Plan Review Details - Permit 20111124
Plan Review Stops For Permit 20111124
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-03-08 Cont ID  
Sent By rmcphers Date 2021-03-08 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2021-03-08 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By rmcphers Date 2020-12-15 Time 08:06 Rev Time 0.00
Received By rmcphers Date 2020-12-15 Time 08:04 Sent To  
Notes
2020-12-15 08:07:23LIGHT POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN DROP OFF THE ORIGINAL
 SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE FRONT DESK
 IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 13:17 Rev Time 0.00
Received By jleahy Date 2020-12-10 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 09:43 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 09:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-31 Cont ID  
Sent By equinone Date 2021-03-31 Time 08:01 Rev Time 0.00
Received By equinone Date 2021-02-16 Time 05:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-02-10 Cont ID  
Sent By cpuell Date 2021-02-10 Time 18:09 Rev Time 0.00
Received By cpuell Date 2020-11-25 Time 06:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 10:24 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 10:24 Sent To  
Notes
2021-10-25 10:27:24LIGHT POLE NOT BEING USED FOR THIS PROJECT. DOCUMENT
 CRYSTAL CONDO 22FT POLE SS.PDF IS LOCKED AND WILL NOT
 BE ISSUED WITH PERMIT. MPETERSON

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 09:38 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 09:38 Sent To  
Notes
2021-10-25 09:42:52THE LIGHT POLE ENGINEERING IN PROJECTDOX "SUPPORTING
 DOC" FOLDER SIGNED AND SEALED BY SHAWN ANDERSON P.E.
 STILL APPEARS AS A COPY OF A PAPER SIGNED AND SEALED
 DOCUMENT.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED
 DOCUMENT TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL
 (IF APPLICABLE) AND COMPLETE THE UPLOAD TASK IN
 PROJECTDOX, OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND
 SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO THE
 BUILDING DIVISION. SIGNATURE DOCUMENTS ARE TYPICALLY
 REVIEWED WITHIN TWO BUSINESS DAYS AFTER SUBMITTAL;
 DIGITALLY SIGNED DOCUMENTS ARE PREFERRED. '
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-08 Cont ID  
Sent By rmcphers Date 2021-03-08 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2021-03-08 Time 14:48 Sent To  
Notes
2021-03-08 14:52:19THE LIGHT POLE ENGINEERING IN PROJECTDOX "SUPPORTING
 DOC" FOLDER SIGNED AND SEALED BY SHAWN ANDERSON P.E.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC OR
 DIGITAL SIGNATURE ? YOU CAN MAIL IN OR DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DEPT. AT THE CITY HALL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-11 Cont ID  
Sent By jleahy Date 2020-12-11 Time 13:17 Rev Time 0.00
Received By jleahy Date 2020-12-11 Time 13:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-10-22 Cont ID  
Sent By llouie Date 2021-10-22 Time   Rev Time 0.00
Received By llouie Date 2021-10-22 Time   Sent To  
Notes
2021-10-22 14:08:50ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES, OR PUBLIC THOROUGHFARES.

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-30 Cont ID  
Sent By llouie Date 2021-03-30 Time   Rev Time 0.00
Received By llouie Date 2021-03-30 Time   Sent To  
Notes
2021-03-30 10:52:40** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SETBACK DISTANCE FROM THE LIGHT POLE FIXTURES TO
 THE PROPERTY LINES SHALL BE SHOWN IN THE SITE PLAN (IN
 ADDITION TO THE SITE PLAN EXHIBIT (SHEET SPE-1)).
 PLEASE NOTE THAT THE LIGHT POLE FIXTURES MUST BE
 SETBACK A MINIMUM OF 25 FT. FROM THE FRONT PROPERTY
 LINE; 5 FT. FROM THE SIDE AND REAR PROPERTY LINES. THE
 LIGHT FIXTURES DO NOT SEEM TO COMPLY WITH THE SETBACK
 REQUIREMENTS. AN ALTERNATIVE MAY BE TO PROVIDE LIGHTING
 ON THE BUILDING IF THE MINIMUM REQUIRED SETBACKS CANNOT
 BE MET. [ZLDR S.94-304(B)]
  
 2.) THE PHOTOMETRIC PLAN SHALL CONTAIN THE FOLLOWING
 NOTE: ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES, OR PUBLIC THOROUGHFARES. [ZLDR S.94-309(A)]
  
 3.) PROVIDED PLANS IN THE PERMIT ARE INCONSISTENT WITH
 THE PROPOSED CHANGES AS PART OF APPLICATION FSPR
 16-03B, SUBMITTED TO THE PLANNING DIVISION FOR A MINOR
 SITE PLAN AMENDMENT (PENDING REVIEW). PLANS SHALL BE
 CONSISTENT WITH THE PROPOSED CHANGES TO THE SITE.
  
 4.) APPROVAL OF FSPR 16-03B IS REQUIRED PRIOR TO THE
 APPROVAL OF THIS PERMIT.
  
  
 NOTES:
  
 * ANY CHANGES WHICH DEVIATE FROM THE PLANS APPROVED BY
 THE CITY COMMISSION WILL REQUIRE AN AMENDMENT TO THE
 OCPD (OFFICE COMMERCIAL PLANNED DEVELOPMENT). THE
 AMENDMENT WILL REQUIRE REVIEW AND APPROVAL BY THE
 PLANNING DIVISION PRIOR TO THE APPROVAL OF SUCH CHANGES
 FOR BUILDING PERMIT.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF32
  
 * REFERENCE: FSPR 16-03B (MINOR SITE PLAN AMENDMENT
 APPLICATION)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-02-10 Cont ID  
Sent By llouie Date 2021-02-10 Time   Rev Time 0.00
Received By llouie Date 2021-02-10 Time   Sent To  
Notes
2021-02-10 15:27:58** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DISTANCE FROM THE LIGHT POLE FIXTURES
 TO THE PROPERTY LINE. PLEASE NOTE THAT THE LIGHT POLES
 MUST BE SETBACK AT LEAST 5 FT. FROM THE PROPERTY
 LINE(S).
  
 2.) THE FOLLOWING NOTE SHALL BE PROVIDED IN THE PLAN
 FOR CONSISTENCY WITH THE LIGHTING REQUIREMENTS OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS): ALL
 OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE GLARE AND
 SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE AWAY FROM
 ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES
 OR PUBLIC THOROUGHFARES. [ZLDR S.94-309(A)]
  
  
 NOTES:
  
 MINOR SITE PLAN AMENDMENT REQUIRED FOR THE AS-BUILT
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 (C.O.).
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: MF20 (THE CRYSTAL)
  