| 1ST REVIEW |
| DATE: TUES. NOV. 24TH/ 2020 |
| ACTION: DENIED |
| |
| 1) ON BOTH THE D1 SHEET AND A1 SHEET THE PLANS SHOW |
| WORK TO BE COMPLETED IN THE COMMON AREA. THERE IS A |
| NOTE THAT STATES ALL COST ASSOCIATED WITH THIS WORK TO |
| BE SEPARATELY PRICED. PLEASE NOTE WORK IN THE COMMON |
| AREAS ARE USUALLY OUT OF THE LEASE LINES, CONSIDERED |
| COMMON AREAS AND UNDER SEPARATE PERMIT. PLEASE NOTE THE |
| WORK CAN BE SHOWN ON THIS PLAN PUT THEN NEITHER PERMIT |
| CAN BE ISSUED UNTIL BOTH PERMITS ARE CODE COMPLIANT. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1 PERMITS. |
| |
| 2) SHEET A-3 SHOWS THE DOOR SCHEDULE 22 OF THE 34 DOORS |
| SHOWN STATE THAT THEY ARE EXISTING AND DO NOT PROVIDE |
| THE WIDTH OF THE DOOR. THE EXISTING DOOR SIZE NEEDS TO |
| BE KNOWN TO SEE IF THEY MEET THE EGRESS REQUIREMENTS |
| AND ACCESSIBILITY MINIMUM WIDTHS. |
| 2017 ACCESS. CODE 404.2.3. CLEAR WIDTH & SIZE OF DOORS, |
| 2017 FBC-B 1010.1.1. WHERE THIS SECTION REQUIRES A |
| MINIMUM CLEAR WIDTH OF 32 INCHES. THE MINIMUM SIZE OF A |
| SWING DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY |
| WITH THE SWINGING DOORS SHALL BE MEASURED BETWEEN THE |
| FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| DEGREES. |
| THE PERMIT APPLICATION INDICATES THE PERMIT VALUE FOR |
| THE WORK TO BE ACCOMPLISHED UNDER THIS PERMIT IS |
| $68,000.00 DOLLARS OF VALUE. PLEASE REVIEW HOW YOU ARE |
| TO MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR |
| THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW |
| HOW THEY ARE GOING TO SPEND UP TO THE 20% |
| DISPROPORTIONATE FUNDS LISTED ($13,600.00 DOLLARS) FOR |
| EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE |
| ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST |
| OF THE 2017 ACCESSIBILITY CODE. IF CODE COMPLIANCE IS |
| MET BEFORE THE VALUE OF WORK $13,600.00 NOTE THE BIG |
| QUESTION IS THE DOORS.IS SPENT THEN NO MORE FUNDS NEED |
| TO BE SPENT FOR ACCESSIBILITY UPGRADES. |
| |
| 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO |
| PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED |
| AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL |
| ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE |
| ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY |
| BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST |
| ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN |
| ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST |
| ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS |
| INSTALLING GRAB BARS, ENLARGING TOILET STALLS, |
| INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET |
| CONTROLS; (III) COST ASSOCIATED WITH PROVIDING |
| ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE |
| TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION |
| DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV) |
| COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING |
| FOUNTAIN. |
| |
| 3) PLEASE NOTE BOTH THE D1 SHEET AND A1 SHEET BOTH SHOW |
| WORK IN THE EXISTING PRIVATE BATHROOM. 2017 EXISTING |
| BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION |
| ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| BUILDING AS WELL AS THE ACCESSIBILITY CODE. CURRENTLY |
| THIS BATHROOM DOES NOT MEET ANY OF THE ACCESSIBLE |
| ELEMENTS OF CHAPTER 6 OF THE ACCESSIBILITY CODE. MUST |
| MEET THE REQUIREMENTS FOR SIZE OF THE RESTROOM AND |
| BACKING REQUIREMENTS WHICH CURRENTLY IT DOES NOT MEET |
| EVEN FOR THE PRIVATE BATHROOM. PLUMBING WILL PROVIDE |
| MORE DETAIL ON HOW THEY VIEW A REMODELED PRIVATE |
| BATHROOM. |
| |
| 4) SHEET A1 RESTROOMS 124, 130, 131, AND PRIVATE |
| BATHROOM 107, NONE ARE DIMENSIONED AS TO VERIFY CODE |
| COMPLIANCE WITH CLEARANCES AT WATER CLOSETS. 604.3 |
| CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS AND IN |
| TOILET COMPARTMENTS SHALL COMPLY WITH 604.3 OF THE 2017 |
| FBC-ACCESSIBILITY CODE. |
| 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR |
| WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE |
| 7-FOOT 1 INCH. |
| |
| 5) SHEET A-3 ACCESSIBLE DETAILS: |
| 5A) GRAB BARS ARE DIMENSIONED TO CENTERLINE NOT THE TOP |
| OF THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY CODE |
| SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE. |
| |
| 5B) LAV & SINK DETAILS. EXPOSED PIPES. 606.5 EXPOSED |
| PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER |
| LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE |
| CONFIGURED TO PROTECT AGAINST CONTACT. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |