Plan Review Details - Permit 20120328
Plan Review Stops For Permit 20120328
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-08 Cont ID  
Sent By cthroop Date 2021-01-08 Time 16:30 Rev Time 0.00
Received By cthroop Date 2021-01-08 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By cthroop Date 2020-12-30 Time 08:38 Rev Time 0.00
Received By cthroop Date 2020-12-30 Time 06:12 Sent To  
Notes
2020-12-30 08:52:19PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PROJECT DATA/DESIGN PARAMETERS:
  
 PROJECT DATA: 1&2 FAMILY DWELLING UNIT
  OCCUPANCY CLASSIFICATION R3 SFR
 SCOPE OF WORK
  
  
 DESIGN PARAMETERS: 2017 FBC EXISTING BUILDING
  2017 FBC RESIDENTIAL
  2014 NEC
  
 CLASSIFICATION OF WORK: ALTERATION LEVEL II
 BUILDING CLASSIFICATION: VB
 EXPOSURE CLASSIFICATION: C
 RISK CATEGORY: II
 MEAN ROOF HEIGHT:
  
 SITE SPECIFIC DESIGN WIND LOADS PER:
 ASCE 7-10(VULT 170MPH 3 SEC GUST / VASD 132MPH)
 2017 FBC R CHPT. 3
  
 DESIGN WIND PRESSURES:
 WINDOWS AND DOORS ZONE 4 INT. / ZONE 5 CORNER
 (POSITVE/NEGATIVE)
 ROOF ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS)
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 2. PROVIDE DOOR AND WINDOW SCHEDULE: INCLUDE ROUGH
 OPENING AND DESIGN PRESSURES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 3. PROVIDE PRODUCT APPROVALS FOR NEW AND RELOCATED
 WINDOWS AND EXT. DOORS AND LINTELS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, DOOR AND LINTEL
 SUBMITTALS.
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED,
 RECYCLED, OR RECLAIMED MATERIALS WHICH MEET THE
 REQUIREMENTS OF THIS CODE FOR NEW MATERIALS IS
 PERMITTED. USED EQUIPMENT AND DEVICES SHALL NOT BE
 REUSED UNLESS APPROVED BY THE BUILDING OFFICIAL.
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 4. PROVIDE DETAIL OF EXTERIOR WALL IN-FILL AND INTERIOR
 BLOCK WALL IN-FILL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-01-11 Cont ID  
Sent By equinone Date 2021-01-11 Time 12:05 Rev Time 0.00
Received By equinone Date 2021-01-11 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By equinone Date 2020-12-17 Time 16:09 Rev Time 0.00
Received By equinone Date 2020-12-17 Time 15:00 Sent To  
Notes
2020-12-17 16:10:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
 .
 1) PLEASE INCLUDE RISER DIAGRAM SHOWING SERVICE
 ENTRANCE CONDUCTOR SIZE AND GROUNDING DETAILS.
 2) PLEASE SPECIFY AIC RATING OF NEW SERVICE PANEL.
 3) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.12; FBC RE E3902.16 (A NOTE WILL
 SUFFICE)
 4) PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER FBC RE
 E4002.14 (A NOTE WILL SUFFICE)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-13 Cont ID  
Sent By lmarchan Date 2021-01-13 Time 13:37 Rev Time 0.00
Received By lmarchan Date 2021-01-11 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-11 Cont ID  
Sent By lmarchan Date 2021-01-11 Time 13:17 Rev Time 0.00
Received By lmarchan Date 2021-01-06 Time 09:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-30 Cont ID  
Sent By cthroop Date 2020-12-30 Time 09:13 Rev Time 0.00
Received By cthroop Date 2020-12-14 Time 17:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-01-12 Cont ID  
Sent By medwards Date 2021-01-12 Time 11:51 Rev Time 0.00
Received By medwards Date 2021-01-12 Time 11:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-01-08 Cont ID  
Sent By medwards Date 2021-01-08 Time 07:56 Rev Time 0.00
Received By medwards Date 2021-01-08 Time 07:47 Sent To  
Notes
2021-01-08 07:59:02PLEASE EXPLAIN THE NEW 100CFM EXHAUST FAN AT FLOOR
 LEVEL OF THE LAUNDRY CLOSET.
 PLEASE SHOW THE DRYER EXHAUST DUCT FROM DRYER LOCATION
 TO OUTSIDE TERMINATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-17 Cont ID  
Sent By hmoser Date 2020-12-17 Time 09:57 Rev Time 0.00
Received By hmoser Date 2020-12-17 Time 08:05 Sent To  
Notes
2020-12-17 09:57:09PLAN DENIED
 REFER TO SECTION M1502.2 INDEPENDENT EXHAUST SYSTEMS
 DRYER EXHAUST MUST BE INDEPENDENT OF BATHROOM EXHAUST.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561- 805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-01-13 Cont ID  
Sent By lcrespo Date 2021-01-13 Time 12:17 Rev Time 0.00
Received By lcrespo Date 2021-01-13 Time 11:38 Sent To  
Notes
2021-01-13 12:17:3901/13/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By lcrespo Date 2020-12-15 Time 14:21 Rev Time 0.00
Received By lcrespo Date 2020-12-15 Time 12:39 Sent To  
Notes
2020-12-15 14:22:1512/15/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-13 Cont ID  
Sent By lcrespo Date 2021-01-13 Time 12:16 Rev Time 0.00
Received By lcrespo Date 2021-01-13 Time 12:16 Sent To  
Notes
2021-01-13 12:17:051. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B
 SIGNATURE TO:
  
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-08 Cont ID  
Sent By cthroop Date 2021-01-08 Time 16:31 Rev Time 0.00
Received By cthroop Date 2021-01-08 Time 15:48 Sent To  
Notes
2021-01-08 16:32:38PLAN REVIEW / SIGNATURES
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLUMBING PLAN PAGES P01 AND P02
  
  
 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY.
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS/O/B
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-30 Cont ID  
Sent By cthroop Date 2020-12-30 Time 08:36 Rev Time 0.00
Received By cthroop Date 2020-12-30 Time 06:12 Sent To  
Notes
2020-12-30 08:38:07PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. THE OWNER/BUILDER, CONTRACTOR OR DESIGNER OF RECORD
 SHALL PROVIDE THEIR PRINTED NAME AND SIGNATURE ON PLAN
 SHEETS UNDER THEIR AUTHORITY
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  