Plan Review Details - Permit 20110999
Plan Review Stops For Permit 20110999
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 08:40 Rev Time 0.00
Received By medwards Date 2021-07-15 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-05-28 Cont ID  
Sent By medwards Date 2021-05-28 Time 07:47 Rev Time 0.00
Received By medwards Date 2021-04-20 Time 16:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-04-15 Cont ID  
Sent By medwards Date 2021-04-15 Time 10:42 Rev Time 0.00
Received By medwards Date 2021-04-07 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 08:40 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 09:25 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 09:25 Sent To  
Notes
2021-06-11 09:30:38THE DESIGNER OF THE DRAWINGS MUST PRINT AND SIGN THEIR
 NAME ON THE DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-05-28 Cont ID  
Sent By medwards Date 2021-05-28 Time 07:44 Rev Time 0.00
Received By medwards Date 2021-05-28 Time 07:17 Sent To  
Notes
2021-05-28 07:46:43THE DESIGNER OF THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS AND THE MECHANICAL DRAWING MUST HAVE THEIR
 NAME AND SIGNATURE ON THE DRAWINGS AND SIZING
 CALCULATIONS. THE DESIGNER MUST BE EITHER AN ENGINEER
 OR THE MECHANICAL CONTRACTOR HOLDING THE PERMIT TO
 INSTALL THIS EQUIPMENT AT THIS LOCATION.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-05-28 07:36:562ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20110999
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) EACH STRUCTURE MUST HAVE A SEPARATE PERMIT. FBC M
 107.2.1
  
 3) PLEASE IDENTIFY ALL DOCUMENTS TO CLEARLY SHOW WHICH
 STRUCTURE THE DOCUMENT IS ASSOCIATED WITH. FBC 107.2.1
  
 4) PLEASE SHOW THE CONDENSATE DRAIN PIPING AND LOCATION
 OF CONDENSATE DISPOSAL. FBC RES M1411.3
  
 5) PLEASE SHOW THE ANCHORING DETAILS FOR THE CONDENSING
 UNITS. FBC RES M1307.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By medwards Date 2021-04-15 Time 10:39 Rev Time 0.00
Received By medwards Date 2021-04-15 Time 10:39 Sent To  
Notes
2021-04-15 10:39:351ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110999
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) EACH STRUCTURE MUST HAVE A SEPARATE PERMIT. FBC M
 107.2.1
  
 3) PLEASE IDENTIFY ALL DOCUMENTS TO CLEARLY SHOW WHICH
 STRUCTURE THE DOCUMENT IS ASSOCIATED WITH. FBC 107.2.1
  
 4) PLEASE SHOW THE CONDENSATE DRAIN PIPING AND LOCATION
 OF CONDENSATE DISPOSAL. FBC RES M1411.3
  
 5) PLEASE SHOW THE ANCHORING DETAILS FOR THE CONDENSING
 UNITS. FBC RES M1307.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status N Date 2021-07-21 Cont ID  
Sent By medwards Date 2021-07-21 Time 08:40 Rev Time 0.00
Received By medwards Date 2021-07-21 Time 08:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2021-06-11 Cont ID  
Sent By medwards Date 2021-06-11 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-06-11 Time 09:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-05-28 Cont ID  
Sent By medwards Date 2021-05-28 Time 07:46 Rev Time 0.00
Received By medwards Date 2021-05-28 Time 07:46 Sent To  
Notes
2021-05-28 07:47:11PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-04-15 Cont ID  
Sent By medwards Date 2021-04-15 Time 10:39 Rev Time 0.00
Received By medwards Date 2021-04-15 Time 10:39 Sent To  
Notes
2021-04-15 10:42:24EACH DOCUMENT MUST HAVE EITHER THE ENGINEERS DIGITAL
 SIGNATURE OR THE MECHANICAL CONTRACTOR THAT HOLDS THE
 PERMITS TO INSTALL THIS PROJECT.
  
  FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  