Plan Review Details - Permit 20120439
Plan Review Stops For Permit 20120439
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 12:54 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By rmcphers Date 2021-04-01 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-04-01 Time 13:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-04 Cont ID  
Sent By mcphers Date 2021-03-04 Time 09:29 Rev Time 0.00
Received By rmcphers Date 2021-03-04 Time 09:29 Sent To  
Notes
2021-03-04 09:36:09INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) NEW DRAWING A4.21 SHOWS TOILET PAPER DISPENSER
 DISTANCE FROM TOILET INCORRECTLY - SHOULD BE 7" TO 9"
 TO THE CENTER LINE OF THE DISPENSER FBC 604.7 (DRAWING
 A0.04 NEEDS TO BE CORRECTED ALSO).
 2) NEW DRAWING A4.21 PLEASE SHOW THE REQUIRED 18" (DOOR
 MANEUVERING CLEARANCE) BESIDE THE DOOR TO ENTER THE
 ACCESSIBLE MEN'S ROOM TOILET COMPARTMENT FBC 404.2.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 12:53 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 11:03 Sent To  
Notes
2021-01-07 12:53:26INTERIOR OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A STATEMENT ON THE DRAWINGS THAT THE
 CREATED "AREA NOT IN CONTRACT" WILL SUBMIT FOR A
 SEPARATE PERMIT FOR THE BUILDOUT. THE "AREA NOT IN
 CONTRACT" DOES NOT HAVE 2 MEANS OF EGRESS PER FBC
 1006.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-01-08 Cont ID  
Sent By jleahy Date 2021-01-08 Time 16:00 Rev Time 0.00
Received By jleahy Date 2021-01-08 Time 13:03 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-01-08 Cont ID  
Sent By jleahy Date 2021-01-08 Time 16:01 Rev Time 0.00
Received By jleahy Date 2021-01-08 Time 16:01 Sent To  
Notes
2021-01-08 16:01:46VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-14 Cont ID  
Sent By pleduc Date 2020-12-14 Time   Rev Time 0.00
Received By pleduc Date 2020-12-14 Time 12:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-01 Cont ID  
Sent By rmcphers Date 2021-04-01 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-03-11 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-04 Cont ID  
Sent By rmcphers Date 2021-03-04 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 20:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-08 Cont ID  
Sent By jleahy Date 2021-01-08 Time 16:01 Rev Time 0.00
Received By jleahy Date 2020-12-09 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By medwards Date 2021-02-22 Time 08:07 Rev Time 0.00
Received By medwards Date 2021-02-22 Time 08:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-19 Cont ID  
Sent By medwards Date 2020-12-19 Time 09:41 Rev Time 0.00
Received By medwards Date 2020-12-19 Time 09:41 Sent To  
Notes
2020-12-19 09:41:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20120439
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: PLEASE SHOW DAMPERS AT RATED WALLS
 PENETRATED BY DUCTWORK TO CORRIDOR FROM VAV-4 AND ALSO
 SHOW DAMPERS FOR EXISTING DUCTWORK AND TRANSFER
 OPENINGS FOR RETURN PATH PENETRATING ALL RATED WALLS.
 FBC M 607
  
 2) PLEASE SHOW THE CORRECT OUTDOOR AIR FOR THIS TENANT
 SPACE.
  
 5/1000 SQ. FT.- 7625/1000 = 7.625; 7.625 X 5 =38.125 X5
 = 190.625 + 7625 X .06 = 457.5; 38.125 + 457.50 = 496
 CFM OF OUTDOOR AIR. FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 08:09 Rev Time 0.00
Received By ccole Date 2021-03-26 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-02-23 Cont ID  
Sent By ccole Date 2021-02-23 Time 13:31 Rev Time 0.00
Received By ccole Date 2021-02-23 Time 12:27 Sent To  
Notes
2021-02-23 13:31:282ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20120439
 2/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.11 & A1.12, A4.21: IT APPEARS THAT THE
 CLOSET DOOR IN THE MEN'S BATHROOM IS SWINGING INTO THE
 CLEAR FLOOR SPACE FOR THE ACCESSIBLE URINAL- SECTION
 603.2.3 FBC ACC.
  
 2) A0.04: THE CENTERLINES OF THE TOILET PAPER
 DISPENSERS SHALL BE LOCATED 7-9 INCHES MEASURED FROM
 THE FRONTS OF THE WATER CLOSETS- SECTION 604.7. PLEASE
 CORRECT THE DETAIL.
  
 3) P0.1: THE SHUTOFF VALVES TO THE TANKLESS WATER
 HEATERS SHALL BE A FULL-OPEN TYPE VALVE, NOT AN ANGLE
 STOP- SECTION 606.1(8) FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-01-06 Cont ID  
Sent By ccole Date 2021-01-06 Time 10:47 Rev Time 0.00
Received By ccole Date 2021-01-06 Time 08:55 Sent To  
Notes
2021-01-06 11:03:241ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20120439
 1/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A1.01: BASED ON THE CONSTRUCTION PLANS, PLEASE
 MODIFY NOTE #8 TO INCLUDE DEMOLITION OF THE TOILET
 COMPARTMENTS, GRAB BARS, ACCESSORIES ETC.- SECTION
 107.2.1 WPB.
  
 2) SHEETS A1.11 & A1.12, A4.21: PROVIDE ACCESSIBLE AND
 STANDARD COMPARTMENT DIMENSIONS AND DETAILS- SECTIONS-
 604.8.1- 604.8.3 FBC ACC, AND SECTION 405.3.1 FBC P.
  
 A) ADVISORY 604.8.1.6 LAVATORY AND 604.8.1.7 FBC ACC-
 WATER CLOSET. FLORIDA LAW, SECTION 553.504(5), F.S.,
 STIPULATES THAT "...REQUIRED BATHING ROOMS AND TOILET
 ROOMS IN NEW CONSTRUCTION SHALL BE DESIGNED AND
 CONSTRUCTED..." WITH AN ACCESSIBLE LAVATORY IN THE
 WHEELCHAIR ACCESSIBLE COMPARTMENT AND THE WATER CLOSET
 LOCATED IN A CORNER DIAGONAL TO THE DOOR. THE ADA
 STANDARDS FOR ACCESSIBLE DESIGN AND THEREFORE THIS CODE
 REQUIRE WHEELCHAIR ACCESSIBLE COMPARTMENTS IN NEW
 CONSTRUCTION AND IN ALTERATIONS OF EXISTING BUILDINGS
 TO HAVE SELF CLOSING DOORS. WHILE THE FLORIDA LAVATORY
 REQUIREMENT AND WATER CLOSET PLACEMENT APPLY ONLY TO
 NEW CONSTRUCTION, THEY ARE DESIRABLE FOR ALL WHEELCHAIR
 ACCESSIBLE COMPARTMENTS AND SHOULD BE CONSIDERED WHERE
 FEASIBLE.
  
 3) REQUIRED DETAILS- FBC-17 ACCESSIBILITY.
  
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS
 IN THE ACCESSIBLE COMPARTMENTS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE ACCESSIBLE
 LAVATORIES- SECTION 606.2.
 C) CENTERLINE OF THE ACCESSIBLE WATER CLOSETS FROM THE
 SIDE WALLS- SECTION 604.2.
 D) HEIGHTS OF THE ACCESSIBLE WATER CLOSET SEATS FROM
 THE FINISHED FLOORS- SECTION 604.4.
 E) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE WATER CLOSETS- SECTION 604.5 &
 609.4
 G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 H) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE ACCESSIBLE WATER CLOSETS-
 SECTION 604.7.
 I) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- SECTION 606.2.
  
 4) SHEETS A1.01, P0.1, P2.1: INSTALLATION OF THE NEW
 CAFE SINK DRAIN MAY REQUIRE THE CONCRETE FLOOR SLAB TO
 BE X-RAYED TO IN ORDER TO LOCATE REINFORCING STEEL OR
 POST STRESSED FLOOR TENDONS. PLEASE PLACE A NOTE ON THE
 PLANS TO VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1
 WPB.
  
 5) P0.1 & P2.1: THE ANNUAL SPACE AROUND THE NEW DRAIN
 PIPE PENETRATION THROUGH THE CONCRETE SLAB MUST BE
 SEALED. PROVIDE A UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAIL ON THE PLAN- SECTION 714.4.1.2 FBC B.
 PLEASE PROVIDE SANITARY DRAIN PIPE MATERIAL
 SPECIFICATIONS- SECTION 303.2 FBC P. BASED ON
 MECHANICAL PLAN NOTES IT APPEARS THE DRAIN PIPING MAY
 BE RUNNING THROUGH PLENUM RATED SPACES WHERE PVC IOS
 PROHIBITED.
  
 6) P0.1 & P2.1: DETAILS ON SHEET P0.1 INDICATE NEW
 WATER SUPPLY AND WATER HEATER FOR THE HANDICAP
 LAVATORY, HOWEVER THE DETAIL ON P2.1 INDICATES NEW
 WATER LINE AND HEATER AT THE CAFE SINK (NOTE 2). PLEASE
 CLARIFY- SECTION 107.2.1 WPB.
  
 7) P0.1 & P2.1: REFER TO TABLE C404.5.1 FBC EC AND
 VERIFY COMPLIANCE FOR PIPING VOLUME AND MAXIMUM PIPING
 LENGTH FOR HOT WATER PIPING SUPPLYING THE PUBLIC
 LAVATORY FAUCETS FROM THE HEATED WATER SOURCE. PLEASE
 NOTE FOR EXAMPLE, THE MAXIMUM LENGTH FOR A 1/2 IN. PIPE
 IS 2 FT AND MAX VOLUME PER SECTION C404.5.2 IS 2
 OUNCES. IT IS ALSO IMPORTMANT TO NOTE THAT
 RECIRCULATING HOT WATER SOURCES SYSTEMS ARE CONSIDERED
 SOURCES OF HEATED WATER.
  
 8) P0.1 & P2.1: PROVIDE A WATER HAMMER ARRESTOR AND
 BACKFLOW PREVENTER FOR THE WATER SUPPLY LINE TO THE ICE
 MAKER- SECTIONS 604.9 & 608.3 FBC P.
  
 9) P2.1: PROVIDE THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSION FOR THE ACCESSIBLE CAFE SINK- SECTION 606.2
 FBC P.
  
 10) P0.1 & P2.1: IT APPEARS A PUMP WILL BE REQUIRED FOR
 THE NEW CONDENSATE PIPING. PLEASE SHOW THE LOCATION AND
 PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION
 314.2.1 FBC P. INDICATE THE TYPE OF CONDENSATE PIPING
 TO BE INSTALLED- 314.2.2. PLEASE NOTE CONDENSATE DRAINS
 SHALL BE TRAPPED AS REQUIRED BY THE EQUIPMENT OR
 APPLIANCE MANUFACTURER- 314.2.4.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-04-01 Cont ID  
Sent By rmcphers Date 2021-04-01 Time 13:33 Rev Time 0.00
Received By rmcphers Date 2021-04-01 Time 13:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-04 Cont ID  
Sent By rmcphers Date 2021-03-04 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2021-03-04 Time 09:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-01-07 Cont ID  
Sent By rmcphers Date 2021-01-07 Time 12:54 Rev Time 0.00
Received By rmcphers Date 2021-01-07 Time 12:54 Sent To  
Notes
***NONE***