Plan Review Details - Permit 20120440
Plan Review Stops For Permit 20120440
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-01-12 Cont ID  
Sent By cpuell Date 2021-01-12 Time 16:36 Rev Time 0.00
Received By cpuell Date 2021-01-12 Time 16:36 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By cpuell Date 2020-12-09 Time 17:07 Rev Time 0.00
Received By cpuell Date 2020-12-09 Time 17:07 Sent To  
Notes
2020-12-09 17:08:51IS THIS ON THE GROUND FLOOR? PLEASE CONTACT
 [email protected] TO DISCUSS ADDRESSING.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By shill Date 2021-02-17 Time 17:16 Rev Time 0.00
Received By shill Date 2021-02-17 Time 14:48 Sent To  
Notes
2021-02-17 17:18:48REDLINED -
 SHAFTS ARE PRESSURIZED
 DOOR (1403) TO COMPLY WITH FBC ACCESSIBILITY 404.2.4,
 MINIMUM 18" CLEARANCE REQUIRED PULL SIDE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 09:02 Sent To  
Notes
2021-01-07 10:53:57INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWINGS SHOW CORRIDOR WALLS BETWEEN ELEVATOR AND
 OFFICES AS NON FIRE RATED. PLEASE SHOW HOW THE EXISTING
 ELEVATOR HOISTWAY IS PROTECTED PER FBC 3006.3
 2) PLEASE SHOW THE REQUIRED MANEUVERING CLEARANCE AT
 DOOR (1403) FROM INSIDE THE CONFERENCE ROOM TO COMPLY
 WITH FBC ACCESSIBILITY 404.2.4
 3) PLEASE SHOW THE REQUIRED FLOOR SPACE FOR ALL
 ACCESSIBLE ELEMENTS SUCH AS SINK, MICROWAVE,
 REFRIGERATOR ETC. PER FBC 305

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-13 Cont ID  
Sent By equinone Date 2021-01-13 Time 15:31 Rev Time 0.00
Received By equinone Date 2021-01-13 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By pleduc Date 2020-12-11 Time   Rev Time 0.00
Received By pleduc Date 2020-12-11 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-02-18 Time   Rev Time 0.00
Received By lmarchan Date 2021-01-29 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-13 Cont ID  
Sent By equinone Date 2021-01-13 Time 15:31 Rev Time 0.00
Received By equinone Date 2020-12-09 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 06:24 Rev Time 0.00
Received By medwards Date 2021-02-17 Time 06:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-23 Cont ID  
Sent By medwards Date 2020-12-23 Time 07:27 Rev Time 0.00
Received By medwards Date 2020-12-22 Time 17:26 Sent To  
Notes
2020-12-23 07:27:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20120440
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ALS.1.1 INDICATES 2 CONFERENCE ROOMS, THE
 VENTILATION DESIGN ON SHEET M2.0.0 DOES NOT SHOW THESE
 ROOMS. PLEASE SHOW THE VENTILATION CALCULATIONS FOR
 THIS TENANT SPACE BASED ON USE OF SPACE AND TABLE
 403.3.1.1. FBC M
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-02-18 Cont ID  
Sent By ccole Date 2021-02-18 Time 16:48 Rev Time 0.00
Received By ccole Date 2021-02-18 Time 16:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By ccole Date 2021-01-06 Time 13:51 Rev Time 0.00
Received By ccole Date 2021-01-06 Time 11:24 Sent To  
Notes
2021-01-06 13:51:541ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120440
 1/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P0.0.0: PLEASE PROVIDE PIPE MATERIAL SPECIFICATIONS
 FOR SANITARY DRAINS AND VENTS, WATER DISTRIBUTION AND
 SUPPLY LINES, CONDENSATE DISPOSAL- SECTION 303.2 FBC P.
 BASED ON MECHANICAL PLAN NOTES IT APPEARS PIPING MAY BE
 RUNNING THROUGH PLENUM RATED SPACES.
  
 2) P0.0.0: IT APPEARS A PUMP WILL BE REQUIRED FOR THE
 NEW CONDENSATE PIPING. PLEASE SHOW THE LOCATION AND
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION
 314.2.1 FBC P. PLEASE NOTE CONDENSATE DRAINS SHALL BE
 TRAPPED AS REQUIRED BY THE EQUIPMENT OR APPLIANCE
 MANUFACTURER- 314.2.4.
  
 3) P0.0.0 & P1.1.2: PLEASE INCLUDE THE BACKFLOW
 PREVENTERS IN THE FIXTURE SCHEDULE- TABLE 608.1 FBC P.
  
 4) A1.1.1 & A3.0.1: SHOW THE CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR THE NEW KITCHEN SINK- SECTION 606.2
 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By ccole Date 2021-02-22 Time 16:48 Rev Time 0.00
Received By ccole Date 2021-02-18 Time 16:48 Sent To  
Notes
2021-02-18 16:57:43 
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-12 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 10:00 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 10:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-12-29 Cont ID  
Sent By aaponte Date 2020-12-29 Time 10:53 Rev Time 0.00
Received By aaponte Date 2020-12-29 Time 10:53 Sent To  
Notes
***NONE***