Plan Review Details - Permit 20120379
Plan Review Stops For Permit 20120379
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-05-17 Cont ID  
Sent By rmcphers Date 2021-05-17 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2021-05-17 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-31 Cont ID  
Sent By rmcphers Date 2021-03-31 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2021-03-31 Time 08:43 Sent To  
Notes
2021-03-31 08:44:22POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLANS NEED TO SHOW WHAT THE REQUIRED POOL BARRIER
 (FBC R4501.17) WILL BE AND LOCATION OF THE BARRIER FBC
 107.3.5.4
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-31 Cont ID  
Sent By lcrespo Date 2020-12-31 Time 13:30 Rev Time 0.00
Received By rmcphers Date 2020-12-31 Time 13:20 Sent To  
Notes
2020-12-31 13:25:57POOL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLANS NEED TO SHOW WHAT THE REQUIRED POOL BARRIER
 (FBC R4501.17) WILL BE AND LOCATION OF THE BARRIER FBC
 107.3.5.4
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-20 Cont ID  
Sent By jleahy Date 2021-05-20 Time 15:58 Rev Time 0.00
Received By jleahy Date 2021-05-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-26 Cont ID  
Sent By jleahy Date 2021-03-26 Time 12:52 Rev Time 0.00
Received By jleahy Date 2021-03-26 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By jleahy Date 2021-01-05 Time 15:02 Rev Time 0.00
Received By jleahy Date 2021-01-05 Time 14:56 Sent To  
Notes
2021-01-05 15:03:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN WIRE SIZES BREAKER SIZES PANEL SIZE
 ECT, ECT ARE REQUIRED

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-07 Cont ID  
Sent By lmarchan Date 2021-06-07 Time 15:30 Rev Time 0.00
Received By lmarchan Date 2021-05-11 Time 07:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-05 Cont ID  
Sent By cthroop Date 2021-05-05 Time 09:07 Rev Time 0.00
Received By cthroop Date 2021-03-17 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-29 Cont ID  
Sent By jleahy Date 2021-01-29 Time 15:03 Rev Time 0.00
Received By jleahy Date 2020-12-18 Time 15:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-05-12 Cont ID  
Sent By lcrespo Date 2021-05-12 Time 09:59 Rev Time 0.00
Received By lcrespo Date 2021-05-12 Time 09:59 Sent To  
Notes
2021-05-12 09:59:3105/12/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-03-19 Cont ID  
Sent By lcrespo Date 2021-03-19 Time 08:59 Rev Time 0.00
Received By lcrespo Date 2021-03-19 Time 08:32 Sent To  
Notes
2021-03-19 09:01:0303/19/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-31 Cont ID  
Sent By lcrespo Date 2020-12-31 Time 09:20 Rev Time 0.00
Received By lcrespo Date 2020-12-31 Time 09:20 Sent To  
Notes
2020-12-31 09:20:5712/31/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SIGNED AND SEALED DRAWINGS OR
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ARCHITECT TO BE
 USED IN ELECTRONIC PLAN REVIEW - OR - IF YOUR THEY DO
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - PLEASE
 DROP OFF (CITY HALL DROPBOX) THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.
  
 2. PLANS CALL OUT FOR A TOTAL OF FOUR PAGES, AND ONLY
 TWO ARE UPLOAD. INFORMATION ABOUT THIS REVIEW MAY BE ON
 THOSE PAGES MISSING, SO PLEASE UPLOAD SO A REVIEW CAN
 BE COMPLETED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP. HAYWARD CALCULATOR CAN PROVIDE HELP
 WITH THE TDH.
  
 5. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 6. THE PUMP SPECIFICATIONS ARE BLURRY; PLEASE SUBMIT
 CLEAR AND LEGIBLE SPECIFICATIONS FOR THE PUMP CURVE PER
 THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SALT
 CHLORINATOR PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 8. SHOWS A VELOCITY CHART PER ANSI/APSP -7 SEC. 4.4.
 REFER TO THE 2013 EDITION OF APSP 7 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-17 Cont ID  
Sent By rmcphers Date 2021-05-17 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2021-05-17 Time 08:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-31 Cont ID  
Sent By rmcphers Date 2021-03-31 Time 08:51 Rev Time 0.00
Received By rmcphers Date 2021-03-31 Time 08:51 Sent To  
Notes
2021-03-31 08:54:05DRAWING LABELED "004 POOL BOND SCHEMATIC.PDF " IN
 PROJECTDOX =
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL
2021-03-26 12:53:24ELECTRICAL PAGE IS OK JLEAHY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-31 Cont ID  
Sent By rmcphers Date 2020-12-31 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2020-12-31 Time 13:26 Sent To  
Notes
2020-12-31 13:27:08SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE - YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop Z ZONING
Rev No 3 Status P Date 2021-06-07 Cont ID  
Sent By kalexand Date 2021-06-07 Time 09:17 Rev Time 0.00
Received By kalexand Date 2021-06-07 Time 09:17 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By kalexand Date 2021-05-04 Time 17:09 Rev Time 0.00
Received By kalexand Date 2021-05-04 Time 17:09 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-26 Cont ID  
Sent By kalexand Date 2021-01-26 Time 15:05 Rev Time 0.00
Received By kalexand Date 2021-01-26 Time 15:05 Sent To I
Notes
2021-01-26 15:07:12ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A CURRENT SURVEY, WHICH INCLUDES THE
 PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. PLEASE
 ILLUSTRATE THE FOLLOWING ON THE SURVEY:
 - LOCATION OF PROPOSED POOL
 - DISTANCE FROM POOL TO PROPERTY LINE
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved