Plan Review Details - Permit 20120513
Plan Review Stops For Permit 20120513
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 5 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 15:02 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status F Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 11:32 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-07 11:32:16TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2022-10-11 Cont ID  
Sent By aoliver Date 2022-10-11 Time 07:38 Rev Time 0.00
Received By aoliver Date 2022-10-11 Time 07:38 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-04-26 Cont ID  
Sent By jwitmer Date 2021-04-26 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2021-04-26 Time 14:31 Sent To  
Notes
2021-04-26 15:00:112ND REQUEST, PLEASE BE AWARE THIS IS A FLORIDA STATE
 STATUTE. COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By jwitmer Date 2021-02-23 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 14:13 Sent To  
Notes
2021-02-23 14:55:44COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 15:17 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 13:39 Rev Time 0.00
Received By jwitmer Date 2023-02-07 Time 11:44 Sent To  
Notes
2023-02-07 13:39:09WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120513
 ADD: 1900 CONSULATE PL. SUITE: 705
 CONT: MOSS DELCO INC.
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. FEB. 07TH/ 2023
 ACTION: DENIED
  
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) COMPLIED, NEW VALUE OF $50,000.00
  
 2-4B) COMPLIED.
  
 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD.
 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS
 AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE
 FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
  
 5) 4TH REVIEW, SEMI- COMPLIED. SUBMITTED THIS REVIEW
 CYCLE HEATHER CHOICE FLOORING STC OF 67, 6 INCH
 CONCRETE SLAB WITH DROPPED CEILING, SUSPENDED GYPSUM
 BOARD CEILING W/ 3-1/2 INCHES OF BATT INSULATION, HCAU
 UNDERLAYMENT & LVT (LUXURY VINYL TILE). THE SPEC SHEET
 SUBMITTED PROVIDES SOUND RATINGS BUT NOT THE FLOOR
 ASSEMBLY.
  
 5A) 4TH REQUEST. NO REPORT THIS REVIEW. FBC-B 2020
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E-492.
  
 5B) 4TH REQUEST. NO TEST REPORTS TO DATE. FBC-B 2020
 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 5) 4TH REQUEST. SUBMITTED ONE PAGE OF A REPORT, PLEASE
 SUBMIT THE FULL REPORT. THE FINISH FLOOR MATERIAL IS
 VINYL SO TEST REPORTS SHOULD BE IN COMPLIANCE WITH
 FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By jwitmer Date 2022-09-19 Time 14:48 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-09-19 14:48:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120513
 ADD: 1900 CONSULATE PL. SUITE: 705
 CONT: MOSS DELCO INC.
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. SEPT. 19TH/ 2022
 ACTION: DENIED
  
  
 ***** NOTICE ONLY ***** 4X FEE / NOTICE!!!!! FLORIDA
 STATUTE 553.80(2)(B)
  
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS???
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW.
  
  
  
  
 1) 3RD REQUEST. SAME NOTES FROM DESIGN PROFESSIONAL
 FROM 4/12/2021. THE PLAN REVIEW RESPONSE COMMENTS STATE
 THAT THE VALUE OF THE WORK HAS BEEN REVISED TO MORE
 ACCURATELY REFLECT THE WORK ACCOMPLISHED. THE VALUE OF
 WORK HAS NOT CHANGED NOR DECLARED. IT APPEARS WHEN
 READING THE PLAN REVIEW RESPONSES THAT THIS WORK HAS
 ALREADY BEEN COMPLETED. PLEASE RESPOND HAS THIS WORK
 BEEN COMPLETED WITHOUT A PERMIT.
  
 1ST ROUND OF COMMENTS. THE DESCRIPTION OF WORK IS TO DO
 A REMODEL OF THE INTERIOR OF THE TENANT SPACE, KITCHEN
 CABINETS AND COUNTERTOP NEW SINK AND SUPPLY, 2 NEW
 VANITIES, TUB & SHOWER AND REPLACEMENT OF FLOORING WITH
 TILE WITH THE EXCEPTION OF THE FOYER, REMOVAL OF ALL
 DEBRIS AND COST OF DESIGN PROFESSIONAL AND THE
 CONTRACTOR OVERHEAD AND PROFIT. THE PERMIT VALUE
 DECLARED IS EXTREMELY LOW!!!
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING
 PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2-4B) COMPLIED.
  
 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD.
 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS
 AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE
 FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
  
 5) 3RD REQUEST. NO FLOORING INSULATION WAS SUBMITTED
 FOR THE 2ND OR 3RD REVIEW. THE RESPONSE STATES THE
 FLOOR SOUND INSULATION MATERIALS WERE INSTALLED AS PER
 THE BUILDING REQUIREMENTS FOR STANDARDS OF TILE FLOOR
 INSTALLATIONS. IF FIELD TESTING BY A CERTIFIED
 LABORATORY, PLEASE SUBMIT BOTH REQUIRED REPORTS FOR THE
 IIC AND STC REQUIREMENTS. COMMENT 5C THE FLAME SPREAD
 REPORT WILL ALSO NEED TO BE SATISFIED.
  
 1ST ROUND COMMENT. THE PLANS STATED REPLACE ALL
 FLOORING, EXCEPT ENTRY, WITH NEW FLOOR TILE. FLOOR
 INSULATION (FBC-B 2017) OR TILE, STONE, MARBLE, VINYL
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A)3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 5)3RD REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-26 Cont ID  
Sent By jwitmer Date 2021-04-26 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2021-04-26 Time 14:31 Sent To  
Notes
2021-04-26 14:57:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120513
 ADD: 1900 CONSULATE PL. SUITE: 705
 CONT: MOSS DELCO INC.
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. APRIL 26TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE PLAN REVIEW RESPONSE COMMENTS STATE
 THAT THE VALUE OF THE WORK HAS BEEN REVISED TO MORE
 ACCURATELY REFLECT THE WORK ACCOMPLISHED. THE VALUE OF
 WORK HAS NOT CHANGED NOR DECLARED. IT APPEARS WHEN
 READING THE PLAN REVIEW RESPONSES THAT THIS WORK HAS
 ALREADY BEEN COMPLETED. PLEASE RESPOND HAS THIS WORK
 BEEN COMPLETED WITHOUT A PERMIT.
  
 1ST ROUND OF COMMENTS. THE DESCRIPTION OF WORK IS TO DO
 A REMODEL OF THE INTERIOR OF THE TENANT SPACE, KITCHEN
 CABINETS AND COUNTERTOP NEW SINK AND SUPPLY, 2 NEW
 VANITIES, TUB & SHOWER AND REPLACEMENT OF FLOORING WITH
 TILE WITH THE EXCEPTION OF THE FOYER, REMOVAL OF ALL
 DEBRIS AND COST OF DESIGN PROFESSIONAL AND THE
 CONTRACTOR OVERHEAD AND PROFIT. THE PERMIT VALUE
 DECLARED IS EXTREMELY LOW!!!
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING
 PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2-4B) COMPLIED.
  
 4C) BUILDING PROVISO: TO BE DETERMINED IN THE FIELD.
 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS
 AND BATHTUBS WITH INSTALLED SHOWER HEADS SHALL BE
 FINISHED WITH A NONABSORBENT SURFACE TO A HEIGHT NOT
 LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
  
 5) 2ND REQUEST. NO FLOORING INSULATION WAS SUBMITTED
 FOR THE 2ND REVIEW. THE RESPONSE STATES THE FLOOR SOUND
 INSULATION MATERIALS WERE INSTALLED AS PER THE BUILDING
 REQUIREMENTS FOR STANDARDS OF TILE FLOOR INSTALLATIONS.
 IF FIELD TESTING BY A CERTIFIED LABORATORY, PLEASE
 SUBMIT BOTH REQUIRED REPORTS FOR THE IIC AND STC
 REQUIREMENTS. COMMENT 5C THE FLAME SPREAD REPORT WILL
 ALSO NEED TO BE SATISFIED.
  
 1ST ROUND COMMENT. THE PLANS STATED REPLACE ALL
 FLOORING, EXCEPT ENTRY, WITH NEW FLOOR TILE. FLOOR
 INSULATION (FBC-B 2017) OR TILE, STONE, MARBLE, VINYL
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-02-23 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 14:13 Sent To  
Notes
2021-02-23 14:54:41WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120513
 ADD: 1900 CONSULATE PL. SUITE: 705
 CONT: MOSS DELCO INC.
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 23RD/ 2021
 ACTION: DENIED
  
 1) THE DESCRIPTION OF WORK IS TO DO A REMODEL OF THE
 INTERIOR OF THE TENANT SPACE, KITCHEN CABINETS AND
 COUNTERTOP NEW SINK AND SUPPLY, 2 NEW VANITIES, TUB &
 SHOWER AND REPLACEMENT OF FLOORING WITH TILE WITH THE
 EXCEPTION OF THE FOYER, REMOVAL OF ALL DEBRIS AND COST
 OF DESIGN PROFESSIONAL AND THE CONTRACTOR OVERHEAD AND
 PROFIT. THE PERMIT VALUE DECLARED IS EXTREMELY LOW!!!
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 109.3 BUILDING
 PERMIT VALUATION. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL, OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE SUBMITTED FLOOR PLAN INDICATES A NEW SHOWER
 LOCATION IN THE MASTER BATH. THE PLANS ARE SILENT AS IF
 A NEW DRAIN WILL BE REQUIRED AND IF A NEW HOLE WILL
 NEED TO BE CORED THROUGH THE FLOOR. BEFORE THIS PROCESS
 WILL OCCUR THE FLOOR SLAB WILL NEED TO BE X-RAYED FOR
 POST TENSION CHORD LOCATIONS. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, TO SAFELY CORE DRILL THE FLOOR
 SYSTEM.
  
 3) THE PLANS ARE SILENT AS TO THE NEW THROUGH
 PENETRATION OF THE FLOOR SYSTEM AND THE REQUIRED
 THOROUGH PENETRATION FIRE STOP SYSTEM FOR THE FLOOR
 ASSEMBLY IN COMPLIANCE WITH THE 2017 FBC-B 714.4.1.2.
  
 4A) WITH THE NEW SHOWER LOCATION BEING ON A TENANT
 SEPARATION WALL PLEASE PROVIDE HOW THE 1 HOUR FIRE
 RATING WILL BE MAINTAINED IN ACCORDANCE WITH THE 2017
 FBC-B SECTION 708.3 FIRE RESISTANCE RATING 1 HOUR.
  
 4B) PLEASE ALSO CONSIDER COMPLIANCE WITH 2017 FBC-B
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR WALL
 TILE IN TUB AND SHOWER AREAS AND WALLS AND CEILING
 PANELS IN SHOWER AREAS SHALL BE OF MATERIALS LISTED IN
 TABLE 2509.2 AND INSTALLED IN ACCORDANCE WITH
 MANUFACTURER?S RECOMMENDATIONS. WATER RESISTANT GYPSUM
 BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER
 CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE
 WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S
 RECOMMENDATIONS.
  
 4C) 2017 FBC-B SHOWERS & TUBS 1210.3. SHOWER
 COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS
 SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A
 HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET.
  
  
 5) THE PLANS STATED REPLACE ALL FLOORING, EXCEPT ENTRY,
 WITH NEW FLOOR TILE. FLOOR INSULATION (FBC-B 2017). OR
 TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED
 TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-10-05 Cont ID  
Sent By mpeterso Date 2022-10-05 Time 13:22 Rev Time 0.00
Received By mpeterso Date 2022-10-05 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-04-30 Cont ID  
Sent By equinone Date 2021-04-30 Time 09:15 Rev Time 0.00
Received By equinone Date 2021-04-30 Time 09:15 Sent To  
Notes
2021-04-30 09:21:45CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
 .
 1) SCOPE OF WORK: CLARIFY WHAT LIGHTING CIRCUITS AND
 DEVICES ARE NEW OR EXISTING.
  
 2) PLEASE PROVIDE PANEL SCHEDULE SHOWING ALL NEW AND
 EXISTING CIRCUITS. SPECIFY IF PANEL IS NEW OR EXISTING.
 SPECIFY AIC RATING OF PANEL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-02-26 Cont ID  
Sent By equinone Date 2021-02-26 Time 14:48 Rev Time 0.00
Received By equinone Date 2021-02-26 Time 14:48 Sent To  
Notes
2021-02-26 15:02:49CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
 .
 1) SCOPE OF WORK IS NOT CLEAR. PLEASE INDICATE IF ALL
 LIGHTING AND RECEPTACLES SHOWN ARE NEW OR IF NOT PLEASE
 INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS NEW.
 FBC 107
 2) PLEASE PROVIDE PANEL SCHEDULE SHOWING ALL NEW AND
 EXISTING CIRCUITS.
 3) SMOKE DETECTOR REQUIRED IN MASTER BEDROOM (AND ALL
 BEDROOMS)
 4) PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR
 MS
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2023-04-03 Cont ID  
Sent By cwalker Date 2023-04-03 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-02-06 Cont ID  
Sent By cwalker Date 2023-02-06 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By pleduc Date 2022-09-19 Time   Rev Time 0.00
Received By pleduc Date 2022-09-19 Time 10:52 Sent To  
Notes
2022-09-19 10:56:20THE PREVIOUS COMNETS FROM FIRE WERE NOT ADDRESSED.
  
 PLEASE RESPOND DIRECTLY TO EACH COMMENT.
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN ATTACHED LETTER FROM A FIRE SPRINKLER
 CONTRACTOR, ACCURATE FIRE SPRINKLERS, STATING THAT FIRE
 SPRINKLER MODIFICATIONS HAVE BEEN COMPLETED.
  
 THERE ARE NO RECORDS OF A FIRE SPRINKLER PERMIT ON
 RECORD FOR THIS WORK.
  
 MY PREVIOUS COMMENTS, NOTED BELOW, CLEARLY STATES THAT
 ANY WORK OF THE FS SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 *******2) THERE ARE INDICATIONS OF WALL & CEILING
 REMOVAL & REPLACEMENT & MOST LIKLEY PAINTING.
  
 THE FIRE SPRINKLER HEAD COVERAGE WILL REQUIRE
 MODIFICATIONS BY A FIRE SPRINKLER CONTRACTOR.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.*******
  
  
  
 THIS WORK HAS BEEN DONE WITHOUT A REQUIRED PERMIT AND
 FIRE INSPECTIONS AND IS NOT ACCEPTABLE.
  
 THE CONTRACTOR SHALL SUBMIT A PERMIT IMMEDIATELY AND
 SCHEDULE THE REQUIRED FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-04-22 Cont ID  
Sent By pleduc Date 2021-04-22 Time   Rev Time 0.00
Received By pleduc Date 2021-04-22 Time 10:05 Sent To  
Notes
2021-04-22 10:18:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN ATTACHED LETTER FROM A FIRE SPRINKLER
 CONTRACTOR, ACCURATE FIRE SPRINKLERS, STATING THAT FIRE
 SPRINKLER MODIFICATIONS HAVE BEEN COMPLETED.
  
 THERE NO RECORDS OF A FIRE SPRINKLER PERMIT ON RECORD
 FOR THIS WORK.
  
 MY PREVIOUS COMMENTS, NOTED BELOW, CLEARLY STATES THAT
 ANY WORK OF THE FS SHALL BE DONE UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS.
  
  
 *******2) THERE ARE INDICATIONS OF WALL & CEILING
 REMOVAL & REPLACEMENT & MOST LIKLEY PAINTING.
  
 THE FIRE SPRINKLER HEAD COVERAGE WILL REQUIRE
 MODIFICATIONS BY A FIRE SPRINKLER CONTRACTOR.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.*******
  
  
  
 THIS WORK HAS BEEN DONE WITHOUT A REQUIRED PERMIT AND
 FIRE INSPECTIONS AND IS NOT ACCEPTABLE.
  
 THE CONTRACTOR SHALL SUBMIT A PERMIT IMMEDIATELY AND
 SCHEDULE THE REQUIRED FIRE INSPECTIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-02-23 Cont ID  
Sent By pleduc Date 2021-02-23 Time   Rev Time 0.00
Received By pleduc Date 2021-02-23 Time 14:25 Sent To  
Notes
2021-02-23 14:33:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK THAT MAY INVOLVE NEW
 FLOOR/TILE BUT NO SPECIFICATIONS SHEETS THAT INDICATE
 MEETING THE REQUIREMENTS PER NFPA FOR FALME SPREAD AND
 SMOKE GENERATION.
  
 PER NFPA 101, CH 32
  
 30.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR
 WALL AND
 CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE
 PERMITTED AS FOLLOWS:
 (1) EXIT ENCLOSURES ? CLASS A
 (2) LOBBIES AND CORRIDORS ? CLASS A OR CLASS B
 (3) OTHER SPACES ? CLASS A, CLASS B, OR CLASS C
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS
 CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS
 COMPLYING
 WITH 30.3.6 SHALL BE NOT LESS THAN CLASS II.
 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR
 10.2.7.2, AS APPLICABLE
  
  
 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS
 SHALL BE IN
 ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING
 ACTUAL
 INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING
 JURISDICTION IS
 PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY
 MATERIAL FOR WHICH
 CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE,
 UNLESS OTHERWISE
 PROVIDED IN 10.2.1.2 OR 10.2.1.4.
 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO
 MATERIALS HAVING
 A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT
 ARE APPLIED DIRECTLY
 TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE
 FOLLOWING
 CONDITIONS ARE MET:
 (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR
 LIMITED COMBUSTIBLE
 MATERIAL.
 (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF
 CLASS A INTERIOR
 WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH
 10.2.3,
 USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 2) THERE ARE INDICATIONS OF WALL & CEILING REMOVAL &
 REPLACEMENT & MOST LIKLEY PAINTING.
  
 THE FIRE SPRINKLER HEAD COVERAGE WILL REQUIRE
 MODIFICATIONS BY A FIRE SPRINKLER CONTRACTOR.
  
 ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS
 OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS.
  
 FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE
 PROTECTED FROM PAINTING OR DAMAGE.
  
 THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE
 COMPLIANCE.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2023-03-31 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2023-02-07 Time 13:41 Rev Time 0.00
Received By amcgrego Date 2023-02-03 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-11 Cont ID  
Sent By aoliver Date 2022-10-11 Time 07:38 Rev Time 0.00
Received By aoliver Date 2022-09-16 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-30 Cont ID  
Sent By equinone Date 2021-04-30 Time 09:21 Rev Time 0.00
Received By equinone Date 2021-04-21 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-03-27 Cont ID  
Sent By pvalenti Date 2021-03-27 Time 07:24 Rev Time 0.00
Received By pvalenti Date 2021-02-18 Time 10:13 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-02-23 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2021-02-23 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-03-03 Cont ID  
Sent By medwards Date 2021-03-03 Time 07:33 Rev Time 0.00
Received By medwards Date 2021-03-03 Time 07:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-09-19 Cont ID  
Sent By ccole Date 2022-09-19 Time 13:39 Rev Time 0.00
Received By ccole Date 2022-09-19 Time 12:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-04-28 Cont ID  
Sent By ccole Date 2021-04-28 Time 15:50 Rev Time 0.00
Received By ccole Date 2021-04-28 Time 15:15 Sent To  
Notes
2021-04-28 15:51:212ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20120513
 4/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS #2 & 3 PRINTED
 BELOW FROM THE 1ST REVIEW STILL EXIST- PLEASE COMPLY.
  
 2) PROVIDE SANITARY DRAINAGE AND WATER SUPPLY ISOMETRIC
 DRAWINGS FOR THE REMODELED KITCHEN AND MASTER BATH-
 SECTION 107.3.5.1.3 WPB. BASED ON THE EXISTING AND
 REMODELED MASTER BATH FLOOR PLAN DRAWINGS IT APPEARS
 NEW DRAIN AND VENT PIPES WILL HAVE TO BE INSTALLED FOR
 THE NEW DOUBLE BOWL VANITY SINK. PLEASE PROVIDE THE
 SANITARY DRAINAGE ISOMETRIC AS REQUESTED IN THE 1ST
 REVIEW.
  
 3) PROVIDE A MASTER BATH SHOWER PAN DETAIL- SECTION
 421.5.2 FBC P. PLEASE SHOW THE SLOPE OF THE LINER IN
 THE DETAIL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-03-08 Cont ID  
Sent By ccole Date 2021-03-08 Time 09:39 Rev Time 0.00
Received By ccole Date 2021-03-08 Time 09:07 Sent To  
Notes
2021-03-08 09:39:511ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120513
 3/8/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE PLUMBING SCOPE OF WORK NOTES ON THE PLAN-
 SECTION 107.2.1 WPB.
  
 2) PROVIDE SANITARY DRAINAGE AND WATER SUPPLY ISOMETRIC
 DRAWINGS FOR THE REMODELED KITCHEN AND MASTER BATH-
 SECTION 107.3.5.1.3 WPB.
  
 3) PROVIDE THE WIDTH DIMENSION OF THE MASTER BATH
 TOILET SPACE, AND THE WIDTH OF THE SHOWER- SECTIONS
 405.3.1 & 417.4 FBC P.
  
 3) PROVIDE A MASTER BATH SHOWER PAN DETAIL- SECTION
 421.5.2 FBC P.
  
 4) PROVIDE PLUMBING NOTES FOR THE NEW SHOWER VALVE:
 412.3 INDIVIDUAL SHOWER VALVES. INDIVIDUAL SHOWER AND
 TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120 DEGREES F, WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
  
 5) MP-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL FOR
 PIPES PENETRATING THE EXISTING SLAB- SECTIONS 315.1 FBC
 P, AND 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-04-03 Cont ID  
Sent By jwitmer Date 2023-04-03 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2023-04-03 Time 15:18 Sent To  
Notes
2023-04-03 15:19:49SAME PAPER PLAN FROM 8/1/22.APPROVED THROUGH INCOMING.
 JWITMER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-02-07 Cont ID  
Sent By jwitmer Date 2023-02-07 Time 13:50 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2023-02-07 13:51:13ARCHITECT OR INTERIOR DECORATOR, DIGITAL SIGNING &
 SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ???SECURE HASH STANDARD,??? MARCH
 2012, WHICH IS HEREBY ADOPTED AND INCORPORATED BY
 REFERENCE BY THE BOARD AND CAN BE OBTAINED FROM HTTP://
 WWW.FLRULES.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR
 THE INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS
 /FIPS/FIPS180-4/FIPS-180-4.PDF.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-10-07 Cont ID  
Sent By mpeterso Date 2022-10-07 Time 14:26 Rev Time 0.00
Received By mpeterso Date 2022-10-07 Time 14:26 Sent To  
Notes
2022-10-07 14:32:15SIGNATURE REVIEW FAILED
  
 IT APPEARS DRAWING IS A COPY OF A WET SIGNED AND SEALED
 DRAWING. PLEASE CORRECT AS OUTLINED BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
  
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-04-21 Cont ID  
Sent By medwards Date 2021-04-21 Time 09:28 Rev Time 0.00
Received By medwards Date 2021-04-21 Time 09:26 Sent To  
Notes
2021-04-21 09:29:06ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ROUTED TO
 STORAGE.ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-02-18 Cont ID  
Sent By medwards Date 2021-02-18 Time 13:53 Rev Time 0.00
Received By medwards Date 2021-02-18 Time 13:52 Sent To  
Notes
2021-02-18 13:54:22ORIGINAL SIGNED AND SEALED PAPER DRAWING ROUTED TO
 STORAGE.ME

Review Stop Z ZONING
Rev No 1 Status N Date 2021-03-26 Cont ID  
Sent By kalexand Date 2021-03-26 Time 16:18 Rev Time 0.00
Received By kalexand Date 2021-03-26 Time 16:17 Sent To I
Notes
***NONE***