2020-12-15 13:08:10 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20111206 |
| 12/15/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P101A: PLEASE CLARIFY IF THE PRVS ARE TO BE |
| INSTALLED ON THE WATER OR GAS SUPPLY PIPING TO THE |
| WATER HEATERS. THE PLAN INDICATES THEY ARE TO BE |
| INSTALLED ON THE GAS PIPING, HOWEVER THE REVISION |
| NARRATIVE I.C. THOMASSON ASS. DOES NOT SPECIFY EITHER |
| WATER OR GAS- SECTION 107.2.1 WPB. |
| |
| 2) P101A: REVISE SHEET P002 TO SHOW THE LOCATIONS OF |
| THE PRVS IN THE WATER HEATER DETAIL- SECTION 107.2.1 |
| WPB. |
| |
| 3) P101A: PROVIDE A PRV VENTING DIAGRAM SHOWING THE |
| TYPE AND SIZE OF VENT MATERIAL, VENT RUN AND |
| TERMINATION LOCATION- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |