Plan Review Details - Permit 20111096
Plan Review Stops For Permit 20111096
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 10:54 Rev Time 0.00
Received By cthroop Date 2020-11-25 Time 09:00 Sent To  
Notes
2020-11-25 11:01:12PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOT ENOUGH INFORMATION TO COMPLETE REVIEW. PROVIDE THE
 FOLLOWING INFORMATION AND RE-SUBMIT.
  
 APPLICANTION CHECKLIST
  
 1. PERMIT APPLICATION
 A. PROVIDE EVENT FUNCTION
  B. ADDRESS OF EVENT - PROVIDED
  C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS -
 PROVIDED
 D. OWNER AND CONTRACTOR INFO. - PROVIDED
  E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER -
 PROVIDED
  F. SPECIFY DATES OF INSTALLATION AND REMOVAL -
 PROVIDED
  
 2. SITE PLAN
  A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE?
  B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER
 FBC CHPT. 6, SEC. 602
  C. PROVIDE SQUARE FOOTAGE - PROVIDED
  D. PROVIDE ESTIMATED OCCUPANCY OF EACH TENT
  E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT
 ENTRANCE
  F. IDENTIFY MEANS OF EGRESS PER CHPT. 10
  G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE
 RESTROOMS
  H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500
 FEET OF TENT
  
 2. FOUNDATION/TIE DOWN - APPROVED
  
 3. CONFORMANCE PER SECTION 3103.1.1 INFORMATION ONLY
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC
 HEALTH, SAFETY AND GENERAL WELFARE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 16:17 Sent To  
Notes
2020-11-24 16:22:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) PLEASE PROVIDE A DETAILED SITE PLAN WITH SEPARATION
 DIMENSIONS TO ALL BUILDING WALLS.
  
  
 2) PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT THIS
 TENT WILL BE USED AS/FOR.
  
  
 3) PLEASE PROVIDE INDICATIONS OF ALL EXIT DOORS FROM
 THE BUILDING IN THE AREA OF WHERE THE TENT IS PROPOSED.
  
 THE TENT CAN NOT OBSTRUCT ANY EXIT OR RESTRICT PEOPLE
 FROM EXITING AWAY FROM THE BUILDING.
  
  
 4) PLEAE PROVIDE AND PROPOSED FLOOR PLAN, LIGHTING,
 EXIT LIGHTS, FIRE EXTINGUISHERS,
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 11:01 Rev Time 0.00
Received By cthroop Date 2020-11-24 Time 10:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 10:42 Rev Time 0.00
Received By cthroop Date 2020-11-25 Time 10:42 Sent To  
Notes
***NONE***