Plan Review Details - Permit 20120019
Plan Review Stops For Permit 20120019
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-03-01 Cont ID  
Sent By cpuell Date 2021-03-01 Time 12:02 Rev Time 0.00
Received By cpuell Date 2021-03-01 Time 12:02 Sent To  
Notes
2021-03-01 12:17:20PRIMARY ADDRESS CHANGED FROM 575 S ROSEMARY AVE TO 635
 HIBISCUS ST, BASED ON NEW MAIN ENTRANCE. ADDITIONAL
 ADDRESSES REQUIRED FOR ADDITIONAL UNITS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-02-18 Cont ID  
Sent By cpuell Date 2021-02-18 Time 15:01 Rev Time 0.00
Received By cpuell Date 2021-02-18 Time 15:01 Sent To  
Notes
2021-02-18 15:01:41APPLICANT PROVIDED PLANS, PROPOSED ADDRESS OF 551
 HIBISCUS ST, WAITING TO HEAR FROM APPLICANT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-12-12 Cont ID  
Sent By cpuell Date 2020-12-12 Time 08:23 Rev Time 0.00
Received By cpuell Date 2020-12-12 Time 08:23 Sent To  
Notes
2020-12-12 08:25:37PLEASE EMAIL [email protected] WITH A SITE PLAN
 SPECIFICALLY SHOWING WHERE THE PRIMARY ENTRANCE WILL
 BE. OTHER ADDRESSES WILL NEED TO BE ESTABLISHED BUT
 THAT CAN BE DONE UNDER THE MAIN BUILDING PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-08-09 Cont ID  
Sent By rmcphers Date 2021-08-09 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 08:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-06-11 Cont ID  
Sent By rmcphers Date 2021-06-11 Time 12:16 Rev Time 0.00
Received By rmcphers Date 2021-06-11 Time 08:04 Sent To  
Notes
2021-06-11 12:16:42FOUNDATION ONLY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 PLAN REVIEW AUDIT - ONLY FOR FOUNDATION PERMIT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW ON THE STRUCTURAL DRAWINGS OR PROVIDE
 THE ARCHITECTURAL DRAWING THAT SHOWS HOW TERMITE
 PROTECTION IS PROVIDED PER FBC 1816.1
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-06-09 Cont ID  
Sent By jleahy Date 2021-06-09 Time 15:55 Rev Time 0.00
Received By jleahy Date 2021-06-08 Time 14:33 Sent To  
Notes
2021-06-09 15:56:05AUDIT ONLY FOR FOUNDATION PERMIT JLEAHY 6/9/21

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-04-06 Cont ID  
Sent By Mgonzale Date 2021-04-06 Time   Rev Time 0.50
Received By rrossano Date 2021-04-06 Time   Sent To I
Notes
2021-04-06 16:07:52PROVISO:
  
 ENGINEERING PERMIT MUST BE FINALIZED BEFORE 1ST
 INSPECTION.
  
 MGONZALEZ.
2021-03-09 13:53:28PROJECT IS CURRENTLY UNDER REVIEW AND WE ARE
 ANTICIPATING RESPONSES TO ENGINEERING COMMENTS (ENG
 SUBMITTAL E21020003).
  
 THANKS,
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-01-12 Cont ID  
Sent By RRossano Date 2021-01-12 Time   Rev Time  
Received By rrossano Date 2021-01-12 Time   Sent To I
Notes
2021-01-12 12:16:54PLEASE ADVISE IF A FORMAL ENGINEERING SUBMITTAL WAS
 MADE, WE ARE UNABLE TO LOCATE ANYTHING IN OUR RECORDS.
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By pleduc Date 2021-03-03 Time   Rev Time 0.00
Received By pleduc Date 2021-03-03 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-18 Cont ID  
Sent By pleduc Date 2020-12-18 Time   Rev Time 0.00
Received By pleduc Date 2020-12-18 Time 13:23 Sent To  
Notes
2020-12-18 15:19:35THERE IS A NOTE BOX ON SHEET P 100 THAT NO PLUMBING
 CONTRACTOR OR PLUMBING WORK WILL BE DONE UNDER THIS
 PERMIT.
  
 FOR INFORMATIONAL PURPOSES THE FIRE PROVISO WAS
 PROVIDED TO THE FIRE PUMP ROOM WHEN APPLICABLE TO THE
 FOUNDATION WORK.
  
  
 FIRE PROVISO:
  
 THE FIRE PUMP ROOM IS REQUIRED TO HAVE A FLOOR DRAIN.
  
 PER NFPA 20:
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
  
 PLEAE ENSURE COMPLIANCE WHEN APPLICABLE TO THE
 FOUNDATION WORK.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-08-10 Time   Rev Time 0.00
Received By aoliver Date 2021-07-30 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-14 Cont ID  
Sent By cpuell Date 2021-06-14 Time 16:22 Rev Time 0.00
Received By cpuell Date 2021-05-27 Time 19:58 Sent To  
Notes
2021-06-01 20:06:23ROUTED TO BLDG DIV AUDIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-29 Cont ID  
Sent By lmarchan Date 2021-05-29 Time 08:57 Rev Time 0.00
Received By lmarchan Date 2021-05-19 Time 07:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-12 Cont ID  
Sent By lmarchan Date 2021-03-12 Time 10:37 Rev Time 0.00
Received By lmarchan Date 2021-02-26 Time 09:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-12 Cont ID  
Sent By equinone Date 2021-01-12 Time 15:57 Rev Time 0.00
Received By equinone Date 2020-12-17 Time 15:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2021-09-13 Cont ID  
Sent By lcrespo Date 2021-09-13 Time 16:36 Rev Time 0.00
Received By shill Date 2021-05-26 Time 13:50 Sent To  
Notes
2021-09-13 16:37:08SEE EMAIL FROM PBC DATED 9/13/21, IMPACT FEES CAN BE
 PAID PRIOR TO ISSUANCE OF VERTICAL PERMIT
  
  
2021-05-26 13:50:295/26/21 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By shill Date 2020-12-10 Time 16:19 Rev Time 0.00
Received By shill Date 2020-12-10 Time 16:19 Sent To  
Notes
2020-12-10 16:20:25PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-06-14 Cont ID  
Sent By lcrespo Date 2021-06-14 Time 09:51 Rev Time 0.00
Received By lcrespo Date 2021-06-10 Time 17:07 Sent To  
Notes
2021-06-14 09:53:01NO PLUMBING WORK IN THE SLAB SHALL BE PERFORMED WITHOUT
 RISER DETAILS SUBMITTED FOR CODE COMPLIANCE.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2021-08-16 Cont ID  
Sent By dbattles Date 2021-08-16 Time 16:55 Rev Time 0.00
Received By dbattles Date 2021-08-09 Time 10:47 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2021-06-14 Cont ID  
Sent By shill Date 2021-06-14 Time 07:23 Rev Time 0.00
Received By shill Date 2021-06-14 Time 07:23 Sent To  
Notes
2021-06-14 07:24:37AFFIDAVITS TO BE REVIEWED AFTER AUDITS COMPLETE, PRIOR
 TO ISSUANCE
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2021-05-26 Cont ID  
Sent By shill Date 2021-05-26 Time 13:35 Rev Time 0.00
Received By shill Date 2021-05-26 Time 12:33 Sent To  
Notes
2021-05-26 13:37:22****CORRECTIONS****
 ****REVIEW IN PROGRESS***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PAGES V-1 SURVEY, V-2 SURVEY, V-3 SURVEY WERE
 SUBMITTED BUT ARE NOT INCLUDED IN ANY OF THE
 AFFIDAVITS.
 2. AFFIDAVIT INCLUDES AS101 THROUGH AS107, AS302,
 AS309, UNABLE TO LOCATE THESE PAGES IN THE SUBMITTAL.
 3. C3.00, C5.00 WERE SUBMITTED BUT I WAS UNABLE TO
 LOCATE AN AFFIDAVIT FOR THESE PAGES.
 4. PAGES A101, A102, A103, A104, A105, A106, A107,
 A302, A309 WERE SUBMITTED BUT I WAS UNABLE TO LOCATE AN
 AFFIDAVIT FOR THESE PAGES.
 5. FP100 WAS SUBMITTED FOR REVIEW, BUT I WAS UNABLE TO
 LOCATE AN AFFIDAVIT FOR THAT PAGE.
 6. STRUCTURAL CALCULATIONS WERE SUBMITTED FOR REVIEW,
 BUT I WAS UNABLE TO LOCATE AN AFFIDAVIT FOR THAT
 DOCUMENT.
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By shill Date 2021-03-02 Time 07:19 Rev Time 0.00
Received By shill Date 2021-03-02 Time 07:19 Sent To  
Notes
2021-03-02 07:20:30SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AFFIDAVITS NEED TO BE REVIEWED EACH CYCLE
  
 SEE PREVIOUS LIST REGARDING SI AGREEMENT, NOT ADDRESSED
 (SEE ALSO THRESHOLD REVIEW STOP)
  
 SI AGREEMENT SENT TO APPLICANT VIA EMAIL
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2020-12-22 Cont ID  
Sent By rgathrig Date 2020-12-22 Time 12:28 Rev Time 0.00
Received By rgathrig Date 2020-12-22 Time 12:26 Sent To  
Notes
2020-12-22 12:28:02PRIVATE PROVIDER REVIEW, HAS FAILED
 AUTHORITY F.S. 553.791
 DOCUMENTS PROVIDED: NOTICE TO BUILDING OFFICIAL SIGNED
 11/24/2020, CERTIFICATE OF INSURANCE, AND PRIVATE
 PROVIDER RESUMES. THE NOTICE TO BUILDING OFFICIAL
 STATES PLAN REVIEW AND INSPECTIONS. THERE ARE NO PLAN
 REVIEW AFFIDAVITS SUBMITTED. THE PAGES SUBMITTED FOR
 THIS APPLICATION ARE DIGITALLY SIGNED BY WESLEY FOSTER,
 BUT PLAN REVIEW AFFIDAVITS AS REQUIRED BY 553.791(6)
 WERE NOT SUBMITTED. WHEN SUBMITTING THE REQUIRED
 AFFIDAVIT(S) PLEASE IDENTIFY THE DESIGNER OF RECORD,
 PAGE NAMES/PAGE NUMBERS, DATES OF PLANS REVIEWED AND
 THE LATEST REVISION OF THE PAGE IF APPLICABLE.
 THIS JOB IS A THRESHOLD BUILDING SO ALL INSPECTIONS FOR
 THE FOUNDATION WILL BE GOVERNED BY THE REQUIREMENTS OF
 F.S 553.79(5). THE PLANS CONTAIN THE THRESHOLD
 INSPECTION PLAN, BUT NO THRESHOLD INSPECTOR INFORMATION
 WAS PROVIDED. PLEASE PROVIDE THE THRESHOLD INSPECTOR
 INFORMATION.
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 5628056679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-08-10 Cont ID  
Sent By dbattles Date 2021-08-10 Time 12:45 Rev Time 0.00
Received By dbattles Date 2021-08-10 Time 12:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-08-09 Cont ID  
Sent By rmcphers Date 2021-08-09 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2021-08-09 Time 08:43 Sent To  
Notes
2021-08-09 08:47:13SIGNATURE REVIEW
 DOCUMENT " 001 PRIVATE PROVIDER AFFIDAVIT -
 BUILDING.PDF V3 " AND "001 PRIVATE PROVIDER AFFIDAVIT -
 STRUCTURAL.PDF V4 " IN PROJECTDOX DOES NOT SHOW AS
 ELECTRONICALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-05-28 Cont ID  
Sent By cthroop Date 2021-05-28 Time 16:28 Rev Time 0.00
Received By cthroop Date 2021-05-28 Time 16:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By shill Date 2021-03-02 Time 07:27 Rev Time 0.00
Received By shill Date 2021-03-02 Time 07:27 Sent To  
Notes
2021-03-02 07:27:08SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SURVEY IS NOT DIGITALLY SIGNED. PROVIDE DIGITALLY
 SIGNED DOCUMENTS. IF THE SURVEYOR DOES NOT HAVE A
 DIGITAL SIGNATURE, PLEASE HAVE HIM CONTACT ME TO
 DISCUSS OPTIONS.
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-21 Cont ID  
Sent By shill Date 2020-12-21 Time 17:34 Rev Time 0.00
Received By shill Date 2020-12-21 Time 17:34 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2021-05-27 Cont ID  
Sent By rgathrig Date 2021-05-27 Time 15:44 Rev Time 0.00
Received By rgathrig Date 2021-05-27 Time 15:44 Sent To  
Notes
2021-05-27 15:48:44WESLEY FOSTER PE PACIFICA ENGINEERING IS THRESHOLD
 ENGINEER
 THRESHOLD INSPECTION PLAN ON S0.04 THRESHOLD NOTES PAGE
 WILL NEED TO SUBMIT ADDITION THRESHOLD INSPECTION PLAN
 WHEN THE
 BUILDING GOES VERTICAL
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By shill Date 2021-03-02 Time 07:22 Rev Time 0.00
Received By shill Date 2021-03-02 Time 07:22 Sent To  
Notes
2021-03-02 07:23:13SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE PREVIOUS LIST; SPECIAL INSPECTOR AGREEMENT NOT
 PROVIDED. PLEASE SUBMIT.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2020-12-22 Cont ID  
Sent By rgathrig Date 2020-12-22 Time 12:30 Rev Time 0.00
Received By rgathrig Date 2020-12-22 Time 12:28 Sent To  
Notes
2020-12-22 12:30:38THRESHOLD REVIEW FAILED
  
 NO DOCUMENTS FOR THE THRESHOLD INSPECTOR WAS SUBMITTED.
  
 PLEASE SUBMIT
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 5618056679

Review Stop Z ZONING
Rev No 3 Status P Date 2021-05-19 Cont ID  
Sent By eschneid Date 2021-05-19 Time 11:56 Rev Time 0.25
Received By eschneid Date 2021-05-19 Time 11:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-12 Cont ID  
Sent By eschneid Date 2021-03-12 Time 09:38 Rev Time 0.25
Received By eschneid Date 2021-03-12 Time 08:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-05 Cont ID  
Sent By eschneid Date 2021-01-05 Time 13:59 Rev Time 4.00
Received By eschneid Date 2020-12-29 Time 08:51 Sent To  
Notes
2021-01-05 14:05:33FAILED
  
 1) CITYPLACE RETAIL, LLC, THE ROSEMARY SQUARE
 MANAGEMENT, IS REQUIRED TO EITHER STAMP THE PLANS OR
 PROVIDE A LETTER REFERENCING THE PLANS THAT THEY HAVE
 APPROVED. THE MANAGEMENT APPROVAL WAS NOT PROVIDED.
  
 2) PROVIDE A SURVEY OF THE PROPERTY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]