Plan Review Details - Permit 20120115
Plan Review Stops For Permit 20120115
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By jleahy Date 2021-02-17 Time 09:36 Rev Time 0.00
Received By jleahy Date 2021-02-17 Time 09:30 Sent To  
Notes
2021-02-17 09:37:15SEE ELECTRICAL SUB 21020286 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By jleahy Date 2020-12-10 Time 08:08 Rev Time 0.00
Received By jleahy Date 2020-12-10 Time 08:06 Sent To  
Notes
2020-12-10 08:09:26FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED AN ELECTRICAL PLAN LAYOUT SHOWING CIRCUIT SIZES
 AND BREAKER/FUSE SIZES. 215.5
  
 2) NEED LOAD CALCULATION FOR ADDING AC/HEAT TO UNIT.

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2020-12-17 Cont ID  
Sent By fmittner Date 2020-12-17 Time 14:43 Rev Time 0.00
Received By fmittner Date 2020-12-17 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-18 Cont ID  
Sent By shill Date 2021-02-18 Time 10:09 Rev Time 0.00
Received By shill Date 2021-02-11 Time 13:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-21 Cont ID  
Sent By shill Date 2020-12-21 Time 17:01 Rev Time 0.00
Received By shill Date 2020-12-02 Time 17:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-02-17 Cont ID  
Sent By medwards Date 2021-02-17 Time 09:43 Rev Time 0.00
Received By medwards Date 2021-02-17 Time 09:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By medwards Date 2020-12-04 Time 15:59 Rev Time 0.00
Received By medwards Date 2020-12-04 Time 15:57 Sent To  
Notes
2020-12-04 16:04:07OUR RECORDS INDICATE THERE WAS NOT A MECHANICAL SYSTEM
 PREVIOUSLY AT THE ADDRESS. PLEASE PROVIDE THE
 MECHANICAL SIZING CALCULATIONS FOR THIS SYSTEM. FBC EC
 R403.7.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-03 Cont ID  
Sent By medwards Date 2020-12-03 Time 07:32 Rev Time 0.00
Received By medwards Date 2020-12-03 Time 07:32 Sent To  
Notes
2020-12-03 07:32:56ORIGINAL SIGNED AND SEALED DOCUMENTS ROUTED TO STORAGE.