Plan Review Stops For Permit 20120595 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2021-04-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-05 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-05 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
mcdouga |
Date |
2021-03-01 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-01 |
Time |
09:27 |
Sent To |
|
|
Notes |
2021-03-01 09:51:53 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) [THE LOCATION OF THE GENERATOR IS NOT SHOWN ON THE | | SURVEY AND THE REQUIRED 10 FT DISTANCE FROM OPENINGS IS | | NOT SPECIFIED.]THE GENERATOR EXHAUST IS REQUIRED TO BE | | 10 FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1 | | INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 2) THE PRE-FAB GENERATOR PAD ENGINEERING IS COMPATIABLE | | WITH THE 24KW GENERATOR SPECIFICATIONS THAT WERE | | SUBMITTED. HOWEVER, THE DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURE. SEE THE SIGNATURE REVIEW | | STOP. | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-23 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-23 |
Time |
09:31 |
Sent To |
|
|
Notes |
2020-12-23 09:40:34 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM | | ANY OPENINGS INTO THE BUILDING. R303.5.1 INTAKE | | OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | 2) THE PRE-FAB GENERATOR PAD ENGINEERING IS COMPATIABLE | | WITH THE 24KW GENERATOR SPECIFICATIONS THAT WERE | | SUBMITTED. HOWEVER, THE DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURE. SEE THE SIGNATURE REVIEW | | STOP. | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | CITY RE-SUBMITTAL FORM. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-03-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-03-10 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-03-10 |
Time |
14:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-12-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-17 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-17 |
Time |
14:23 |
Sent To |
|
|
Notes |
2020-12-17 14:48:57 | PLAN REVIEW / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2014 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE UPDATED LOAD CALC'S. SHOW LOAD SHARING. | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | 2. USE PROPER FILE NAMING GUIDELINES. | | SEE PROJECT DOX QUICK START GUIDE. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2021-04-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-04-07 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-04-07 |
Time |
15:41 |
Sent To |
|
|
Notes |
2021-04-07 17:10:06 | 04/07/21 REVIEWED FOR CODE COMPLIANCE (GAS) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2021-03-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2021-03-19 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2021-03-19 |
Time |
13:17 |
Sent To |
|
|
Notes |
2021-03-19 13:19:45 | IT APPEARS THAT NONE OF THE EXISTING COMMENTS HAVE BEEN | | ADDRESSED ON THIS RESUBMITTAL. | | | | 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU | | LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | G2413.4 (1 ) THROUGH G2413.4 (21). | | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE | | BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS | | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, | | G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY | | SHOW THE DISTANCE AS 39 FEET. | | 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW | | THIS SYSTEM AS A 2 PSI SYSTEM. | | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS | | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. | | 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. | | 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET | | OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1. | | 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2 | | PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING | | REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS | | LINE TO THE GENERATOR. CLARIFY. | | 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR | | IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S | | SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE | | REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE | | BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER | | FFBC-FUEL GAS SEC.410.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2021-01-19 |
Time |
|
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2021-01-19 |
Time |
06:29 |
Sent To |
|
|
Notes |
2021-01-19 06:50:23 | 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU | | LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS | | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) | | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES | | G2413.4 (1 ) THROUGH G2413.4 (21). | | 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS | | METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE | | BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS | | SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1, | | G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY | | SHOW THE DISTANCE AS 39 FEET. | | 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW | | THIS SYSTEM AS A 2 PSI SYSTEM. | | 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS | | SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. | | 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY | | RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS. | | THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED | | INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE | | EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE | | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE | | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM | | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD | | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO | | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH | | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | OUTLET AND THE LOAD OF THE SECTION. | | 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET | | OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1. | | 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2 | | PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING | | REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS | | LINE TO THE GENERATOR. CLARIFY. | | 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR | | IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S | | SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE | | REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE | | BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER | | FFBC-FUEL GAS SEC.410.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-04-15 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-04-15 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-03-24 |
Time |
15:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-03-19 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-03-19 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-02-23 |
Time |
06:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-01-19 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-01-19 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-12-15 |
Time |
10:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
N |
Date |
2021-04-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-04-07 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-04-07 |
Time |
15:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
N |
Date |
2021-03-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2021-03-19 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2021-03-19 |
Time |
13:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
N |
Date |
2021-03-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-03-10 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-03-10 |
Time |
14:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2021-01-19 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2021-01-19 |
Time |
06:28 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2021-01-19 |
Time |
05:33 |
Sent To |
|
|
Notes |
2021-01-19 06:29:11 | THERE IS NO PLUMBING ASSOCIATED WITH THIS PERMIT. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
4 |
Status |
P |
Date |
2021-04-12 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-12 |
Time |
16:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-12 |
Time |
16:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2021-04-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-05 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-05 |
Time |
09:27 |
Sent To |
|
|
Notes |
2021-04-05 09:29:01 | THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2021-03-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-03-01 |
Time |
09:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-01 |
Time |
09:52 |
Sent To |
|
|
Notes |
2021-03-01 09:59:33 | THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | | | | NO SIGNATURE OF CONTRACTOR ON ELECTRIC RISER DIAGRAHM. | | CT |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-12-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-23 |
Time |
09:31 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-23 |
Time |
09:31 |
Sent To |
|
|
Notes |
2020-12-23 09:37:35 | THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE | | ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED | | DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL | | SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT | | THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER | | THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT | | THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | 2020-12-17 14:49:28 | NO SIGNATURE OF CONTRACTOR ON ELECTRIC RISER DIAGRAHM. | | CT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2021-04-14 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-04-14 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2021-04-14 |
Time |
|
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-03-05 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2021-03-05 |
Time |
|
Rev Time |
0.00 |
Received By |
rthermid |
Date |
2021-03-05 |
Time |
|
Sent To |
I |
|
Notes |
2021-03-05 11:40:29 | ADDRESS PREVIOUS ZONING COMMENTS. | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2020-12-17 |
|
|
Cont ID |
|
Sent By |
rthermid |
Date |
2020-12-17 |
Time |
|
Rev Time |
|
Received By |
rthermid |
Date |
2020-12-17 |
Time |
|
Sent To |
I |
|
Notes |
2020-12-17 09:25:03 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: 12/17/2020 | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICATING | | THE SETBACKS OF THE PROPOSED GENERATOR TO ALL PROPERTY | | LINES. PER THE CITY ZONING CODE, MECHANICAL EQUIPMENT | | CANNOT ENCROACH MORE THAN 4 FEET INTOA REQUIRED | | SETBACK. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN | | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | TTY: 800.955.8771 | | E: [email protected] | | W: WPB.ORG | | |
|
|