Plan Review Stops For Permit 20120459 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2021-04-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-08 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-08 |
Time |
08:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2021-04-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-01 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-01 |
Time |
10:50 |
Sent To |
|
|
Notes |
2021-04-01 10:54:12 | PLAN | | REVIEW COMMENTS | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | [ PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED ] | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT | | WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY | | THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE | | ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA | | NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES | | THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS | | PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE | | SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING | | PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A | | FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH | | AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2 | | | | 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE | | PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING | | THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL | | BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS | | MUST BE GREATER THAN THE COMPONENT AND CLADDING | | PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1 | | | | 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT | | SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE | | WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC | | CHAPTER 16 | | | | 4) NEW COMMENT. SUBMIT A RESPONSE LETTER STATING HOW | | EACH REVIEW COMMENT HAS BEEN ADDRESSED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-02-17 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-02-17 |
Time |
12:03 |
Sent To |
|
|
Notes |
2021-02-17 11:45:39 | PLAN | | REVIEW COMMENTS | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT | | WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY | | THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE | | ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA | | NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES | | THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS | | PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE | | SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING | | PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A | | FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH | | AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2 | | | | 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE | | PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING | | THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL | | BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS | | MUST BE GREATER THAN THE COMPONENT AND CLADDING | | PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1 | | | | 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT | | SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE | | WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC | | CHAPTER 16 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-12-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-18 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-18 |
Time |
14:07 |
Sent To |
|
|
Notes |
2020-12-18 14:30:22 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THIS PROJECT IS LOCATED IN A HIGH RISE BUILDING. | | PLEASE SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & | | CLADDING PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM | | A FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH | | AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2 | | | | 2) CIRCLE OR HI-LIGHT THE ITEMS IN THE PRODUCT APPROVAL | | THAT APPLY TO THIS PROJECT, INCLUDING THE DESIGN | | PRESSURES FOR THE SPECIFIC DOORS THAT WILL BE | | INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS MUST | | BE GREATER THAN THE COMPONENT AND CLADDING PRESSURES | | DETERMINED BY THE ENGINEER. FBC 107.2.1 | | | | 3) SPECIFY THE HEIGHT OF THE BUILDING AND THE WALL ZONE | | THAT EACH OF THE DOORS IS LOCATED IN. FBC CHAPTER 16 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-04-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-08 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-04-06 |
Time |
09:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-04-01 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-04-01 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-03-22 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-02-17 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-02-10 |
Time |
11:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-12-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-18 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-15 |
Time |
07:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-02-17 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2021-02-17 |
Time |
12:04 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2021-02-17 |
Time |
12:03 |
Sent To |
|
|
Notes |
2021-02-17 12:05:08 | ANY NEW SUBMITTALS FROM THE ENGINEER WILL NEED TO BE | | REVIEWED FOR SIGNATURES. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2020-12-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2020-12-18 |
Time |
14:34 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2020-12-18 |
Time |
14:07 |
Sent To |
|
|
Notes |
2020-12-18 14:36:27 | THE REQUIRED WIND LOADS FOR THE OPENINGS ARE REQUIRED | | TO BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER WHEN | | THEY ARE ELECTRONICALLY SUBMITTED. ELECTRONICALLY | | SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S | | DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO | | SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. | | AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN | | SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING | | DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15 | | | | |
|
|