANCH IS LOCATED
 MORE THAN FOUR BRANCH INTERVALS FROM THE TOP OF THE
 STACK UNLESS THE HORIZONTAL BRANCH IS PROVIDED WITH A
 RELIEF VENT THAT SHALL CONNECT TO A VENT STACK OR STACK
 VENT, OR EXTEND OUTDOORS TO THE OPEN AIR PER
 FBC-PLUMBING SEC. 918.3.1.
 90) SHT. P-5.2 - SANITARY AND WATER RISERS -
 IDENTIFY/LABEL EACH RISER WITH THE SPECIFIC RESTROOM
 NUMBER AND AREA. WPB AMEND. TO FBC SEC. 107.2.1.
 91) SHT. P-5.2 - RISER 11/S IS SHOWN ON THIS SHEET BUT
 I COULD NOT FIND THIS RISER ON ANY OF THE PLANS.
 CLARIFY.
 92) SHT. P-5.2 - DETAIL #2 - THE VENT BETWEEEN THE TWO
 WATER CLOSETS APPEARS TO BE A FLAT, DRY VENT. EVERY DRY
 VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE PER
 FBC-PLUMBING SEC.905.3. CLARIFY HOW THIS VENT IS
 CONNECTED TO THE HORIZONTAL DRAIN.
 93) SHT. P-8.1-SHT. P-8.1 - SUBMIT APPROVED ASSEMBLY
 DETAILS FOR THE FIRESTOP PENETRATION DETAILS.SUBMIT THE
 MANUFACTURER'S INFORMATION AND THE APPROVED LISTING
 NUMBERS. WPB AMEND. TO FBC SEC. 107.3.5.1.1.
 94) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE SUB-METERS. IF THE METERS WILL BE LOCATED IN A
 RETURN AIR CLOSET THEY SHALL MEET THE FLAME SPREAD
 INDEX AND SMOKE-DEVELOPED INDEX OF SEC. 602.2.1 OF THE
 FBC-MECHANICAL AND THE TEST CRITERIA OF ASTM E84 OR UL
 723.
 95) SHT. P-8.1 - SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC.
 107.2.1.
 96) SHT. P-8.1 - CLARIFY WHAT TYPE OF EFFLUENT WILL BE
 DISCHARGING FROM THE POOL EQUIPMENT INTO THE SANITARY
 SYSTEM. POOL WATER SHALL NOT BE DISCHARGED TO THE
 SANITARY SYSTEM PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES CHAPTER 90, ARTICLE III, SSEC.90-126 (B)(5)
 UNLESS SSPECIFICALLY AUTHORIZED BY THE CITY IN WRITING.
 97) SSHT. P-8.1 - PIPE HANGER DETAIL - PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC-PLUMBING SEC.308 AND
 TABLE 308.5.
 98) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER DETAIL
 SHOWING ALL RISER CONNECTIONS, PIPE SIZES, VENTS,
 ETC.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 99) SUBMIT A COMPLETE UNDERGROUND STORM DRAINAGE RISER
 DETAIL SHOWING ALL RISER CONNECTIONS, PIPE SIZES, GPM,
 ETC.
 100) SUBMIT A STORM DRAIN RISER SYSTEM FOR THE
 ABOVEGROUND STORM DRAIN COLLECCTION SYSTEM SHOWING
 RISER TAGS,PIPE SIZES, GPM THROUGH THE DRAINS AND
 PIPES. PROVIDE VERIFICATION THAT THE SIZING
 CALCULATIONS FOR THE SYSTEM INCLUDES 1/2 THE AREA OF
 ANY VERTICAL WALLS AND ANY DRAINAGE OF STORMWATER FROM
 UPPER ROOFS TO THE LOWER ROOF WHERE THE ROOF DRAINS ARE
 LOCATED. FBC-PLUMBING SEC.106.4.WPB AMEND. TO FBC SEC.
 107.2.1.
 101) SHT. A-7.6 - SANITATION UNIT DETAIL - A REDUCED
 PRESSURE BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED
 ON THE TRASH CHUTE WATER LINE PER FBC-PLUMBING
 608.13.2.
 102) THE WASHING MACHINE WATER SUPPLY VALVES SHALL BE
 PROVIDED WITH ACCESS WITHOUT MOVING THE UNIT. SHOW THE
 LOCATION OF THE VALVES ON THE PLANS. FBC-PLUMBING SEC.
 606.3.
 103) SUBMIT SANITARY AND WATER RISERS FOR ALL THE
 COMMON AREA PLUMBING FIXTURES AND TOILET ROOMS. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 104) THE WATER SUPPLY TO DISHWASHERS AND ICEMAKERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER FBC-PLUMBING
 SEC.608..2. THE BACKFLOW DEVICE SHALL COMPLY WITH ASSE
 1024.
 105) SUBMIT A PIPING DETAIL FOR THE DOMESTIC BOOSTER
 SYSTEM AND SUBMIT WATER RISER DIAGAM FOR THE MAIN WATER
 SYSTEM IN THE BUILDING. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 106) PRESSURE REDUCING VALVES ARE REQUIRED ON THE WATER
 DISTRIBUTION SYSTEM WHERE THE WATER PRESSSURE WITHIN A
 BUILDING EXCEEDS 80 PSI STATIC.WATER PRESURE REDUCING
 VALVES SHALL CONFORM TO ASSE 1003 OR CSA B356. WATER
 PRESURE REDUCING VALVES, REGULATORS AND TRAINERS SHALL
 BE SO CONSTRUCTED AND INSTALLED AS TO PERMIT REPAIR OR
 REMOVAL OF PARTS WITHOUT BREAKING A PIPELINE OR
 REMOVING THE VALVE AND TRAINER FROM THE PIPELINE PER
 FBC SECS.604.8, 604.8.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-16 Cont ID  
Sent By abelisle Date 2021-03-16 Time 08:21 Rev Time 0.00
Received By abelisle Date 2021-03-02 Time 16:33 Sent To  
Notes
2021-03-04 18:48:131ST REVIEW FBC-2017 PLUMBING
 PERMIT-20120803
 3/15/2021
  
 CODES IN EFFECT:
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- THIS BUILDING WAS DESIGNED UNDER THE REQUIREMENTS OF
 THE FAIR HOUSING ACT. INDICATE ON THE PLAN IN EACH UNIT
 WHICH DESIGN SPECIFICATION ("A" OR "B" OF THE ACT) WAS
 USED IN THE DESIGN OF THE UNITS.
  
 2- THE WASHING MACHINE VALVES SHALL BE ACCESSIBLE
 WITHOUT MOVING THE UNIT PER THE 2017 FBC SEC. P 606.3
  
 3- THE ADDRESS OF THE PROJECT MUST BE ON THE PLANS. WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4- NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7. PER FBCACC SEC. 211.2 & FBC-PLUMBING SEC.
 410.3.
  
 5- ON PAGE A2.1.2 RR A-110 & RR A-109 WHERE PLUMBING
 FIXTURES ARE REQUIRED, SEPARATE FACILITIES SHALL BE
 PROVIDED FOR EACH SEX. PER FBC P 403.2
  
 6- ON PAGE A2.1.2 B1 UNITS DO NOT SHOW THE LAVATORIES
 OR THE WATER CLOSETS ON THE FLOOR PLAN
  
 7- ON PAGE A2.1.2 ASSE 1022 BACKFLOWS ARE REQUIRED FOR
 THE BISTRO BAR ICE MAKER AND DISHWASHER
  
 8- AN OUTSIDE SHOWER IS REQUIRED FOR THE POOL AREA
  
 9- PLEASE PROVIDE A DETAIL OF WHAT WILL BE INSTALLED IN
 THE DOG SPA
  
 10- REDUCED PRESSURE PRINCIPAL BACKFLOW PREVENTER IS
 REQUIRED FOR THE TRASH CHUTE WATER LINE THAT COMPLIES
 WITH FBCP 608.13.2
  
 11- ON PLAN PAGE A4.3 UNIT B1- PLEASE CLARIFY
 TUB/SHOWER? INDICATED IN THE SHOWER
  
 12- ON PLAN PAGE A4.9 DETAIL 7 & 8 UNIT B2 IS NOT A
 BATHROOM
  
 13- ON PLAN A5.1 IN THE WOMENS RESTROOM A-119 CLEAR
 FLOOR SPACE SHALL NOT IMPEDE ON THE WATER CLOSET 5'
 CLEAR FLOOR SPACE
  
 14- ON PLAN A5.1 BOH ROOM A-120 . PROVIDE ELEVATION ON
 THE CABINETRY AND SINK LOCATION
  
 15- ON PLAN A5.1 POWDER ROOM A-111 RESTROOMS INDICATE
 THE CLEAR FLOOR SPACE FOR THE LAVATORY
  
 16- ON PLAN A5.4 DETAIL NUMBER 2. PLEASE INDICATE THE
 INTERIOR DIMENTIONS OF THE ACCESSIBLE RESTOOMS & IN THE
 WOMENS RESTROOM A-119 CLEAR FLOOR SPACE SHALL NOT
 IMPEDE ON THE WATER CLOSET 5' CLEAR FLOOR SPACE
  
 17- PROVIDE SPECIFICATIONS ON THE ROOF DRAINS THAT WILL
 BE INSTALLED
  
 18- ON PAGE 256-P5.1 AAV'S ARE NOT ALLOWED TO BE
 INSTALLED ON THE 1ST- 4TH FLOORS PER FBCP 918.3.1 WHERE
 THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR.
  
 19- WATER METERS : THERE IS NO INFORMATION ON THE SPECS
 SHOWING THE FLAME SPREAD INDEX AND SMOKE-DEVELOPED
 INDEX OF THE UNIT. IT MUST COMPLY WITH T SEC.602.2.1 OF
 THE MECHANICAL CODE AND COMPLY WITH THE TESTING
 CRITERIA IN ASTM E84 OR UL 723.
  
 20- ON PLAN PAGE A5.4 DETAIL 1 THE 5 FOOT WATER CLOSET
 CLEAR FLOOR SPACE SHALL NOT HAVE ANY OTHER PLUMBING
 FIXTURES INSIDE OF THAT 5 FOOT CLEAR FLOOR SPACE. THE
 URINAL SHALL BE RELOCATED. PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR ALL OF THE ACCESSIBLE PLUMBING FIXTURES IN
 THE MEN'S AND WOMEN'S RESTROOMS.
  
 21- ON PLAN PAGE A5.4 DETAIL 2,3,4,5,8,9,10,11,12,14
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 22- ON PLAN PAGE A5.4 DETAIL 1 & 2 BOTH DETAILS
 INDICATE "POOL ACCESS/ PAVILLION LEVEL 1. PLEASE
 CLARIFY WHICH DETAIL IS FOR THE POOL ACCESS PAVILLION
 AND WHICH DETAIL IS FOR THE RESTROOM.
  
 23. PER FBCACC 2017 603.3 MIRRORS. A SINGLE FULL-LENGTH
 MIRROR CAN ACCOMMODATE A GREATER NUMBER OF PEOPLE,
 INCLUDING CHILDREN. IN ORDER FOR MIRRORS TO BE USABLE
 BY PEOPLE WHO ARE AMBULATORY AND PEOPLE WHO USE
 WHEELCHAIRS, THE TOP EDGE OF MIRRORS SHOULD BE 74
 INCHES (1880 MM) MINIMUM FROM THE FLOOR OR GROUND
  
 24- GRAB BARS ON A5.4 THE SIDE WALL GRAB BAR SHALL BE
 42 INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES
 (305 MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54
 INCHES (1370 MM) MINIMUM FROM THE REAR WALL. THE REAR
 WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG MINIMUM
 AND EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 INCHES (610
 MM) MINIMUM ON THE OTHER SIDE.
  
 25. ON PAGE A5.4 TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
 AND SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS
 SHALL NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT
 DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 26. ON PAGE A5.4 IF SOAP AND TOWEL DISPENSERS ARE
 PROVIDED, THEY MUST BE LOCATED WITHIN THE REACH RANGES
 SPECIFIED IN 308. LOCATE SOAP AND TOWEL DISPENSERS SO
 THAT THEY ARE CONVENIENTLY USABLE BY A PERSON AT THE
 ACCESSIBLE LAVATORY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 14:32 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 14:32 Sent To  
Notes
2021-06-15 14:33:09ROOFING TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By rmcphers Date 2021-02-10 Time 14:51 Rev Time 0.00
Received By rmcphers Date 2021-02-10 Time 14:51 Sent To  
Notes
2021-02-10 14:51:51SEE BUILDING PLAN REVIEW
 WILL NEED A BUILDING PERMIT APPLICATION FOR THE ROOFING
 (MARKED ROOFING)

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-12-14 Cont ID  
Sent By rmcphers Date 2021-12-14 Time 09:44 Rev Time 0.00
Received By rmcphers Date 2021-12-14 Time 09:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-12-06 Cont ID  
Sent By rmcphers Date 2021-12-06 Time 16:00 Rev Time 0.00
Received By rmcphers Date 2021-12-06 Time 16:00 Sent To  
Notes
2021-12-06 16:07:59SIGNATURE REVIEW
  
 DRAWINGS SHOWN BELOW - DO NOT SHOW IN "ADOBE" AS
 DIGITALLY SIGNED.
  
 A-2.6, A-2.6.1, A-2.6.2, A-2.6.1C, A-2.6.2C, A-2.7,
 A-2.7.2C, A-2.8, A-2.8.1, A-2.8.2, A-2.8.1C, A-2.8.2C,
 A-2.9, A-2.9.1, A-4.9, S-2.1A, S-2.1.B, S-2.1.C,
 S-2.1.D, S-2.1.G, S-2.6.A, S-3.4, S-3.9, S-5.5, S-7.3,
 SOIL REPORT (GEOTECHNICAL REPORT), ENERGY CALCS.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-09-30 Cont ID  
Sent By rmcphers Date 2021-09-30 Time 11:56 Rev Time 0.00
Received By rmcphers Date 2021-09-30 Time 10:43 Sent To  
Notes
2021-09-30 11:56:41SIGNATURE REVIEW
  
 DRAWINGS LABELED IN PROJECTDOX SHOWN BELOW - DO NOT
 SHOW IN "ADOBE" AS DIGITALLY SIGNED.
 129 S 2.1.D FOUNDATION.PDF V3
 130 S 2.1.G FOUNDATION.PDF V3
 128 S 2.1.C FOUNDATION.PDF V3
 127 S 2.1.B FOUNDATION.PDF V3
 126 S 2.1.A FOUNDATION.PDF V3
 134 S.2.2.D SECOND FLOOR.PDF V2
 123A A10.5 AMENITY & LEASING ACCESSIBILITY REQ..PDF V2
 109 A7.3 PLANS & SECTIONS STAIR #3.PDF V3
 092 A4.6 UNIT DOOR, FINISH SCHEDULE & TYPES.PDF V3
 080A A2.9.1 BLDG. DIM. FL. PLAN ROOF LEV. SECTOR 2.PDF
 V2
 079A A2.9 BUILDING FLOOR PLAN ROOF LEVEL.PDF V2
 078A A2.8.2C BLDG. CLG. FL. PLAN LEV. 8 SECTOR 2.PDF V2
 077A A2.8.1C BLDG. CLG. FL. PLAN LEV. 8 SECTOR 1.PDF V2
 076A A2.8.2 BLDG. DIM. FL. PLAN LEV. 8 SECTOR 2.PDF V2
 075A A2.8.1 BLDG. DIM. FL. PLAN LEV. 8 SECTOR 1.PDF V2
 074A A2.8 BUILDING FLOOR PLAN LEVEL 8.PDF V2
 073A A2.7.2C BLDG. CLG. FL. PLAN LEV. 7 SECTOR 2.PDF V2
 070A A2.7.1 BLDG. DIM. FL. PLAN LEV. 7 SECTOR 1.PDF V2
 069A A2.7 BUILDING FLOOR PLAN LEVEL 7.PDF V2
 063J A2.5.1C BLDG. CLG. FL. PLAN LEV. 5 SECTOR 1.PDF V2
 063F A2.4.2C BLDG. CLG. FL. PLAN LEV. 4 SECTOR 2.PDF V2
 063E A2.4.1C BLDG. CLG. FL. PLAN LEV. 4 SECTOR 1.PDF V2
 063D A2.4.2 BLDG. DIM. FL. PLAN LEV. 4 SECTOR 2.PDF V2
 063C A2.4.1 BLDG. DIM. FL. PLAN LEV. 4 SECTOR 1.PDF V2
 068A A2.6.2C BLDG. CLG. FL. PLAN LEV. 6 SECTOR 2.PDF V2
 067A A2.6.1C BLDG. CLG. FL. PLAN LEV. 6 SECTOR 1.PDF V2
 066A A2.6.2 BLDG. DIM. FL. PLAN LEV. 6 SECTOR 2.PDF V2
 065A A2.6.1 BLDG. DIM. FL. PLAN LEV. 6 SECTOR 1.PDF V2
 064A A2.6 BUILDING FLOOR PLAN LEVEL 6.PDF V2
 063K A2.5.2C BLDG. CLG. FL. PLAN LEV. 5 SECTOR 2.PDF V2
 063I A2.5.2 BLDG. DIM. FL. PLAN LEV. 5 SECTOR 2.PDF V2
 063B A2.4 BUILDING FLOOR PLAN LEVELS 4.PDF V2
 063 A2.3.2C BLDG. CLG. FL. PLAN LEV. 3 TO 5 SECTOR
 2.PDF V3
 062 A2.3.1C BLDG. CLG. FL. PLAN LEV. 3 TO 5 SECTOR
 1.PDF V3
 061 A2.3.2 BLDG. DIM. FL. PLAN LEV. 3 TO 5 SECTOR 2.PDF
 V3
 060 A2.3.1 BLDG. DIM. FL. PLAN LEV. 3 TO 5 SECTOR 1.PDF
 V3
 059A A2.3 BUILDING FLOOR PLAN LEVEL 3.PDF V2
 123 A10.4 ACCESSIBILITY STANDARDS.PDF V2
 122 A10.3 FAIR HOUSING ACT UNIT PLANS & NOTES.PDF V2
 119 A9.2 FIRE PENETRATION DETAILS.PDF V3
 112 A7.6 TRASH ROOM.PDF V3
 106 A6.5 WALL PARTIAL SECTIONS.PDF V3
 094 A4.8 ROOM FINISH SCHEDULE COMMON AREAS.PDF V3
 091 A4.5 DOOR SCHEDULE AND TYPES COMMON AREAS.PDF V3
 089 A4.3 UNIT PLANS.PDF V3
 085 A3.5 BUILDING SECTIONS.PDF V3
 084 A3.4 BUILDING SECTIONS.PDF V3
 083 A3.3 BUILDING ELEVATIONS.PDF V3
 058 A2.2.2C BLDG. CLG. FL. PLAN LEV. 2 SECTOR 2.PDF V3
 057 A2.2.1C BLDG. CLG. FL. PLAN LEV. 2 SECTOR 1.PDF V3
 056 A2.2.2 BLDG. DIM. FL. PLAN LEV. 2 SECTOR 2.PDF V3
 055 A2.2.1 BLDG. DIM. FL. PLAN LEV. 2 SECTOR 1.PDF V3
 054 A2.2 BUILDING FLOOR PLAN LEVEL 2.PDF V3
 053 A2.1.2C BLDG. CLG. FL. PLAN LEV. 1 SECTOR 2.PDF V3
 052 A2.1.1C BLDG. CLG. FL. PLAN LEV. 1 SECTOR 1.PDF V3
 050 A2.1.1 BLDG. DIM. FL. PLAN LEV. 1 SECTOR 1.PDF V3
 049 A2.1 BUILDING FLOOR PLAN LEVEL 1.PDF V3
 040 SP1 SITE PLAN.PDF V3
 039 MSP1 MASTER SITE PLAN.PDF V3
 003 SD1 SITE DATA.PDF V2
 001 INDEX DRAWINGS.PDF V2
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 15:28 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 15:28 Sent To  
Notes
2021-09-01 15:22:41ORIGINAL SIGNED AND SEALED THRESHOLD FORM TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-29 Cont ID  
Sent By medwards Date 2021-01-29 Time 08:46 Rev Time 0.00
Received By medwards Date 2021-01-29 Time 08:46 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2021-08-16 Cont ID  
Sent By rmcphers Date 2021-08-16 Time 11:12 Rev Time 0.00
Received By rmcphers Date 2021-08-16 Time 11:12 Sent To  
Notes
2021-09-01 15:22:04ORIGINAL SIGNED AND SEALED THRESHOLD FORM TO STORAGE

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-06-15 Cont ID  
Sent By rmcphers Date 2021-06-15 Time 14:29 Rev Time 0.00
Received By rmcphers Date 2021-06-15 Time 14:29 Sent To  
Notes
2021-06-15 14:30:28THRESHOLD BUILDING REVIEW
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
 1) PLEASE FILL OUT THE THRESHOLD INSPECTOR FORMS AND
 PROVIDE THE REQUIRED DOCUMENTS - SEE THE "GUIDELINES
 AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL
 INSPECTORS AND RESIDENT INSPECTORS" - YOU CAN EMAIL
 ([email protected]) FOR A COPY OF THE GUIDELINES.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-09-23 Cont ID  
Sent By llouie Date 2021-09-23 Time   Rev Time 0.00
Received By llouie Date 2021-09-23 Time   Sent To  
Notes
2021-09-23 13:19:37REFERENCES:
  
 * RESOLUTION NO. 228-20
  
 * COMMENCEMENT OF DEVELOPMENT EXTENSION (EO 21-94):
 9/11/2025

Review Stop Z ZONING
Rev No 2 Status F Date 2021-05-13 Cont ID  
Sent By llouie Date 2021-05-13 Time   Rev Time 0.00
Received By llouie Date 2021-05-13 Time   Sent To  
Notes
2021-05-13 13:29:53** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) BUILDING PERMIT PLANS DO NOT MATCH THE PLANS
 APPROVED BY THE CITY COMMISSION. CHANGES HAVE BEEN
 DETECTED (I.E. BUILDING FOOTPRINT, PARKING
 CONFIGURATION, SITE ELEMENTS, ARCHITECTURAL ELEVATIONS,
 ETC.). SUBMISSION, REVIEW AND APPROVAL OF A MINOR
 PLANNED DEVELOPMENT (PD) AMENDMENT APPLICATION
 REFLECTING ALL NEW CHANGES IS REQUIRED. [1/12/2021
 REPEAT COMMENT: A MINOR PD AMENDMENT APPLICATION HAS
 BEEN SUBMITTED (REFERENCE: PB 1837D); HOWEVER, THE
 APPLICATION IS STILL PENDING APPROVAL WITH CITY STAFF.
 ZONING APPROVAL CANNOT BE ISSUED UNTIL THE MINOR PD
 AMENDMENT HAS BEEN APPROVED.]
  
 2.) ALL BUILDING SETBACKS (FROM THE CLOSEST POINT OF
 THE BUILDING) TO THE PROPERTY LINE SHALL BE PROVIDED IN
 THE PLANS. BUILDING SETBACKS CANNOT EXCEED WHAT THE
 ZLDRS AND THE WAIVER(S) TO BUILDING SETBACKS ALLOW.
 (REFERENCE: RESOLUTION NO. 228-20). [1/12/2021 REPEAT
 COMMENT: A MINOR PD AMENDMENT APPLICATION HAS BEEN
 SUBMITTED (REFERENCE: PB 1837D); HOWEVER, THE
 APPLICATION IS STILL PENDING APPROVAL WITH CITY STAFF.
 ZONING APPROVAL CANNOT BE ISSUED UNTIL THE MINOR PD
 AMENDMENT HAS BEEN APPROVED.]
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED, BUT NOT LIMITED TO THE
 FOLLOWING: TREE ALTERATION, LANDSCAPING, IRRIGATION,
 PARKING/PAVING, LIGHTING, SIGNAGE, GATES/FENCE.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * Z = CPD (PALM BEACH RIVER STONE)
  
 * REFERENCE: RESOLUTION NO. 228-20 (CPD); RESOLUTION
 NO. 331-20 (PLAT) - PLAT BOOK 131, PAGE 95.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By llouie Date 2021-01-12 Time   Rev Time  
Received By llouie Date 2021-01-12 Time   Sent To  
Notes
2021-01-12 12:19:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) BUILDING PERMIT PLANS DO NOT MATCH THE PLANS
 APPROVED BY THE CITY COMMISSION. CHANGES HAVE BEEN
 DETECTED (I.E. BUILDING FOOTPRINT, PARKING
 CONFIGURATION, SITE ELEMENTS, ARCHITECTURAL ELEVATIONS,
 ETC.). SUBMISSION, REVIEW AND APPROVAL OF A MINOR
 PLANNED DEVELOPMENT (PD) AMENDMENT APPLICATION
 REFLECTING ALL NEW CHANGES IS REQUIRED.
  
 2.) ALL BUILDING SETBACKS (FROM THE CLOSEST POINT OF
 THE BUILDING) TO THE PROPERTY LINE SHALL BE PROVIDED IN
 THE PLANS. BUILDING SETBACKS CANNOT EXCEED WHAT THE
 ZLDRS AND THE WAIVER(S) TO BUILDING SETBACKS ALLOW.
 (REFERENCE: RESOLUTION NO. 228-20)
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED, BUT NOT LIMITED TO THE
 FOLLOWING: TREE ALTERATION, LANDSCAPING, IRRIGATION,
 PARKING/PAVING, LIGHTING, SIGNAGE, GATES/FENCE.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * Z = CPD (PALM BEACH RIVER STONE)
  
 * REFERENCE: RESOLUTION NO. 228-20 (CPD); RESOLUTION
 NO. 331-20 (PLAT) - PLAT BOOK 131, PAGE 95.
  