Plan Review Details - Permit 20120058
Plan Review Stops For Permit 20120058 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-01-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-01-07 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-01-04 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2020-12-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-12-15 |
Time |
05:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-12-02 |
Time |
09:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2020-12-04 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-12-04 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-12-04 |
Time |
09:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-01-07 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-01-07 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-01-07 |
Time |
15:00 |
Sent To |
|
|
Notes |
2021-01-07 15:42:43 | 01/07/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2020-12-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-12-15 |
Time |
05:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-12-15 |
Time |
04:43 |
Sent To |
|
|
Notes |
2020-12-14 13:51:38 | 1) SUBMIT A COPY OF THE INSTALLATION MANUAL FOR THE | | PUMP FOR REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SHOW THE VENT FOR THE PUMP AND THE CONNECTION POINT | | TO THE EXISTING VENT SYSTEM. THE SANITARY RISER SHOWS | | AN AIR ADMITTANCE VALVE ON THE BREAK SINK. THIS AIR | | ADMITTANCE VALVE CANNOT BE USED TO VENT THE PUMP UNIT | | PER THE MANUFACTURER'S INSTALLATION MANUAL. AN | | INDIVIDUAL VENT MUST NE INSTALLED AND CONNECTED TO A | | CODE COMPLIANT PLUMBING VENT SYSTEM PER FBC-PLUMBING | | SEC. 712.1,906.5. | | 3) THE DISCHARGE LINE FROM THE PUMP SHALL CONNECT TO | | THE SANITARY SYSTEM IN ACCORDANCE WITH FBC-PLUMBING | | SEC.712.3.5. INDICATE ON THE PLAN. | | 4) THE PLANS DO NOT BEAR AN ELECTRONIC SIGNATURE OR | | SEAL PER FL. ADMIN. CODE RULE 61G15-23.004, | | 61G15-23.005 NOR DO THEY BEAR A SEAL OR SIGNATURE PER | | FL. ADMIN. CODE RULE 61G15-23.001. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2020-12-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2020-12-15 |
Time |
05:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2020-12-14 |
Time |
13:52 |
Sent To |
|
|
Notes |
2020-12-14 13:58:09 | PLANS DO NOT BEAR AN ELECTRONIC SEAL OR SIGNATURE OR A | | SIGNATURE AND STAMPED SEAL PER FAC CODE RULE | | 61G15-23.001, 61G15-23.004, 61G15-23.005. |
|
|
|