Plan Review Details - Permit 20120003
Plan Review Stops For Permit 20120003
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-12-08 Cont ID  
Sent By jwitmer Date 2020-12-09 Time 08:30 Rev Time 0.00
Received By jwitmer Date 2020-12-09 Time 08:30 Sent To  
Notes
2020-12-08 14:27:39TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-05-27 Cont ID  
Sent By jwitmer Date 2021-05-27 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2021-05-27 Time 08:31 Sent To  
Notes
2021-05-27 08:47:35WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120003
 ADD: 2400 S DIXIE HWY.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD & 4TH REVIEW
 DATE: THURS. MAY 27TH/2021
 ACTION: BUILDING PROVISOS
  
 1) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A
 NEW WALK IN COOLER / FREEZER. PLEASE NOTE WALK IN
 COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS
 AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT
 APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS.
 THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND
 2603.4.1.3.
  
 2) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
  
 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP &
 EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE
 SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP
 DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-04-07 Cont ID  
Sent By jwitmer Date 2021-04-07 Time 10:33 Rev Time 0.00
Received By jwitmer Date 2021-04-07 Time 08:44 Sent To  
Notes
2021-04-07 09:44:26WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120003
 ADD: 2400 S DIXIE HWY.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. APRIL 07TH/2021
 ACTION: BUILDING PROVISOS
  
 1) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A
 NEW WALK IN COOLER / FREEZER. PLEASE NOTE WALK IN
 COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS
 AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT
 APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS.
 THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND
 2603.4.1.3.
  
 2) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 3) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
  
 7) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP &
 EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE
 SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP
 DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-03 Cont ID  
Sent By jwitmer Date 2021-03-03 Time 10:54 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-03-03 10:54:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120003
 ADD: 2400 S DIXIE HWY.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 03RD/2021
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SHEET A101:
 3A) COMPLIED.
  
 3B) SEMI-COMPLIED. A NEW SHEET SHOWING THE BASEMENT
 STAIR, HANDRAIL AND ENCLOSURE. THE BASEMENT PORTION OF
 THE STAIRWAY IS AN OPEN STAIR, NO ENCLOSURE. EXIT
 ACCESS STAIRWAYS ARE ALLOWED IN THE 2017 FBC-B SECTION
 1019.3. THE SUBMITTED PLAN DOES NOT SHOW A GUARDRAIL,
 IT WAS ASSUMED THERE WAS A WALL AND GUARDRAILS WERE NOT
 REQUIRED. GUARDRAILS MUST SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTIONS 1015.3 & 11015.4.
  
 1ST ROUND OF COMMENTS. THERE IS NO INFORMATION ON THE
 STAIRWAY AND HANDRAILS IF THEY ARE EXISTING AND THE
 RISE / RUN OF THE STAIRS NOR IF THERE IS ANY HANDRAILS.
 SEE THE 2017 FBC-EXISTING BUILDING CODE SECTION
 1012.4.2.
  
 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN:
 4A)2ND REQUEST. EGRESS DOORWAYS MUST SHOW THEY ARE
 ACCESSIBLE, THE INTERIOR AND EXTERIOR GRADE ARE IN
 COMPLIANCE WITH THE 2017 ACCESSIBILITY CODE SECTION
 303.2 VERTICAL OR 303.3 BEVELED, CHANGE IN LEVEL GRADE.
 1ST ROUND OF COMMENTS. THE PLANS DO NOT SHOW WHICH
 EGRESS DOORS ARE ACCESSIBLE EXITS. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) SEE NOTE ABOVE 2ND REVIEW. THE PLANS DO NOT SHOW
 COMPLIANCE WITH SECTION 1007.1.1 OF THE 2017 FBC-B, TWO
 EXITS AND OR EXIT ACCESS DOORWAYS.
 WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM
 ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A
 DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 THEM.
 EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL
 NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR AREA TO BE SERVED MEASURED IN A
 STRAIGHT LINE BETWEEN THEM.
  
 4C)2ND REVIEW. SEE COMMENT 3B.
 1ST ROUND OF COMMENTS. PLEASE REVIEW THE STAIRWAY THAT
 LEADS FORM THE BASEMENT. THE 2017 FBC-B SECTION 1019.3
 WOULD REQUIRE THE STAIRWAY TO BE ENCLOSED WITH A SHAFT
 ENCLOSURE CONSTRUCTED IN ACCORDANCE WITH 713. DOORS
 WILL NEED TO SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE
 BARRIER. DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY
 SMOKE DETECTION IN ACCORDANCE WITH 716.5.9.3.
  
 4D) BUILDING PROVISO: THE PROPOSED FLOOR PLAN SHOWS A
 NEW 602 SQ. FT. WALK IN COOLER. PLEASE NOTE WALK IN
 COOLERS REQUIRE A SEPARATE PERMIT, REVIEW AND
 ASSOCIATED FEES. THEY ARE ALSO PART OF THE COMPONENTS
 AND CLADDING OF THE BUILDING AND REQUIRE PRODUCT
 APPROVALS. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS.
 THE 602 SQ. FT. COOLERS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND
 2603.4.1.3.
  
 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE
 FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE
 SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
  
 4E)(1)SEMI-COMPLIED. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
 110X0.05= 6 ACCESSIBLE SEATS. THE PROBLEM IS THE BAR
 AREA SEATING.
  
 4E)(2) SEMI-COMPLIED. THE PROBLEM IS THE BAR AREA
 SEATING. 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4E)(3) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA
 SEATING. 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4E)(4) SEMI-COMPLIED, THE PROBLEM IS THE BAR AREA
 SEATING. 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 4E)(5)(1) COMPLIED. 902.2 CLEAR FLOOR OR GROUND SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(5)(2) SEMI-COMPLIED ,THE PROBLEM AREA IS THE BAR
 AREA SEATING. PLEASE PROVIDE A CUT SECTION THROUGH THE
 ACCESSIBLE SEATING AREA AT THE BAR TO SHOW COMPLIANCE
 WITH 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4F) 2ND REQUEST, THE DESIGNER OF RECORD SHOW THE
 MANEUVERING CLEARANCES ON THE WRONG SIDE OF THE DOOR.
 PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING
 CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 4G) COMPLIED.
  
 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN &
 ELEVATIONS:
 5A) 2ND REQUEST. PLEASE BE AWARE ONE NOTE WAS ADDED
 CERAMIC TILE WAINSCOT WAS ADDED FOR ALL ELEVATIONS. THE
 HEIGHT OF THE WAINSCOT IS NOT GIVEN AND IN THE FINISH
 SCHEDULE THE WALL SCHEDULE STILL STATES TO PAINT THE
 DRYWALL WALLS.
 1ST ROUND COMMENT. THERE IS NO FINISHES SHEET FOR
 FLOORS, WALLS & CEILINGS. SHEET A104 IN THE SOUTH
 ELEVATION OF THE MENS RESTROOM STATES LINE OF SMOOTH,
 HARD, NONABSORBENT SURFACES ABOVE THE FLOOR. 2017 FBC-B
 1210.2.2. WALLS & PARTITIONS. THIS COMMENT IS A RESULT
 OF THE BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 5A)(1) SEMI-COMPLIED. 1210.2.2 WALLS & PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS, URINALS, AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIAL
 USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE.
  
 5B) COMPLIED. LOCATION OF THE BABY CHANGING TABLE.
  
 5C) 2ND ROUND OF COMMENTS. THE PLANS SHOW THE 40 INCHES
 TO THE BOTTOM OF THE MIRROR, NOT THE REFLECTIVE
 SURFACE.
 1ST ROUND OF COMMENTS. IN BOTH THE MENS AND WOMENS
 RESTROOMS THE HEIGHT ABOVE THE FLOOR IS NOT GIVEN, SHOW
 COMPLIANCE WITH 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY
 CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5D-F) COMPLIED.
  
 5G) 2ND ROUND OF COMMENTS. ALL PARTS OF 5G. TO ANSWER
 CODE REQUIREMENTS YOU CAN NOT RECITE THE CODE. 2017
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. W.P.B.
 ADMINISTRATIVE CODE/2017 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "CODE SECTIONS SHALL NOT BE CITED AS A
 WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1ST ROUND OF COMMENTS. WHAT DETAILS FOR ACCESSIBILITY
 WERE NOT PROVIDED AND OR EXCEPTION ARE FOR DRINKING
 FOUNTAINS.
 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 6) COMPLIED.
  
 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302
 FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK
 YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF.
 WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD
 SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO
 ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND
 IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE
 R301.2(2).
  
 8) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 11) BUILDING PROVISO/ DEFERRED SUBMITTALS: IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 12) BUILDING PROVISO/ DEFERRED SUBMITTALS: THE ROOF TOP
 A/C STAND PRODUCT APPROVALS, TO BE REVIEWED BY THE
 DESIGNER OF RECORD. PLEASE IDENTIFY THE FOLLOWING
 REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) OF THE
 ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, THE MEAN
 ROOF HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT,
 CIRCLED THE DESIGN PARAMETERS IN THE TABLES, ANCHORS
 AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE STAND AND
 THE STAND TO THE ROOF. THE PRODUCT APPROVAL IS TO BE
 REVIEWED BY THE DESIGNER OF RECORD, APPROVED BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT.
  
 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) BUILDING PROVISO/ DEFERRED SUBMITTALS: ROOF TOP &
 EQUIPMENT MAINTENANCE LADDER SHOP DRAWINGS TO BE
 SUBMITTED TO DESIGNER OF RECORD FOR REVIEW AND SHOP
 DRAWING STAMP OF APPROVAL BEFORE BEING SUBMITTED TO THE
 BUILDING DEPARTMENT. 2017 FBC-M 306.5 EQUIPMENT AND
 APPLIANCES ON ROOFS.
  
 15) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-07 Cont ID  
Sent By jwitmer Date 2021-03-01 Time 09:02 Rev Time 0.00
Received By jwitmer Date 2021-03-01 Time 15:31 Sent To  
Notes
2021-04-07 09:02:11BUILDING REVIEW # 2 HAD BEEN LOCKED COULD NOT PUT
 COMMENTS IN THE COMPUTER, REFER TO 3RD. REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2020-12-08 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2020-12-08 Time 09:01 Sent To  
Notes
2020-12-08 14:24:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20120003
 ADD: 2400 S DIXIE HWY.
 CONT: BUTLER CONSTRUCTION
 TEL: 561-832-9700
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 08TH/2020
 ACTION: DENIED
  
 1) MISSING CODE DATA NOT FOUND ON THE PLANS, NO LIFE
 SAFETY SHEET.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 1A) MISSING CODE DATA:
 OCCUPANCY GROUP OLD AND PROPOSED NEW
 CHANGE OF OCCUPANCIES FOR A WHOLE BUILDING WOULD
 REQUIRE THE PLANS DESIGNED TO THE 2017 FBC-EXISTING
 BUILDING CODE, CHAPTER 10, AND SECTION 1001.2.2, FOR A
 FULL BUILDING.
  
 1B) MINIMUM TYPE OF CONSTRUCTION SECTION 503
 FIRE SPRINKLERED OR NOT
 FIRE RESISTANCE SEPARATION
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE
 RESISTANCE
  
 1C) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 RISER DIAGRAM
  
 1D) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
 CONSTRUCTION REQUIREMENTS
  
 2) SHEET A002 SITE DETAILS / ACCESSIBLE STALL PARKING.
 THE DETAIL DOES NOT MEET THE CITY STANDARD FOR
 ACCESSIBLE PARKING SPACES, PLEASE REVIEW CITY OF W. P.
 B. STANDARD LINES ARE 4 INCHES WIDE WITH 12 INCHES/ 1
 FOOT BETWEEN LINES.
 ACCESSIBLE PARKING SPACE / STALL PAINTING.
  
 2A) 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE
 SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET
 WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL
 HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3.
 ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR
 OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT
 MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485
 ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL
 PAINTING.
  
 2B) IN THESE DETAILS THE ELEVATIONS ARE NOT GIVEN AT
 THE CORNERS OF THE ACCESSIBLE PARKING SPACE AND
 ADJACENT ACCESS AISLE.
 2017 FBC-ACCESSIBILITY CODE 502.4 ACCESS AISLE &
 PARKING SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND
 SURFACES. PARKING SPACES AND THE ACCESS AISLES SERVING
 THEM SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT
 THE SAME LEVEL AS THE PARKING SPACES THEY SERVE.
 CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES
 NOT GREATER THAN 1:48 SHALL BE PERMITTED.
  
 3) SHEET A101:
 3A) SHEET A101 IT IS ASSUMED TO BE THE PROPOSED LAYOUT
 OF THE BASEMENT PLAN. NO LIFE SAFETY INFORMATION WAS
 PROVIDED FOR THIS REVIEW. THE BASEMENT PLAN DOES NOT
 SHOW THE COMMON PATH OF TRAVEL FROM THE FURTHEST POINT
 TIN THE BASEMENT TO THE HEAD OF THE STAIRS AT WHICH YOU
 HAVE 2 CHOICES OF EXIT TRAVEL, PLEASE SHOW COMPLIANCE
 WITH THE 2017 FBC-B TABLE 1006.3.2(2).
  
 3B) THERE IS NO INFORMATION ON THE STAIRWAY AND
 HANDRAILS IF THEY ARE EXISTING AND THE RISE / RUN OF
 THE STAIRS NOR IF THERE IS ANY HANDRAILS. SEE THE 2017
 FBC-EXISTING BUILDING CODE SECTION 1012.4.2.
  
 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN:
 4A) THE PLANS DO NOT SHOW WHICH EGRESS DOORS ARE
 ACCESSIBLE EXITS. 2017 FBC-ACCESSIBILITY CODE SECTION
 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 4B) THE PLANS DO NOT SHOW COMPLIANCE WITH SECTION
 1007.1.1 OF THE 2017 FBC-B, TWO EXITS AND OR EXIT
 ACCESS DOORWAYS.
 WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM
 ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A
 DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 THEM.
 EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL
 NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF
 THE BUILDING OR AREA TO BE SERVED MEASURED IN A
 STRAIGHT LINE BETWEEN THEM.
  
 4C) PLEASE REVIEW THE STAIRWAY THAT LEADS FORM THE
 BASEMENT. THE 2017 FBC-B SECTION 1019.3 WOULD REQUIRE
 THE STAIRWAY TO BE ENCLOSED WITH A SHAFT ENCLOSURE
 CONSTRUCTED IN ACCORDANCE WITH 713. DOORS WILL NEED TO
 SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE BARRIER.
 DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY SMOKE
 DETECTION IN ACCORDANCE WITH 716.5.9.3.
  
 4D)(1) THE PROPOSED FLOOR PLAN SHOWS A NEW 800 SQ. FT.
 WALK IN COOLER. PLEASE NOTE WALK IN COOLERS REQUIRE A
 SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. THEY ARE
 ALSO PART OF THE COMPONENTS AND CLADDING OF THE
 BUILDING AND REQUIRE PRODUCT APPROVALS. 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS
  
 4D)(2) *00 SQ. FT. COOLERS WILL ALSO NEED TO SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND
 2603.4.1.3.
  
 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE
 FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE
 SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
  
 4E)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. 110X0.05= 6SEATS.
  
 4E)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4E)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4E)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS (CHECK-OUT COUNTERS).
  
 4E)(5)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(5)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4F) PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING
 CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE.
  
 4G) PLEASE NOTE THE EXTERIOR DOOR LOCATED BY THE HAND
 SINK AND OLE HICKORY IS A INSWING DOOR THE OCCUPANT
 LOAD OF THE BUILDING IS WELL OVER 50. 2017 FBC-B
 1010.1.2.1. DIRECTION OF SWING. PIOT OR SIDE-HINGED
 SWINGING DOORS SHALL SWING IN THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING ROOMS OR AREAS CONTAINING AN
 OCCUPANT LOAD OF 50 OR MORE.
  
 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN &
 ELEVATIONS:
 5A) THERE IS NO FINISHES SHEET FOR FLOORS, WALLS &
 CEILINGS. SHEET A104 IN THE SOUTH ELEVATION OF THE MENS
 RESTROOM STATES LINE OF SMOOTH, HARD, NONABSORBENT
 SURFACES ABOVE THE FLOOR. 2017 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 5A)(1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 5A)(2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET
 WALLS SHALL COMPLY WITH 1210.2.
  
 5A)(3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS
 AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY
 WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 5B) WITHIN THE LADIES RESTROOM WHEN THE BABY CHANGING
 TABLE IS IN THE DOWN POSITION YOU DO NOT HAVE THE
 MANEUVERING CLEARANCES AT DOOR # 07. ACCESS. CODE
 404.2.4 MANEUVERING CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE. FIGURE 404.2.4.1(A).
  
 5C) IN BOTH THE MENS AND WOMENS RESTROOMS THE HEIGHT
 ABOVE THE FLOOR IS NOT GIVEN, SHOW COMPLIANCE WITH
 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5D) THE TOILET PAPER DISPENSER DOES NOT COMPLY WITH THE
 DISTANCE FROM THE FRONT OF THE WATER CLOSET. TOILET
 PAPER DISPENSERS. 604.7. THE TOILET PAPER DISPENSER
 SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM
 TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER.
  
 5E) THE ELEVATIONS FOR BOTH THE MENS AND LADIES
 RESTROOMS DEPICT THE GRAB BARS DIMENSIONED FROM THE
 CENTER LINE. PLEASE NOTE THE 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 5F) THE ELEVATIONS FOR BOTH THE MENS AND LADIES
 RESTROOMS DEPICT THE LAVATORY WITH A PROTECTION BOARD
 FOR PREVENTING EXPOSED PIPES IN COMPLIANCE WITH 606.5.
 WHAT IS MISSING FROM THE DETAIL IS COMPLIANCE WITH
 306.2 CLEARANCES FOR TOES AND 306.3 CLEARANCES FOR
 KNEES.
  
 5G) WHAT DETAILS FOR ACCESSIBILITY WERE NOT PROVIDED
 AND OR EXCEPTION ARE FOR DRINKING FOUNTAINS.
 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 6) SHEET S101 THE ROOF FRAMING PLAN. THE WIND DESIGN
 CRITERIA ARE GIVEN ON THIS PLAN WHAT IS MISSING IS THE
 MEAN ROOF HEIGHT. WIND EXPOSURE. APPLICABLE WIND
 DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED.
 TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE
 30.3.1. THE ELEVATIONS ON THE 200 SERIES OF DRAWINGS
 SHOWS THE ROOF AT 29.0 + PARAPET APPROX.. 30 FEET.
  
 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302
 FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK
 YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF.
 WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD
 SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO
 ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND
 IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE
 R301.2(2).
  
 8) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 9) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 12) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL
 WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE
 GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN
 INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT
 OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE
 LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET
 WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE
 PARAPET WALL.
  
 15) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 16) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-05-26 Cont ID  
Sent By jleahy Date 2021-05-26 Time 06:48 Rev Time 0.00
Received By jleahy Date 2021-05-26 Time 06:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-02-26 Cont ID  
Sent By jleahy Date 2021-02-26 Time 13:12 Rev Time 0.00
Received By jleahy Date 2021-02-26 Time 12:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-09 Cont ID  
Sent By jleahy Date 2020-12-09 Time 08:07 Rev Time 0.00
Received By jleahy Date 2020-12-08 Time 16:40 Sent To  
Notes
2020-12-09 08:19:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.1.1
  
 OUTLETS ON CIRCUITS D-13, AND A-17 NEED TO BE GFCI
 PROTECTED 210.8 (B) NFPA 70
  
 PAGE E.2.1
  
 EXIT IN BACK BY OLE HICKORY NEEDS AN EXIT SIGN, NFPA
 101 7.10.1.5.2
  
 PAGE E.3.1
  
 1200 AMPERE MDP SHALL COMPLY WITH 240.87 FOR ARC FLASH
 MITIGATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-05-25 Cont ID  
Sent By pleduc Date 2021-05-25 Time   Rev Time 0.00
Received By pleduc Date 2021-05-25 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-03 Cont ID  
Sent By pleduc Date 2021-03-03 Time   Rev Time 0.00
Received By pleduc Date 2021-03-03 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-12-04 Cont ID  
Sent By pleduc Date 2020-12-04 Time   Rev Time 0.00
Received By pleduc Date 2020-12-04 Time 14:56 Sent To  
Notes
2020-12-04 15:45:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE DOES NOT APPEAR TO BE A LIFE SAFETY PLAN. AS
 THIS IS AN ASSEMBLY OCCUPANCY, A LIFE SAFETY PLAN IS
 REQUIRED.
  
 PER NFPA 101, CH 12 12.4.1.4.3 LIFE SAFETY FLOOR PLANS.
 LIFE SAFETY FLOOR PLANS OF EACH
 LEVEL SHALL BE PROVIDED ? AS APPLICABLE ? WITH THE
 FOLLOWING:
 (1) OCCUPANT LOAD, EXIT LOCATION, EGRESS CAPACITY, MAIN
 ENTRANCE/EXIT, HORIZONTAL EXITS, TRAVEL DISTANCE, AND
 EXIT
 DISCHARGE
  
 PLEASE PROVIDE DETAILS
  
  
 2) THERE IS A BASEMENT INDICATED AND AS THIS IS A NEW
 ASSEMBLY/CHANGE OF OCCUPANCY AND THE BASEMENT HAS WALLS
 AND STORAGE FIRE SPRINKLER PROTECTION IS REQUIRED.
  
 SEE FL BUILDING CODE 903.2.11.1.3
  
 PLEASE REVIEW AND CORRECT OR PROVIDE APPLICABLE CODE
 REFERNCES AND DETAILED NARRATIVE.
  
  
  
 3) THERE IS STORAGE INDICATED IN THE BASEMENT. AS THIS
 IS RESTURAUNT WITH POSSIBLE AEROSOL PRODUCTS, PLEASE
 PROVIDE IN COMPLAINCE WITH THE BELOW CODE.
  
 PER NFPA 1
  
 61.3.4.2 FIRE PROTECTION ? BASIC REQUIREMENTS.
 61.3.4.2.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL
 PRODUCTS SHALL
 NOT BE PERMITTED IN BASEMENT AREAS OF WAREHOUSES. [30B:
 6.4.2.1]
 61.3.4.2.1.1 STORAGE OF LEVEL 2 AND LEVEL 3 AEROSOL
 PRODUCTS SHALL
 BE PERMITTED AS PROVIDED FOR IN 6.3.3 OF NFPA 30B.
 [30B:
 6.4.2.1.1]
  
 PLEASE PROVIDE DETAILS.
  
  
  
 4) THE IS A STAIRWELL LEADING DOWN INTO THE BASEMENT
 THAT MAY BE CONFUSED AS AN EXIT.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10.8.3* NO EXIT.
 7.10.8.3.1 ANY DOOR, PASSAGE, OR STAIRWAY THAT IS
 NEITHER AN EXIT NOR A
 WAY OF EXIT ACCESS AND THAT IS LOCATED OR ARRANGED SO
 THAT IT IS LIKELY TO
 BE MISTAKEN FOR AN EXIT SHALL BE IDENTIFIED BY A SIGN
 THAT READS AS
 FOLLOWS:
 NO
 EXIT
  
 A.7.10.8.3 THE LIKELIHOOD OF OCCUPANTS MISTAKING
 PASSAGEWAYS
 OR STAIRWAYS THAT LEAD TO DEAD-END SPACES FOR EXIT
 DOORS
 AND BECOMING TRAPPED GOVERNS THE NEED FOR EXIT SIGNS.
 THUS,
 SUCH AREAS SHOULD BE MARKED WITH A SIGN THAT READS AS
 FOLLOWS:
 NO EXIT
 SUPPLEMENTARY IDENTIFICATION INDICATING THE CHARACTER
 OF
 THE AREA, SUCH AS TO BASEMENT, STOREROOM, LINEN
 CLOSET, OR THE LIKE, IS PERMITTED TO BE PROVIDED.
  
 PLEASE CORRECT AND PROVIDE FOR THE APPLICABLE SIGNANGE.
  
  
 5) THERE ARE INDICATIONS OF OUTDOOR SMOKERS. AS THIS IS
 LOCATED CLOSE TO RESIDENTIAL HOMES PLEASE PROVIDE HOW
 THE SMOKE FROM THESE SMOKERS WILL BE CONTROLLED.
  
 PLEASE PROVIDE DETAILS.
  
  
 6) SHEET A 102 - THERE IS AN INDICATION OF WALK-IN
 COOLERS WITH NO DETAIL
  
 PLEASE PROVIDE SPECIFIC DETAILS OF THESE COOLERS,
 INCLUDING EXACT CONFIGURATION, DOORS, LIGHTING, EXITS,
 EXIT HARDWARE.
  
  
 7) SHEET E 2.1 - THERE ARE INDICATION OF AN EXT SIGNS
 OVER DOORS 12 & 13 THAT LEAD TO THE OUTDOOR ENCLOSED
 SMOKER AREA.
  
 THERE IS ONE INSWING DOOR FROM THAT AREA. THE DOES NOT
 APPEAR TO BE ANY EXIT SIGNAGE OVER THIS DOOR AND IT
 NEEDS TO SWING IN PATH OF EXIT TRAVEL AND BE EQUIPPED
 WITH EXIT HARDWARE.
  
 ADDITIONALLY, THE EXIT PATH IS REQUIRED TO BE
 ILLUMINATED.
  
 PLEASE REVIW AND CORRECT.
  
  
 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2021-02-01 Cont ID  
Sent By jleahy Date 2021-02-01 Time 13:25 Rev Time 0.00
Received By jleahy Date 2020-12-04 Time 10:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By lcrespo Date 2021-05-26 Time 15:25 Rev Time 0.00
Received By lcrespo Date 2021-05-26 Time 15:25 Sent To  
Notes
2021-05-26 15:26:1405/26/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-04-14 Cont ID  
Sent By lcrespo Date 2021-04-14 Time 14:33 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 16:17 Sent To  
Notes
2021-04-14 14:33:5204/14/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-03-18 Cont ID  
Sent By lcrespo Date 2021-03-18 Time 13:11 Rev Time 0.00
Received By lcrespo Date 2021-03-15 Time 14:42 Sent To  
Notes
2021-03-18 13:12:3003/18/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By abelisle Date 2020-12-10 Time 18:28 Rev Time 0.00
Received By abelisle Date 2020-12-07 Time 17:52 Sent To FIRE
Notes
2020-12-10 17:17:071ST REVIEW FBC-2017 GAS
 PERMIT-2012003
 12/10/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A GAS SUB PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1
 3) GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS SEC. 402.2 AND 301.3
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1
 5) GAS SHUTOFF VALVES FOR EACH APPLIANCE SHALL BE
 INDICATED ON THE GAS ISOMETRIC. WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6) 1" IS SHOWN AFTER THE REQULATOR FOR THE SMOKERS AND
 NOT 3/4" PLEASE CLARIFY
 7) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE SMOKERS.
 FBC FG SEC.305.1
 8) THERE IS NO PIPE SIZE INDICATED ON THE EQUALIZER
 OVERHEAD LINE INDICATED
 9) ALL FLEXIBLE CONNECTORS USED TO CONNECT GAS
 APPLIANCES SHALL BE INSTALLED PER FLEXIBLE CONNECTORS
 MANUFACTURES INSTALLATION INSTRUCTIONS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-27 Cont ID  
Sent By lmarchan Date 2021-05-27 Time 12:31 Rev Time 0.00
Received By lmarchan Date 2021-05-24 Time 08:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-04-14 Cont ID  
Sent By lcrespo Date 2021-04-14 Time 14:46 Rev Time 0.00
Received By lcrespo Date 2021-04-06 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-22 Cont ID  
Sent By pvalenti Date 2021-03-22 Time 08:59 Rev Time 0.00
Received By pvalenti Date 2021-02-24 Time 07:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-04 Cont ID  
Sent By lmarchan Date 2021-01-04 Time 09:42 Rev Time 0.00
Received By lmarchan Date 2020-12-01 Time 18:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-06-30 Cont ID  
Sent By lmarchan Date 2021-06-30 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2021-05-27 Time 12:31 Sent To  
Notes
2021-06-18 08:12:46RECEIPT MU-2021-28973 - $70,888.67 - PAID
2021-05-27 12:31:585/27/21 EMAILED IMPACT FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-12-08 Cont ID  
Sent By jwitmer Date 2020-12-08 Time 14:26 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-12-08 14:26:25CHANGE IN OCCUPANCY. IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 10:36 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 10:14 Sent To  
Notes
2021-03-01 10:37:50KITCHEN HOOD SYSTEMS AND MUA'S WILL REQUIRE SEPARATE
 PERMIT AND REVIEWS.
 REFRIGERATION SYSTEMS WILL REQUIRE SEPARATE PERMIT AND
 REVIEWS. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By medwards Date 2020-12-04 Time 13:56 Rev Time 0.00
Received By medwards Date 2020-12-04 Time 13:56 Sent To  
Notes
2020-12-04 13:56:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20120003
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) HOODS SHALL BE SUBMITTED UNDER A SEPARATE PERMIT AND
 REVIEWED SEPARATELY.
  
 2) ALL REFRIGERATION SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT AND REVIEWED SEPARATELY.
  
 3) PLEASE PROVIDE THE MUA UNITS ON THE MECHANICAL
 SCHEDULE SHEET. FBC 107.2.1
  
 4) SHEET M0.3 INDICATES MUA-2 AND MUA-4. SHEET M1.2
 INDICATES MUA-1 ON THE ROOF. THESE PAGES DO NOT MATCH,
 PLEASE BE CONSISTENT ON BOTH SHEETS. FBC 107.2.1
  
 5) SHEET M0.3 INDICATES KEF-1, KEF-3 AND KEF-5. SHEET
 M1.2 INDICATES ONLY KEF-1 AND KEF-5. PLEASE SHOW THE
 LOCATION OF KEF-3. FBC 107.2.1
  
 6) PLEASE INCLUDE THE KEF?S ON THE FAN SCHEDULE ON
 SHEET M0.2 FBC 107.2.1
  
 7) PLEASE PROVIDE ON DRAWING THE ACCESS POINT FOR THE
 ROOF. FBC M 306.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By lcrespo Date 2021-05-26 Time 15:15 Rev Time 0.00
Received By lcrespo Date 2021-05-26 Time 15:15 Sent To  
Notes
2021-05-26 15:25:5005/26/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-04-14 Cont ID  
Sent By lcrespo Date 2021-04-14 Time 14:45 Rev Time 0.00
Received By lcrespo Date 2021-04-13 Time 16:17 Sent To  
Notes
2021-04-14 14:46:0104/14/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-18 Cont ID  
Sent By lcrespo Date 2021-03-18 Time 11:45 Rev Time 0.00
Received By lcrespo Date 2021-03-15 Time 14:41 Sent To  
Notes
2021-03-18 11:45:3803/18/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A CIVIL DRAWING SHOWING THE GREASE
 INTERCEPTOR'S LOCATION AND SIZE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. ON THE COVER SHEET, PLEASE PROVIDE UNDER CODE DATA
 THE YEAR, PLUMBING AND ACCESSIBILITY REFERENCED USED,
 AS WELL AS THE GAS PER THE WPB AMENDMENTS TO THE FBC
 SEC. 101.4 REFERENCED CODES.
  
 3. ON P0.1 UNDER PLUMBING FIXTURES;
  
 A. NOTE THREE HAS A TABLE BUT NO YEAR REFERENCE OR CODE
 TYPE. PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. NOTE FOUR REFERS TO WALL-HUNG PLUMBING FIXTURES, AND
 CODE REFERENCE IS NOT FOUND. PLEASE CLARIFY AND OR
 CORRECT IT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. NOTE FIVE HAS UNDER LAVATORIES EXPOSED PIPING, AND
 IT SHOULD BE 2017 FBC ACC SEC. 606.5; PLEASE CORRECT
 PER THE 2017 FBC ACC SEC. 606.5.
  
 4. ON SHEET P0.2;
  
 A. IN DETAIL TEN, THERE ARE TANK-LESS WATER HEATERS AND
 NO SPECIFICATIONS PROVIDED; SOME UNITS HAVE
 CONDENSATION IN THEIR SYSTEMS FOR THE WATER HEATING.
 PLEASE PROVIDE MANUFACTURER SPECIFICATIONS OR NOTE THE
 CONDENSATE TO AN APPROVED DISPOSAL PLACE PER THE 2017
 FBC M 307.2.1 CONDENSATE DISPOSAL.
  
 B. PLEASE PROVIDE DETAIL FOR THE EQUIPMENT AND FIXTURES
 UTILIZED FOR THE STORAGE, PREPARATION, AND HANDLING AND
 SHOW THE MULTIPLE-COMPARTMENT SINK THAT SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR PER THE 2017 PBC SEC.
 802.1.2 FLOOR DRAINS IN FOOD STORAGE AREAS.
  
 5. ON SHEET P0.3, THE SUMP PUMP SHALL DISCHARGE THROUGH
 A CONNECTION THAT SHALL BE MADE THROUGH A WYE FITTING
 INTO THE TOP OF THE DRAINAGE PIPING PER THE 2017 FBC P
 712.3.5. PUMP CONNECTION TO THE DRAINAGE SYSTEM.
  
 6. ON SHEET P0.4;
  
 A. ON THE RECIRCULATION SYSTEM WILL REQUIRE INSULATION,
 AND PLEASE PROVIDE SIZE, DETAIL, AND VERBIAGE FOR
 APPLICATION PER THE 2017 FBC EC SEC. C403.2.10.
  
 B. THE WATER CIRCULATION SYSTEM SHALL BE A DEDICATED
 RETURN PIPE, PER THE 2017 FBC EC SEC. C404.6.1
 CIRCULATION SYSTEMS.
  
 C. THE RECIRCULATION SYSTEM SHALL BE THE NEAREST SOURCE
 OF HEATED WATER, AND THE FIXTURE SUPPLY PIPE'S
 TERMINATION SHALL BE PER THE 2017 TABLE 404.5.1.
  
 D. ON THE HOSE BIBBS, THE ROOF PLAN SHOWS TWO, AND ONLY
 ONE IS SHOWN ON THE WATER RISER DIAGRAM. PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. ON THE ISOMETRIC, YOU SHOW DOUBLE CHECK VALVES FOR
 THE ICE MAKER AND COFFEE MAKER THAT SHALL BE EQUIPPED
 WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE
 1024 PER THE 2017 FBC SEC. 608.13.10, PLEASE PUT A NOTE
 ON SCHEDULE, AND IF THERE ARE BEVERAGE, THEY SHALL BE
 EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES
 WITH ASSE 1022 PER THE 2017 FBC SEC. 608.16.1.
  
 6. ON SHEET P1.1, THE SERVICE SINK AND MOP SINK
 SURROUNDING WALLS SHALL BE NON-ABSORBENT SURFACE, AND
 PAINT IS NOT ACCEPTABLE PER THE AHJ AND ACCORDING TO
 THE 2017 FBC BUILDING 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 PLEASE REFER TO THE BUILDING COMMENT FOR THE FIXTURE
 WALL IN ALL RESTROOMS.
  
 7. ON SHEET A104, PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES PER FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE (DRINKING FOUNTAIN, TOILET, LAVS,
 AND URINAL).
  
 A. FOR THE DRINKING, PLEASE PROVIDE DRAWINGS AND
 DETAILS SHOWING: THAT SHOWS THE KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS PER THE 2017
 FBC ACC SEC. 306, 307, & 602.2, COMPLIANCE WITH 2017
 FBC ACC SEC. 307.2 PROTRUSION LIMITS.
  
 B. ON LAVS IN THE OPEN RESTROOM FOR MEN'S AND WOMAN'S,
 PLEASE SHOW CLEAR FLOOR SPACE FOR A FORWARD APPROACH,
 AND IT SHALL COMPLY PER THE 2017 FBC ACC SEC. 602.2.
  
 C. IN THE MEN'S RESTROOM FOR THE URINAL, PLEASE SHOW
 CLEAR FLOOR SPACE FOR A FORWARD APPROACH, AND IT SHALL
 COMPLY PER THE 2017 FBC ACC SEC. 602.2.
  
 D. THE WATER CLOSETS SHOW THE FLUSH VALVE'S LOCATION ON
 THE OPPOSITE SIDE OF THE OPEN AREA. PLEASE MOVE PER THE
 2017 FBC SEC. 604.6 FLUSH CONTROLS.
  
 E. PLEASE SHOW THE URINAL HEIGHT OF 17" INCHES SHALL BE
 A MAXIMUM AND 13 1/2" INCHES PER THE 2017 FBC ACC. SEC.
 605.2
  
 F. PLEASE SHOT THE WALLS OR PARTITIONS THAT SHALL BEGIN
 AT A HEIGHT NOT GREATER THAN 12 INCHES FROM AND EXTEND
 NOT LESS THAN 60 INCHES ABOVE THE FINISHED FLOOR
 SURFACE PER THE 2017 FBC P 405.3.5.
  
 E. PLEASE SHOW THE TOILET PAPER DISPENSERS SHALL BE 7"
 INCHES MINIMUM AND 9" INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF DISPENSER
 PER THE 2017 FBC ACC SEC. 604.7.
  
 F. PEASE SHOWS THE HANDICAP CAP WATER CLOSET FLUSH
 CONTROL SHALL BE HAND OPERATED OR AUTOMATIC AND SHALL
 BE 36? INCHES MAXIMUM ABOVE THE FINISH FLOOR AND ON THE
 OPEN SIDE PER THE 2017 FBC ACC SEC. 604.9.5.
  
 G. PLEASE SHOW OR NOTE THAT THE DOOR HANDLE HARDWARE
 SHOULD BE NOTED ON BOTH SIDES OF THE DOOR PER THE 2017
 FBC ACC SEC. 404.2.7.
  
 H. PLEASE NOTE THAT TEMPERED WATER SHALL BE DELIVERED
 FROM LAVATORIES AND GROUP WASH FIXTURES LOCATED IN
 PUBLIC TOILET FACILITIES PROVIDED FOR CUSTOMERS,
 PATRONS, AND VISITORS. TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
  
 I. PLEASE NOTE THAT ALL SEAT NEEDS TO BE OPEN FRONT,
 2017 FBC P 420.3 WATER CLOSET SEATS.
  
 K. THE MIRRORS NEED TO THE REFLECTIVE PART OF THE
 MIRROR AT 40" PER THE 2017 FBC ACC SEC. 603.3.
  
 L. ON THE ELEVATION DRAWING FOR MEN, RESTROOM THE GRAB
 BARS IN THE REAR WALL SHALL COMPLY WITH 2017 FBC SEC.
 604.5.2. PLEASE SHOW THE DIMENSIONS TO THE CENTER ON A
 HORIZONTAL VIEW.
  
 M. ON THE ELEVATION FOR THE DRAWING WOMAN'S, THE GRAB
 BARS ON THE SIDE SHALL COMPLY WITH 2017 FBC SEC.
 604.5.1. PLEASE SHOW THE DIMENSIONS TO THE CENTER ON A
 HORIZONTAL VIEW.
  
 PLEASE FEEL FREE TO CALL ME TO DISCUSS ANY COMMENTS OR
 CONCERNS ON THE ABOVE CORRECTION.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By abelisle Date 2020-12-10 Time 17:14 Rev Time 0.00
Received By abelisle Date 2020-12-07 Time 17:48 Sent To  
Notes
2020-12-08 16:40:021ST REVIEW FBC-2017 PLUMBING
 PERMIT-2012003
 12/10/2020
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 FBCACCESS. SEC. 211.2 & FBC-PLUMBING SEC. 410.3.
 2) BAR AREA SHALL HAVE AN ACCESSIBLE TOP ELEVATION AS
 PER FBC 2017 A 902.1 A902.2 A902.3
 3) PLEASE PROVIDE THE USE AND OCCUPANCY FOR THIS
 INTERIOR BUILD-OUT WILL BE. PREVIOUS CITY RECORD
 INDICATES THAT THIS WAS A A3 GYM AND IT APEARS THIS IS
 GOING TO BE A A2. THIS INFORMATION NEEDS TO BE ON THE
 PLANS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW
 PREVENTER. MANUFACTURER'S SPECIFICATIONS AND A SEPARATE
 PLUMBING PERMIT SHALL BE SUBMITTED PRIOR TO THE
 INSTALLATION OF THE DEVICE. THE DEVICES MUST BE
 INSTALLED BY A LICENSED PLUMBING
 CONTRACTOR.F.S.489.103.
 5) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GREASE
 INTERCEPTOR. MANUFACTURER'S SPECIFICATIONS & DETAILS
 AND FACTORY SIZING CALCULATIONS WILL BE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE INTERCEPTOR PERMIT.
 6) A SEPARATE PERMIT WILL BE REQUIRED FOR THE GAS.
 7) BACKLOW PREVENTERS ARE REQUIRED AT THE ICE MAKER,
 COFFEE, CARBONATED SODA, CAN WASH, DISHWASHER AND SHALL
 BE INDICATED ON P0.4
 8) ON P0.3 CIRCUIT VENT REQUIRED BEFORE THE LAST WATER
 CLOSET AND BEFORE THE FLOOR DRAIN.
 9) PROVIDE THE DISTANCES FOR DRAIN S3 AND FS FROM POINT
 OF VENT, IT MAY BE NECISSARY TO ADD A VENT ON THE DRAIN
 MARKED S3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-03-17 Cont ID  
Sent By lcrespo Date 2021-03-17 Time 09:11 Rev Time 0.00
Received By lcrespo Date 2021-03-17 Time 09:09 Sent To  
Notes
2021-03-17 09:11:32PER FAE CONSULTING?S RESPONSE: ARCHITECT SHALL PROVIDE
 SEPARATE PERMIT FOR RENIEW. A GENERAL PLUMBING
 CONTRACTOR SHALL PROVIDE GREASE INTERCEPTOR
 MANUFACTURER SPECIFICATIONS, DETAILS AND FACTORY SIZING
 CALCULATIONS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-05-26 Cont ID  
Sent By pvalenti Date 2021-05-26 Time 06:06 Rev Time 0.00
Received By pvalenti Date 2021-05-26 Time 06:06 Sent To  
Notes
2021-05-26 06:10:59 
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEWS OK BY SUBMITTAL OF PAPER ORIGINALS
 SIGNED/SEALED. THESE SUBMITTALS HAVE BEEN ROUTRED TO AO
 FOR STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-04-14 Cont ID  
Sent By lcrespo Date 2021-04-14 Time 14:45 Rev Time 0.00
Received By lcrespo Date 2021-04-14 Time 14:45 Sent To  
Notes
2021-04-14 14:45:19SOME PAGES ARE NOT SIGNED AND SEALED DRAWINGS WHICH
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED BY THE
 ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC PLAN
 REVIEW. - PLEASE DROP OFF THE ORIGINAL SIGNED AND
 SEALED DOCUMENT ALONG WITH A "PLAN REVIEW REQUEST FORM"
 EXPLAINING THE REASON FOR SUBMITTING THE DOCUMENT OR
 DRAWINGS. THE PLAN REVIEW REQUEST FORM CAN BE OBTAINED
 BY EMAILING [email protected] AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By medwards Date 2021-03-01 Time 10:46 Rev Time 0.00
Received By medwards Date 2021-03-01 Time 10:46 Sent To  
Notes
2021-03-01 10:47:222ND NOTICE:
 THE ARCHITECTURAL AND STRUCTURAL SHEETS MUST BE
 DIGITALLY SIGNED AND SEAL OR PAPER ORIGINALS BROUGHT TO
 THE OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By medwards Date 2020-12-04 Time 14:19 Rev Time 0.00
Received By medwards Date 2020-12-04 Time 14:19 Sent To  
Notes
2020-12-04 14:21:10THE ARCHITECTURAL AND STRUCTURAL SHEETS MUST BE
 DIGITALLY SIGNED AND SEAL OR PAPER ORIGINALS BROUGHT TO
 THE OFFICE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2021-05-27 Cont ID  
Sent By llouie Date 2021-05-27 Time   Rev Time 0.00
Received By llouie Date 2021-05-27 Time   Sent To  
Notes
2021-05-27 09:35:08ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) SUBJECT TO THE CONDITIONS IN THE APPROVAL LETTER
 FOR CASE NO. ISPR 20-09 (ATTACHED AND ON FILE WITH THE
 DEVELOPMENT SERVICES DEPARTMENT - PLANNING DIVISION).
 CONDITIONS MUST BE SATISIFIED PRIOR TO THE ISSUANCE OF
 A C.O. - CONTRACTOR STEPHEN BUTLER HAS BEEN NOTIFIED.
  
 2.) SEPARATE PERMITS REQUIRED FOR EXTERIOR SITE WORK
 (I.E. LANDSCAPING, SITE LIGHTING, PAVING/PARKING LOT,
 DUMPSTER ENCLOSURE, BICYCLE RACKS, FENCE, ETC.).
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2021-04-13 Cont ID  
Sent By llouie Date 2021-04-13 Time   Rev Time 0.00
Received By llouie Date 2021-04-13 Time   Sent To  
Notes
2021-04-13 13:54:13** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THIS SITE HAS A PENDING SITE PLAN APPLICATION IN
 REVIEW WITH THE PLANNING DEPARTMENT (REFERENCE: ISPR
 CASE NO. 20-09). SITE PLAN APPROVAL MUST BE GRANTED
 PRIOR TO ZONING APPROVAL FOR THIS PERMIT. [12/7/2020
 AND 3/1/2021 REPEAT COMMENT]
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * REFERENCE: ISPR 20-09
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-01 Cont ID  
Sent By llouie Date 2021-03-01 Time   Rev Time 0.00
Received By llouie Date 2021-03-01 Time   Sent To  
Notes
2021-03-01 10:28:24** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THIS SITE HAS A PENDING SITE PLAN APPLICATION IN
 REVIEW WITH THE PLANNING DEPARTMENT (REFERENCE: ISPR
 CASE NO. 20-09). SITE PLAN APPROVAL MUST BE GRANTED
 PRIOR TO ZONING APPROVAL FOR THIS PERMIT. [12/7/2020
 REPEAT COMMENT]
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * REFERENCE: ISPR 20-09
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By llouie Date 2020-12-07 Time   Rev Time  
Received By llouie Date 2020-12-07 Time   Sent To  
Notes
2020-12-07 16:04:32** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THIS SITE HAS A PENDING SITE PLAN APPLICATION IN
 REVIEW WITH THE PLANNING DEPARTMENT (REFERENCE: ISPR
 CASE NO. 20-09). SITE PLAN APPROVAL MUST BE GRANTED
 PRIOR TO ZONING APPROVAL FOR THIS PERMIT.
  
  
 NOTES:
  
 * ANY REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * REFERENCE: ISPR 20-09
  
  