Plan Review Details - Permit 20120459
Plan Review Stops For Permit 20120459
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-04-08 Cont ID  
Sent By rmcdouga Date 2021-04-08 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2021-04-08 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-04-01 Cont ID  
Sent By rmcdouga Date 2021-04-01 Time 10:50 Rev Time 0.00
Received By rmcdouga Date 2021-04-01 Time 10:50 Sent To  
Notes
2021-04-01 10:54:12PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 [ PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED ]
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT
 WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY
 THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE
 ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA
 NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES
 THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS
 PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE
 SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING
 PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A
 FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH
 AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2
  
 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE
 PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING
 THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL
 BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS
 MUST BE GREATER THAN THE COMPONENT AND CLADDING
 PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1
  
 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT
 SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE
 WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC
 CHAPTER 16
  
 4) NEW COMMENT. SUBMIT A RESPONSE LETTER STATING HOW
 EACH REVIEW COMMENT HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 12:03 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 12:03 Sent To  
Notes
2021-02-17 11:45:39PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. [ SUBMIT THE CALCULATIONS/DATA THAT
 WERE USED TO DETERMINE THE DESIGN PRESSURES. SPECIFY
 THE WALL ZONES THAT THE OPENINGS ARE LOCATED IN. THE
 ENGINEER'S LETTER REFERS TO A TRIPLE WINDOW AND NOA
 NO.20-0722.09. THE PERMIT APPLICATION ONLY INDICATES
 THAT (2) SGDS ARE BEING REPLACED. PLEASE CLARIFY.]THIS
 PROJECT IS LOCATED IN A HIGH RISE BUILDING. PLEASE
 SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT & CLADDING
 PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM A
 FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH
 AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2
  
 2) NOT RESOLVED. CIRCLE OR HI-LIGHT THE ITEMS IN THE
 PRODUCT APPROVAL THAT APPLY TO THIS PROJECT, INCLUDING
 THE DESIGN PRESSURES FOR THE SPECIFIC DOORS THAT WILL
 BE INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS
 MUST BE GREATER THAN THE COMPONENT AND CLADDING
 PRESSURES DETERMINED BY THE ENGINEER. FBC 107.2.1
  
 3) PARTIALLY RESOLVED. [ THE WALL ZONES WERE NOT
 SPECIFIED.] SPECIFY THE HEIGHT OF THE BUILDING AND THE
 WALL ZONE THAT EACH OF THE DOORS IS LOCATED IN. FBC
 CHAPTER 16

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By rmcdouga Date 2020-12-18 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2020-12-18 Time 14:07 Sent To  
Notes
2020-12-18 14:30:22PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS LOCATED IN A HIGH RISE BUILDING.
 PLEASE SUBMIT DIGITALLY SIGNED AND SEALED COMPONENT &
 CLADDING PRESSURES FOR THE TWO SLIDING GLASS DOORS FROM
 A FLORIDA LICENSED ENGINEER. THE WIND SPEED IS 170 MPH
 AND THE EXPOSURE CATEGORY IS D. FBC 107.2.1.2
  
 2) CIRCLE OR HI-LIGHT THE ITEMS IN THE PRODUCT APPROVAL
 THAT APPLY TO THIS PROJECT, INCLUDING THE DESIGN
 PRESSURES FOR THE SPECIFIC DOORS THAT WILL BE
 INSTALLED. NOT: THE DESIGN PRESSURES FOR THE DOORS MUST
 BE GREATER THAN THE COMPONENT AND CLADDING PRESSURES
 DETERMINED BY THE ENGINEER. FBC 107.2.1
  
 3) SPECIFY THE HEIGHT OF THE BUILDING AND THE WALL ZONE
 THAT EACH OF THE DOORS IS LOCATED IN. FBC CHAPTER 16

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-04-08 Cont ID  
Sent By rmcdouga Date 2021-04-08 Time 08:14 Rev Time 0.00
Received By rmcdouga Date 2021-04-06 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-01 Cont ID  
Sent By rmcdouga Date 2021-04-01 Time 10:54 Rev Time 0.00
Received By rmcdouga Date 2021-03-22 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 12:05 Rev Time 0.00
Received By rmcdouga Date 2021-02-10 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-18 Cont ID  
Sent By rmcdouga Date 2020-12-18 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2020-12-15 Time 07:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 12:04 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 12:03 Sent To  
Notes
2021-02-17 12:05:08ANY NEW SUBMITTALS FROM THE ENGINEER WILL NEED TO BE
 REVIEWED FOR SIGNATURES.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-18 Cont ID  
Sent By rmcdouga Date 2020-12-18 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2020-12-18 Time 14:07 Sent To  
Notes
2020-12-18 14:36:27THE REQUIRED WIND LOADS FOR THE OPENINGS ARE REQUIRED
 TO BE DIGITALLY SIGNED AND SEALED BY THE ENGINEER WHEN
 THEY ARE ELECTRONICALLY SUBMITTED. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ENGINEER'S
 DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO
 SUBMIT THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS.
 AFTER THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN
 SUBMIT THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 471 & 61G15
  
  