Plan Review Details - Permit 20120638
Plan Review Stops For Permit 20120638
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 07:47 Rev Time 0.00
Received By rmcphers Date 2021-01-25 Time 14:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2021-01-11 Time 13:27 Sent To  
Notes
2021-01-11 13:43:14ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 *****COMMENTS BELOW ARE FOR THE "SILCOR 900HA LIQUID
 WATERPROOFING"********
 1) PLEASE PROVIDE INSTALLATION DETAILS ALONG WITH
 STRUCTURAL CALCULATIONS TO SHOW THAT THE LIQUID
 WATERPROOFING WILL MEET OR EXCEED THE REQUIRED WIND
 DESIGN PRESSURES OR PROVIDE A COMPLETE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL THAT SHOWS THE DESIGN
 WIND PRESSURES WILL MEET OR EXCEED THE PRESSURES SHOWN
 ON DRAWING (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER'S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).
 2) R905.15.1 SLOPE.
 LIQUID-APPLIED ROOFING SHALL HAVE A DESIGN SLOPE OF NOT
 LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-23 Cont ID  
Sent By rmcphers Date 2020-12-23 Time 08:21 Rev Time 0.00
Received By rmcphers Date 2020-12-23 Time 08:21 Sent To  
Notes
2020-12-23 08:23:05ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL THAT
 SHOWS THE DESIGN WIND PRESSURES NEEDED SHOWN ON DRAWING
 (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER'S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).
 2) R905.15.1 SLOPE.
 LIQUID-APPLIED ROOFING SHALL HAVE A DESIGN SLOPE OF NOT
 LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By rmcphers Date 2020-12-18 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2020-12-17 Time 15:45 Sent To  
Notes
2020-12-18 08:11:36ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A COMPLETE PRODUCT APPROVAL THAT
 SHOWS THE DESIGN WIND PRESSURES NEEDED SHOWN ON DRAWING
 (S1) - FBC R905.15.3 APPLICATION.
 LIQUID-APPLIED ROOFING SHALL BE INSTALLED IN ACCORDANCE
 WITH THIS CHAPTER AND THE MANUFACTURER?S INSTRUCTIONS.
 THE APPROVED ALLOWABLE UPLIFT RESISTANCE FOR THE
 LIQUID-APPLIED COATINGS SHALL BE EQUAL TO OR GREATER
 THAN THE UPLIFT RESISTANCE FOR THE ROOF BASED ON TABLE
 R301.2(2).

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-01-28 Cont ID  
Sent By rmcphers Date 2021-01-28 Time 07:47 Rev Time 0.00
Received By rmcphers Date 2021-01-21 Time 09:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2021-01-09 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-23 Cont ID  
Sent By rmcphers Date 2020-12-23 Time 08:23 Rev Time 0.00
Received By rmcphers Date 2020-12-18 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-18 Cont ID  
Sent By rmcphers Date 2020-12-18 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2020-12-14 Time 17:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-12 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2021-01-12 Time 08:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-18 Cont ID  
Sent By rmcphers Date 2020-12-18 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2020-12-18 Time 08:11 Sent To  
Notes
***NONE***