2020-12-02 09:35:21 | 12/02/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| EXISTING TANK-LESS GAS ON STRUCTURE, THERE WAS A PERMIT |
| IN 2007 FOR A 35 BTU?S HEATER IN SHED AND A 30 BTU?S |
| BBQ. A FULL EVALUATION OF ALL GAS EQUIPMENT WILL BE |
| NEEDED AT THIS TIME. PLEASE PROVIDE THE FOLLOWING ITEM. |
| |
| 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER THE 2017 FBC |
| RES. SECS. G2413.4.1, G2413.4.2. |
| |
| 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC. |
| G2420.4. |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER THE 2017 FBC FG SEC. 402.2 OR 2017 FBC |
| RES. SEC. G2413.2. |
| |
| 7. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR TANK-LESS ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FG |
| SEC.305.1 OR 2017 FBC RES. SEC. G2408.1. |
| |
| 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC RES. |
| SECS. G2413.3, G2413.4, AND TABLES G2413.4 (1) THROUGH |
| G2413.4 (21). |
| |
| 9. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE |
| GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS |
| LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| STANDARD THAT WERE USED IN THE DESIGN OF THIS SYSTEM |
| PER THE 2017 FBC RES. SEC. G2413.3. |
| |
| 10. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017 |
| FBC FG SEC 410.2. |
| |
| 11. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| THE 2017 FBC RES. SEC. G2401.1.3. |
| |
| 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR |
| APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 FBC |
| RES. SEC. G2419.2. |
| |
| 13. PLEASE REFER TO THE SPECIFICATION ON THE TANK-LESS |
| AS IT SHOWS A WINDOW ABOVE, GIVE THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 14. IF TANK-LESS REQUIRES CONDENSATE DRAIN IT BE 1' |
| AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5. |
| |
| 15. WATER PIPES NOT IN CONDITION SPACE NEED TO BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| 403.5.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |