Plan Review Details - Permit 20111134
Plan Review Stops For Permit 20111134
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By rbrown Date 2020-12-03 Time 17:01 Rev Time 0.00
Received By rbrown Date 2020-12-03 Time 17:01 Sent To  
Notes
2020-12-03 17:04:02CITY OF WEST PALM BEACH EXECUTIVE ORDER 2020-15 (EVENTS
 AND GATHERINGS) REGARDING THE NOVEL CORONAVIRUS,
 COVID-19:
  
 PROVISOS:
  
 1) PRESENTERS AND PRODUCTION TEAM ONLY. PLANS STATE 40
 OCCUPANTS MAXIMUM.
  
 2) APPLICATION MUST COMPLY WITH CITY OF WEST PALM BEACH
 EXECUTIVE ORDER 2020-15 WHICH WENT INTO EFFECT ON
 NOVEMBER 4, 2020.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
  
 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By rbrown Date 2020-11-25 Time 19:26 Rev Time 0.00
Received By rbrown Date 2020-11-25 Time 19:26 Sent To  
Notes
2020-11-25 19:38:33CITY OF WEST PALM BEACH EXECUTIVE ORDER 2020-15 (EVENTS
 AND GATHERINGS) REGARDING THE NOVEL CORONAVIRUS,
 COVID-19:
  
 1) THE SUBMITTED PLAN SHOWS SEETING SECTIONS WITH 96,
 90, 70, 68 AND 62 SIDE-BY-SIDE SEATS FOR THIS PROPOSED
 INDOOR EVENT. THAT CONFIGUARTION DOES NOT ADDRESS CDC
 GUIDANCE FOR SOCIAL DISTANCING TO REDUCE EXPOSURE TO
 THE NOVEL CORONAVIRUS, COVID-19.
  
 2) SECTION 4 OF CITY OF WEST PALM BEACH EXECUTIVE ORDER
 2020-15 WHICH WENT INTO EFFECT ON NOVEMBER 4, 2020, AND
 CAN BE VIEWED AT
 HTTPS://WWW.WPB.ORG/HOME/SHOWDOCUMENT?ID=2653 STATES
 THAT THE CITY RESERVES THE RIGHT TO CANCEL PERMITTED
 EVENTS IF THE COUNTY-WIDE POSITIVITY RATE WEEKLY
 AVERAGE EXCEEDS 5% FOR 4 CONSECUTIVE WEEKS. ACCORDING
 TO THE POSITIVE TEST RATE GRAPH ON THE FOLLOWING
 WEBSITE (SEE WEB LINK BELOW), THE PALM BEACH COUNTY
 POSITIVITY RATE RISED TO 5.8% ON OCTOBER 28, 2020, AND
 HAS RISEN STEADILY SINCE THEN TO THE CURRENT POSITIVITY
 RATE OF 8.7%, AND IT CONTINUES TO INCREASE. THAT MEANS
 THAT THE POSITIVITY RATE WEEKLY AVERAGE WILL HAVE
 EXCEEDED 5% FOR 4 CONSECUTIVE WEEKS LEADING UP TO THE
 EVENT.
 PALM BEACH COUNTY POSITIVITY RATE GRAPH:
 HTTPS://COVIDACTNOW.ORG/US/FLORIDA-FL/COUNTY/PALM_BEACH
 _COUNTY?S=1371355
  
 3) FOR THE REASONS STATED ABOVE THIS EVENT PERMIT
 APPLICATION CANNOT BE APPROVED AT THIS TIME. IF THE
 EVENT IS TO PROCEED WHEN THE RISK OF EXPOSURE TO THE
 NOVEL CORONAVIRUS, COVID-19 HAS REDUCED, STRUCTURAL AND
 ACCESSIBILTY DETAILS FOR THE STAGE, DETAILS FOR THE
 MECHANICAL VENTILATION BASED ON THE NUMBER OF
 ATTENDEES, AND DETAILS FOR NUMBER AND CONFIGURATION OF
 WHEELCHAIR ACCESSIBLE RESTROOMS, WOULD ALL BE REQUIRED.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
  
 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-03 Cont ID  
Sent By equinone Date 2020-12-03 Time 17:34 Rev Time 0.00
Received By equinone Date 2020-12-03 Time 17:34 Sent To  
Notes
2020-12-03 17:42:14CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: APPROVED WITH PROVISOS AND
 SUBJECT TO FIELD VERIFICATION
  
 CITY OF WEST PALM BEACH EXECUTIVE ORDER 2020-15 (EVENTS
 AND GATHERINGS) REGARDING THE NOVEL CORONAVIRUS,
 COVID-19:
  
 PROVISOS:
  
 1) PRESENTERS AND PRODUCTION TEAM ONLY. PLANS STATE 40
 OCCUPANTS MAXIMUM.
  
 2) APPLICATION MUST COMPLY WITH CITY OF WEST PALM BEACH
 EXECUTIVE ORDER 2020-15 WHICH WENT INTO EFFECT ON
 NOVEMBER 4, 2020.
  
 3) ALL WORK SUBJECT TO FIELD VERIFICATION BY CITY OF
 WEST PALM BEACH ELECTRICAL INSPECTORS. VERIFICATION
 SHALL INCLUDE ELECTRICAL LOADS, FEEDER SIZES,
 OVERCURRENT PROTECTION, GROUNDING DETAILS.
  
  
 END OF REVIEW COMMENTS
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
 ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-02 Cont ID  
Sent By pleduc Date 2020-12-02 Time   Rev Time 0.00
Received By pleduc Date 2020-12-02 Time 14:03 Sent To  
Notes
2020-12-02 14:04:45PER EMAIL COMMENTS TO BUILDING OFFICIAL: PRODUCTION
 STAFF ONLY, NO GENERAL PUBLIC
  
 ADDITIONALLY:
  
 ALL EXITS SHALL NOT BE LOCKED WHEN BUILDING IS OCCUPIED
  
 ALL EXITS FREE EGRESS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By pleduc Date 2020-11-25 Time   Rev Time 0.00
Received By pleduc Date 2020-11-25 Time 12:19 Sent To  
Notes
2020-11-25 12:46:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET SITE PLAN - THE OCCUPANCY LOAD CALUCLATION
 DOES NOT APPEAR TO MEET THE REQUIRMENTS OF NFPA 101, CH
 7
  
 13,237 SQ FT OF AN ASSEMBLY OCCUPANCY IS PER TABLE
 7.3.1.2 AT 15 SQ FT/ PERSON. P OR 889
  
 PLEASE REVIEW AND CORRECT.
  
  
 1A) THERE ARE INDICATIONS OF STAIRS LEADING FROM EACH
 AREA AS A PART OF THE EGRESS PATH TO A PUBLIC WAY.
  
 THE CAPACITY AND CLACULATION OF STAIRS WITHIN AN EXIT
 TRAVLE PATH ARE CALCULATED DIFFERENT AND SEPARATE OF A
 SIMPLE EXIT OPENING.
  
 PER TABLE 7.3.3.1 - .3 IS THE REQUIRED FACTOR
  
 PLEASE CORRECT.
  
  
  
 1B) BASED ON THE ABOVE THERE ARE INSUFFICIENT EGRESS
 CAPACITY TO ACCOMDATE THE REQUIREMENT.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) THERE IS AN INDICATION A FIRE SPRINKLERS AND A
 STATEMENT " AND SHALL HAS A FIRE ALARM SYSTEM"
  
 PLEASE DEFINE THIS STATEMENT AND PROVIDE WHAT TYPE OF
 FIRE ALARM IS EXISTING OR WILL BE PROVIDED.
  
 WHAT KIND/TYPE/LOCATION OF NOTIFICATION DEVICES ARE
 WITHIN THE PROPOSED AREA?
  
 PLEASE PROVIDE DETAILS.
  
  
 2A) ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) EXIT DOORS ARE INDICATED; HOWEVER, THERE ARE NO
 INDICATIONS OF THE EXIT HARDWARE TYPE.
  
 PANIC HARDWARE IS REQUIRED.
  
 PER NFPA 101, CH 12 ASSEMBLY OCCUPANCIES
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT.
  
  
  
 4) PLEASE PROVIDE DETAILS OF WHAT KIND OF EVENT IS
 PROPOSED.
  
 WILL THERE BE ANY PYROTECHICS/ OPEN FLAME EFFECTS,
 ETC.?
  
 PLEASE PROVIDE DETAILS
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-11-30 Time   Rev Time 0.00
Received By bbennett Date 2020-11-24 Time 16:35 Sent To  
Notes
2020-11-30 19:23:51EVENT PERMIT APPLICATION IS BEING WITHDRAWN BECAUSE THE
 PRESENTATION WILL NOW BE VIRTUAL SO THERE WILL NOT BE
 ANY IN-PERSON ATTENDEES. RB

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By rbrown Date 2020-12-03 Time 19:19 Rev Time 0.00
Received By rbrown Date 2020-12-03 Time 19:19 Sent To  
Notes
2020-12-03 19:22:47DUE TO COVID-19 CONCERNS THE EVENT ORGANIZER HAS SCALED
 BACK THE PRODUCTION SO THAT IT IS A VIRTUAL PRESENATION
 WITH NO AUDIENCE PREESENT. THERE WILL BE NO MORE THAN
 40 PEOPLE IN THE BUILDING AT THE TIME OF THE EVENT AND
 THEY WILL BE THE PRESENTERS AND THE PRODUCTION STAFF.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
  
 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By medwards Date 2020-11-30 Time 09:04 Rev Time 0.00
Received By medwards Date 2020-11-30 Time 09:04 Sent To  
Notes
2020-11-30 09:04:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20111134
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THAT THIS BUILDING IS A WAREHOUSE. FROM
 THE SITE PLAN IT INDICATES THAT THIS EVENT WILL BE
 INDOORS. PLEASE PROVIDE THE ROOM SIZE AND THE OCCUPANCY
 COUNT FOR THE SPACE. ALSO PLEASE PROVIDE VENTILATION
 CALCULATIONS FOR THE ASSEMBLY OCCUPANCY. FBC M TABLE
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-12-03 Cont ID  
Sent By eschneid Date 2020-12-03 Time 10:01 Rev Time 0.25
Received By eschneid Date 2020-12-03 Time 10:01 Sent To  
Notes
***NONE***