Plan Review Details - Permit 20120394
Plan Review Stops For Permit 20120394
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-04-13 Cont ID  
Sent By rmcphers Date 2021-04-13 Time 10:44 Rev Time 0.00
Received By rmcphers Date 2021-04-13 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 09:58 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 09:57 Sent To  
Notes
2021-03-01 09:58:39GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 4TH REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GENERATOR EXHAUST NEEDS TO BE 10' FROM OPENINGS PER
 FBC R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 13:24 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 13:24 Sent To  
Notes
2021-02-01 13:26:05GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 3RD REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GENERATOR EXHAUST NEEDS TO BE 10' FROM OPENINGS PER
 FBC R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-31 Cont ID  
Sent By rmcphers Date 2020-12-31 Time 08:15 Rev Time 0.00
Received By rmcphers Date 2020-12-31 Time 08:15 Sent To  
Notes
2020-12-31 08:15:50GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GENERATOR EXHAUST NEEDS TO BE 10' FROM OPENINGS PER
 FBC R303.5.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-21 Cont ID  
Sent By rmcphers Date 2020-12-21 Time 11:32 Rev Time 0.00
Received By rmcphers Date 2020-12-21 Time 11:32 Sent To  
Notes
2020-12-21 11:40:47GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) GENERATOR EXHAUST NEES TO BE 10' FROM OPENINGS PER
 FBC R303.5.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-09 Cont ID  
Sent By cthroop Date 2020-12-09 Time 15:50 Rev Time 0.00
Received By cthroop Date 2020-12-09 Time 15:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-04-22 Cont ID  
Sent By rmcphers Date 2021-04-22 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2021-04-07 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 10:01 Rev Time 0.00
Received By rmcphers Date 2021-02-07 Time 23:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-01-19 Time 22:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-06 Cont ID  
Sent By lmarchan Date 2021-01-06 Time 15:42 Rev Time 0.00
Received By lmarchan Date 2020-12-22 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-21 Cont ID  
Sent By rmcphers Date 2020-12-21 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2020-12-08 Time 16:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-03-01 Cont ID  
Sent By rmcphers Date 2021-03-01 Time 10:00 Rev Time 0.00
Received By rmcphers Date 2021-03-01 Time 10:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-02-01 Cont ID  
Sent By rmcphers Date 2021-02-01 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2021-02-01 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-31 Cont ID  
Sent By rmcphers Date 2020-12-31 Time 08:16 Rev Time 0.00
Received By rmcphers Date 2020-12-31 Time 08:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-21 Cont ID  
Sent By rmcphers Date 2020-12-21 Time 11:35 Rev Time 0.00
Received By rmcphers Date 2020-12-21 Time 11:35 Sent To  
Notes
2020-12-09 15:50:51VERIFIED CONTRACTORS SIGNATURE ON LOAD CALCS AND
 ELECTRIC RISER. CT

Review Stop Z ZONING
Rev No 4 Status P Date 2021-04-21 Cont ID  
Sent By rthermid Date 2021-04-21 Time   Rev Time 0.00
Received By rthermid Date 2021-04-21 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-03-12 Cont ID  
Sent By rthermid Date 2021-03-12 Time   Rev Time 0.00
Received By rthermid Date 2021-03-12 Time   Sent To I
Notes
2021-03-12 08:44:10ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 3/12/2021
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE ADDRESS BUILDING/STRUCTURAL COMMENTS. PER
 THE FLORIDA BUILDING CODE, MECHANICAL EQUIPMENT EXHAUST
 MUST BE 10 FEET FROM ANY DOOR/WINDOW OPENINGS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-01-06 Cont ID  
Sent By rthermid Date 2021-01-06 Time   Rev Time 0.00
Received By rthermid Date 2021-01-06 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By rthermid Date 2020-12-16 Time   Rev Time  
Received By   Date 2020-12-16 Time   Sent To I
Notes
2020-12-16 08:49:24ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 12/16/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PLEASE PROVIDE THE SETBACKS OF THE PROPOSED
 GENERATOR TO THE PROPERTY LINES ON THE SURVEY.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN
 INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
  
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved