2021-03-15 09:08:32 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20120096 |
| 3/15/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW LISTED BELOW HAVE NOT BEEN COMPLETELY |
| ADDRESSED. NOTES IN CAP LETTERS HAVE BEEN ADDED FOR |
| FURTHER CLARIFICATION. AFTER REVIEWING THE COMMENTS |
| PLEASE CONTACT ME AT 561-805-6719. |
| |
| 1) FAILED. PLEASE CLARIFY THE EXACT LOCATIONS OF THE |
| NEW METER AND NEW GAS LINE. THE DRAWING APPEARS TO |
| INDICATE THE METER IS FREESTANDING ON THE PROPERTY OR |
| POSSIBLY INSTALLED ON A SITE WALL. THERE ARE NOTES |
| INDICATING THE NEW GAS PIPING TO BE INSTALLED ON |
| UNISTRUTS ALONG THE PROPERTY LINE WHICH IS ASSUMED TO |
| BE ON THE BLOCK SITE WALL INSTALLED UNDER PERMIT- |
| 07100359. PLEASE PROVIDE A COPY OF THE SURVEY MARKED UP |
| TO SHOW THE INSTALLATION LOCATIONS. PLEASE NOTE THE |
| SITE WALL IS INSTALLED IN A UTILITY EASEMENT, THEREFORE |
| IF THE METER AND PIPING ARE TO BE INSTALLED ON THE WALL |
| AN EASEMENT CONSENT FORM SHALL BE SUBMITTED WITH THE |
| SURVEY- SECTION 107.2.1 WPB. THE EASEMENT CONSENT FORM |
| CAN BE FOUND ON THE CITY OF WEST PALM BEACH WEBSITE. IF |
| YOU NEED ASSISTANCE WITH OBTAINING THE FORM PLEASE |
| EMAIL [email protected]. THE NEW GAS PIPING IS BEING INSTALLED |
| IN A FLOOD ZONE. INDICATE WHERE THE UNISTRUTS ARE |
| MOUNTED- SLAB, WALL? PLEASE NOTE THAT THE PIPING SHALL |
| BE INSTALLED A MINIMUM OF 3-1/2 INCHES ABOVE GROUND, |
| AND SHALL BE RESISTANT TO WATER INTRUSION, CORROSION, |
| AND TO HYDROSTATIC AND HYDRODYNAMIC LOADS AND STRESSES- |
| SECTION 322.1.6 FBC RES. |
| |
| 2) FAILED PROVIDE A GAS RISER DRAWING- SECTION |
| 107.3.5.3 WPB. THE RISER SHALL PROVIDE THE FOLLOWING |
| INFORMATION: RISER IS INCOMPLETE- SEE BELOW. |
| |
| B) FAILED. TOTAL DEVELOPED LENGTH OF THE PIPING FROM |
| THE METER TO THE MOST REMOTE GAS OUTLET- SECTION |
| G2413.4.1.NOT PROVIDED. |
| |
| D) FAILED. BRANCH AND CUT PIPING LENGTHS- SECTION |
| G2413.4.2. PLEASE INCLUDE THE PIPING RUN TO THE |
| EXISTING GAS RANGE THAT IS BEING REPLACED. NOT |
| PROVIDED. |
| |
| E) FAILED. INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL |
| LOAD OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & |
| G2413.2 FBC RES. NOT PROVIDED. |
| |
| F) FAILED. LOCATIONS OF REGULATORS AND OUTLET |
| PRESSURES- SECTIONS G2421.1 & G2421.2. NOT PROVIDED. |
| |
| 3) FAILED. INDICATE A GAS-TIGHT CAP WILL BE PROVIDED |
| FOR THE PIPING SUPPLYING THE FUTURE POOL HEATER- |
| SECTION G2415.15 FBC RES. THE RISER DOES NOT SHOW A TEE |
| TO A FUTURE POOL HEATER AND THE GAS-TIGHT CAP NOT |
| PROVIDED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |