Plan Review Details - Permit 20110996
Plan Review Stops For Permit 20110996
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-21 Cont ID  
Sent By cthroop Date 2021-01-21 Time 16:30 Rev Time 0.00
Received By cthroop Date 2021-01-21 Time 16:25 Sent To  
Notes
2021-01-21 16:31:53PROVISO: TENT SHALL BE REMOVED IF WINDS ARE EXPECTED TO
 EXCEED 30 MPH PER ROBERT BROWN, BUILDING OFFICIAL. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-21 Cont ID  
Sent By cthroop Date 2020-11-21 Time 07:08 Rev Time 0.00
Received By cthroop Date 2020-11-21 Time 06:20 Sent To  
Notes
2020-11-21 07:38:02PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ADDITIONAL INFORMATION IS REQUIRED FOR A THOUROUGH
 REVIEW.
  
 GENERAL REQUIREMENTS PER FBC CHPT 1 AND CHPT 31,
 TEMPORARY MEMBRANE STRUCTURES
  
 1. TEMPORARY STRUCTURES SHALL NOT EXCEED 6 MONTHS.
 PROVIDE DATE OF INSTALLATION AND DATE OF REMOVAL. FBC
 CHPT 1 SEC. 108.
  
 2. CONFORMANCE STANDARDS.
 108.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 3. IDENTIFY LOCATION OF ACCESSIBLE RESTROOMS ON SITE
 PLAN. ACCESSIBLE PATH OF TRAVEL NOT TO EXCEED 500 FEET.
  
 4. TENTS 30 FEET OR MORE IN ANY DIRECTION.
 PROVIDE ENGINEERED DESIGN SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OR PROVIDE STATEMENT ON PLAN "TENT WILL BE
 REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH".
  
 5. IF TENT IS A CLOSED STRUCTURE, (SIDEWALLS)
 ADDITIONAL INFORMATION REQUIRED PER FBC CHPT 10.
  
 1. OCCUPANCY LOAD.
 2. POSTING OF OCCUPANT LOAD.
 3. MEANS OF EGRESS.
 4. EMERGENCY LIGHTING.
 5. POWER SOURCE FOR ILLUMINATION.
 6. ACCESSIBLE PATH OF TRAVEL.
 7. EXIT SIGN.
 8. NUMBER OF EXISTS.
  
 6. TWO DIFFERENT SEATING ARRANGEMENTS ARE PROVIDE IN
 ROOF TOP TT ENGINEERING PLAN. IDENTIFY WHICH SEATING
 PLAN WILL BE USED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-23 Cont ID  
Sent By pleduc Date 2020-11-23 Time   Rev Time 0.00
Received By pleduc Date 2020-11-23 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-23 Cont ID  
Sent By cthroop Date 2020-11-23 Time 15:30 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 15:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-11-21 Cont ID  
Sent By cthroop Date 2020-11-21 Time 06:54 Rev Time 0.00
Received By cthroop Date 2020-11-21 Time 06:21 Sent To  
Notes
2020-11-21 06:56:12OPTION TO ENGINEERED DESIGN - PROVIDE STATEMENT ON PLAN
 "TENT WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED
 30 MPH".