Plan Review Details - Permit 20120595
Plan Review Stops For Permit 20120595
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2021-04-05 Time 09:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By mcdouga Date 2021-03-01 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2021-03-01 Time 09:27 Sent To  
Notes
2021-03-01 09:51:53PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [THE LOCATION OF THE GENERATOR IS NOT SHOWN ON THE
 SURVEY AND THE REQUIRED 10 FT DISTANCE FROM OPENINGS IS
 NOT SPECIFIED.]THE GENERATOR EXHAUST IS REQUIRED TO BE
 10 FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1
 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) THE PRE-FAB GENERATOR PAD ENGINEERING IS COMPATIABLE
 WITH THE 24KW GENERATOR SPECIFICATIONS THAT WERE
 SUBMITTED. HOWEVER, THE DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE. SEE THE SIGNATURE REVIEW
 STOP.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-23 Cont ID  
Sent By rmcdouga Date 2020-12-23 Time 09:31 Rev Time 0.00
Received By rmcdouga Date 2020-12-23 Time 09:31 Sent To  
Notes
2020-12-23 09:40:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE 10 FEET FROM
 ANY OPENINGS INTO THE BUILDING. R303.5.1 INTAKE
 OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2) THE PRE-FAB GENERATOR PAD ENGINEERING IS COMPATIABLE
 WITH THE 24KW GENERATOR SPECIFICATIONS THAT WERE
 SUBMITTED. HOWEVER, THE DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURE. SEE THE SIGNATURE REVIEW
 STOP.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 15:09 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By cthroop Date 2020-12-17 Time 14:42 Rev Time 0.00
Received By cthroop Date 2020-12-17 Time 14:23 Sent To  
Notes
2020-12-17 14:48:57PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE UPDATED LOAD CALC'S. SHOW LOAD SHARING.
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 2. USE PROPER FILE NAMING GUIDELINES.
 SEE PROJECT DOX QUICK START GUIDE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-04-07 Cont ID  
Sent By lcrespo Date 2021-04-07 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-04-07 Time 15:41 Sent To  
Notes
2021-04-07 17:10:0604/07/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-19 Cont ID  
Sent By tklarge Date 2021-03-19 Time 13:19 Rev Time 0.00
Received By tklarge Date 2021-03-19 Time 13:17 Sent To  
Notes
2021-03-19 13:19:45IT APPEARS THAT NONE OF THE EXISTING COMMENTS HAVE BEEN
 ADDRESSED ON THIS RESUBMITTAL.
  
 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE
 BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS
 SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1,
 G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY
 SHOW THE DISTANCE AS 39 FEET.
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW
 THIS SYSTEM AS A 2 PSI SYSTEM.
 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION.
 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET
 OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2
 PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING
 REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC.
 107.2.1.
 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS
 LINE TO THE GENERATOR. CLARIFY.
 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR
 IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE
 REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER
 FFBC-FUEL GAS SEC.410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-01-19 Time   Rev Time 0.00
Received By tklarge Date 2021-01-19 Time 06:29 Sent To  
Notes
2021-01-19 06:50:231) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 2) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) LIST THE BTU LOAD OF THE GENERATOR AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER) TO THE MOST REMOTE OUTLET/ REGULATOR IN THE
 BUILDING AND / OR SYSTEM PER THE 2017 FBC-FUEL GAS
 SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. SEC. G 2413.4.1,
 G2413.4.2. NOTE: EXISTING PLANS ON FILE WITH THE CITY
 SHOW THE DISTANCE AS 39 FEET.
 5) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. NOTE: CITY RECORDS SHOW
 THIS SYSTEM AS A 2 PSI SYSTEM.
 6) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
 7) THE PLANS INDICATE AN EXISTING GAS METER AND CITY
 RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS ADDRESS.
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION.
 8) ) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET
 OF THE 2-PSI METER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SHOW THE PIPE SIZE TO THE THE EXISTING GAS LOAD. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) EXISTING PLANS ON FILE SHOW THE GAS SYSTEM AS A 2
 PSI SYSTEM. SHOW THE LOCATION OF ALL EXISTING
 REGULATORS ON THE GAS PLAN.WPB AMEND. TO FBC SEC.
 107.2.1.
 11) THE GAS DRAWING SHOWS TWO SHUTOFF VALVES IN THE GAS
 LINE TO THE GENERATOR. CLARIFY.
 12) SINCE THIS IS AN EXISTING 2 PSI SYSTEM, A REGULATOR
 IS REQUIRED AT THE GENERATOR. SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALATION INTRUCTIONS FOR THE
 REGULATOR. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED OR OUTDOOR INSTALLATION PER
 FFBC-FUEL GAS SEC.410.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-15 Cont ID  
Sent By lcrespo Date 2021-04-15 Time 11:27 Rev Time 0.00
Received By cthroop Date 2021-03-24 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-19 Cont ID  
Sent By lmarchan Date 2021-03-19 Time 13:27 Rev Time 0.00
Received By lmarchan Date 2021-02-23 Time 06:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-19 Cont ID  
Sent By lmarchan Date 2021-01-19 Time 11:22 Rev Time 0.00
Received By lmarchan Date 2020-12-15 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2021-04-07 Cont ID  
Sent By lcrespo Date 2021-04-07 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-04-07 Time 15:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-03-19 Cont ID  
Sent By tklarge Date 2021-03-19 Time 13:20 Rev Time 0.00
Received By tklarge Date 2021-03-19 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-03-10 Cont ID  
Sent By cthroop Date 2021-03-10 Time 14:51 Rev Time 0.00
Received By cthroop Date 2021-03-10 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-01-19 Cont ID  
Sent By tklarge Date 2021-01-19 Time 06:28 Rev Time 0.00
Received By tklarge Date 2021-01-19 Time 05:33 Sent To  
Notes
2021-01-19 06:29:11THERE IS NO PLUMBING ASSOCIATED WITH THIS PERMIT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-04-12 Cont ID  
Sent By rmcdouga Date 2021-04-12 Time 16:39 Rev Time 0.00
Received By rmcdouga Date 2021-04-12 Time 16:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-04-05 Cont ID  
Sent By rmcdouga Date 2021-04-05 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2021-04-05 Time 09:27 Sent To  
Notes
2021-04-05 09:29:01THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By rmcdouga Date 2021-03-01 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2021-03-01 Time 09:52 Sent To  
Notes
2021-03-01 09:59:33THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  
 NO SIGNATURE OF CONTRACTOR ON ELECTRIC RISER DIAGRAHM.
 CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-23 Cont ID  
Sent By rmcdouga Date 2020-12-23 Time 09:31 Rev Time 0.00
Received By rmcdouga Date 2020-12-23 Time 09:31 Sent To  
Notes
2020-12-23 09:37:35THE PREFAB GENERATOR PAD DRAWINGS DO NOT HAVE THE
 ENGINEER'S DIGITAL SIGNATURES. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
2020-12-17 14:49:28NO SIGNATURE OF CONTRACTOR ON ELECTRIC RISER DIAGRAHM.
 CT

Review Stop Z ZONING
Rev No 3 Status P Date 2021-04-14 Cont ID  
Sent By rthermid Date 2021-04-14 Time   Rev Time 0.00
Received By rthermid Date 2021-04-14 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By rthermid Date 2021-03-05 Time   Rev Time 0.00
Received By rthermid Date 2021-03-05 Time   Sent To I
Notes
2021-03-05 11:40:29ADDRESS PREVIOUS ZONING COMMENTS.
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By rthermid Date 2020-12-17 Time   Rev Time  
Received By rthermid Date 2020-12-17 Time   Sent To I
Notes
2020-12-17 09:25:03ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12/17/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE A SURVEY OF THE PROPERTY INDICATING
 THE SETBACKS OF THE PROPOSED GENERATOR TO ALL PROPERTY
 LINES. PER THE CITY ZONING CODE, MECHANICAL EQUIPMENT
 CANNOT ENCROACH MORE THAN 4 FEET INTOA REQUIRED
 SETBACK.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  