Plan Review Details - Permit 20120372
Plan Review Stops For Permit 20120372
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-12-10 Cont ID  
Sent By jgomez Date 2020-12-10 Time 17:03 Rev Time 0.00
Received By jgomez Date 2020-12-10 Time 16:55 Sent To  
Notes
2020-12-10 16:56:25TALKED TO ERIC SALAMA (OWNER). USING APPROVED ASSEMBLY
 ON PAGE 26 OF 29. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-10 Cont ID  
Sent By jgomez Date 2020-12-10 Time 15:44 Rev Time 0.00
Received By jgomez Date 2020-12-10 Time 15:12 Sent To  
Notes
2020-12-10 15:52:58ROOFING REVISION SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
  
 1- PROVIDE NEW ROOFING PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEETT THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE LIMITATIONS ON
 PRODUCT APPROVAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOA 20-0902.19 SUBMITTED:
 SELECTED ASSEMBLY ON PAGE 23 OF 29 HAS A MAXIMUM DESIGN
 PRESSURE OF -52.5 PSF. THESE DESIGN PRESSURES ARE NOT
 ENOUGH TO MEE THE DESIGN PRESSURES AT THE PERIMETER AND
 CORNER AREAS. SEC. R301.2.1 FBC-RESIDENTIAL. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 16:24 Rev Time 0.00
Received By jgomez Date 2020-12-08 Time 15:44 Sent To  
Notes
2020-12-08 16:27:43ROOFING REVISION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- SELF-ADHERING MODIFIED BITUMEN ROOFING SYSTEM NOA
 18-1219.01 SUBMITTED IS FOR CEMENTITIOUS WOOD FIBER
 DECKS. THIS TYPE OF ROOD DECKING DOESN'T SEEM TO MATCH
 ROOF DECK OF THIS STRUCTURE. ACCORDING TO CITY RECORDS
 THIS IS A WOOD FRAMED RESIDENTIAL STRUCTURE. TYPICALLY,
 THIS TYPE OF FRAMED BUILDINGS DON'T HAVE CEMENTITIOUS
 WOOD FIBER DECKS. MOST LIKELY, THERE IS A WOOD DECK IN
 THIS STRUCTURE. REVISE ROOFING NOA OR PROVIDE PROOF
 THAT THIS IS A CEMENTITIOUS WOOD FIBER DECK.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE NEW ROOFING PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE LIMITATIONS ON
 PRODUCT APPROVAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-12-10 Cont ID  
Sent By jgomez Date 2020-12-10 Time 17:03 Rev Time 0.00
Received By jgomez Date 2020-12-10 Time 16:55 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-10 Cont ID  
Sent By jgomez Date 2020-12-10 Time 15:53 Rev Time 0.00
Received By jgomez Date 2020-12-10 Time 11:20 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 16:27 Rev Time 0.00
Received By jgomez Date 2020-12-07 Time 15:35 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-12-08 Cont ID  
Sent By jgomez Date 2020-12-08 Time 16:28 Rev Time 0.00
Received By jgomez Date 2020-12-08 Time 16:28 Sent To  
Notes
2020-12-08 16:28:42NOT REQUIRED, UNLESS RAS 117 CALCULATIONS ARE REQUIRED.
 JG.