Plan Review Details - Permit 20110979
Plan Review Stops For Permit 20110979
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 10:10 Rev Time 0.00
Received By cthroop Date 2021-03-18 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-02-22 Cont ID  
Sent By chtroop Date 2021-02-22 Time 09:51 Rev Time 0.00
Received By cthroop Date 2021-02-22 Time 09:08 Sent To  
Notes
2021-02-22 09:53:04PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. COMPLETE.
  
 2. PROVIDE SITE SPECIFIC WIND LOAD DESIGN PRESSURES PER
 PAD DESIGN REQUIREMENTS.
  
 FBC 107.3.5.3 PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-28 Cont ID  
Sent By cthroop Date 2020-11-28 Time 14:20 Rev Time 0.00
Received By cthroop Date 2020-11-28 Time 14:04 Sent To  
Notes
2020-11-28 14:23:43PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE COPLETE SET OF GENERATOR SPECIFICATIONS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE SITE SPECIFIC WIND LOAD DESIGN PRESSURES PER
 PAD DESIGN REQUIREMENTS.
  
 FBC 107.3.5.3 PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-28 Cont ID  
Sent By cthroop Date 2020-11-28 Time 14:10 Rev Time 0.00
Received By cthroop Date 2020-11-28 Time 14:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By chtroop Date 2021-02-22 Time 09:50 Rev Time 0.00
Received By cthroop Date 2021-02-22 Time 09:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 14:51 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 13:36 Sent To  
Notes
2020-12-02 15:15:56PLAN REVIEW / PLUMBING / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1- A SEARCH OF CITY RECORDS INDICATES THERE IS NO
 RECORD OF A PERMIT FOR THE INSTALLATION OF GAS
 APPLIANCES AT THIS ADDRESS. THE EXISTING GAS LINES
 SHALL BE CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 2 -SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
 2A) PROVIDE AN ISO DRAWING SHOWING THE ENTIRE SYSTEM
 INCLUDING ALL BRANCH PIPES FROM THE METER TO THE MOST
 REMOTE OUTLET. THE BTUH LOAD OF EACH EXISTING APPLIANCE
 AND THE LOCATIONS OF REGULATORS SHALL BE INDICATED ON
 THE DRAWING- SECTIONS G2412.3 & G2412.4 FBC RES.
 NOTE: EXCEPTION PER TIM LARGE CHIEF PLUMBING INSPECTOR
 - IF IT IS NOT POSSIBLE TO GAIN ACCESS TO THE DWELLING
 UNIT YOU MAY ESTIMATE THE TOTAL BTUH OF THE EXISTING
 APPLIANCES.
  
 3- SUBMIT GAS REGULATOR SPECIFICATIONS. SUBMIT SPECS
 FOR THE REGULATOR AT THE GENERATOR WITH MARKUPS TO
 INDICATE WHICH MODEL TO BE INSTALLED, INLET AND OUTLET
 PRESSURES, AND ORIFICE SIZE- SECTION G2421.1.2017 FBC
 FUEL GAS SEC.305.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
  
 4- SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF ALL GAS APPLIANCES. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5- SUBMIT THE SIZING TABLES USED IN THE DESIGN FOR THE
 GAS SYSTEM. 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 10:10 Rev Time 0.00
Received By cthroop Date 2021-02-26 Time 10:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-02-22 Cont ID  
Sent By cthroop Date 2021-02-22 Time 09:53 Rev Time 0.00
Received By cthroop Date 2021-02-03 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-14 Cont ID  
Sent By lmarchan Date 2021-01-14 Time 16:10 Rev Time 0.00
Received By lmarchan Date 2020-11-20 Time 16:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-22 Cont ID  
Sent By cthroop Date 2021-02-22 Time 09:07 Rev Time 0.00
Received By cthroop Date 2021-02-22 Time 09:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-02 Cont ID  
Sent By cthroop Date 2020-12-02 Time 14:18 Rev Time 0.00
Received By cthroop Date 2020-12-02 Time 13:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-18 Cont ID  
Sent By cthroop Date 2021-03-18 Time 10:10 Rev Time 0.00
Received By cthroop Date 2021-03-18 Time 09:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-22 Cont ID  
Sent By cthroop Date 2021-02-22 Time 09:50 Rev Time 0.00
Received By cthroop Date 2021-02-22 Time 09:08 Sent To  
Notes
2021-02-22 09:51:10PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONCRETE PAD DESIGN
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-28 Cont ID  
Sent By cthroop Date 2020-11-28 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-11-28 Time 14:04 Sent To  
Notes
2020-11-28 14:20:30PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONCRETE PAD DESIGN
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-01-11 Cont ID  
Sent By kalexand Date 2021-01-11 Time 12:45 Rev Time 0.00
Received By kalexand Date 2021-01-11 Time 12:45 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved