Plan Review Details - Permit 20110928
Plan Review Stops For Permit 20110928
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-01-13 Cont ID  
Sent By jwitmer Date 2021-01-13 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2021-01-13 Time 10:15 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-01-09 Cont ID  
Sent By jwitmer Date 2021-01-09 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-01-09 Time 15:15 Sent To  
Notes
2021-01-09 15:45:01COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 17:42 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 16:00 Sent To  
Notes
2021-01-05 17:40:40COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING: THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By jwitmer Date 2020-11-24 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2020-11-24 Time 13:47 Sent To  
Notes
2020-11-24 15:00:46TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-01-13 Cont ID  
Sent By jwitmer Date 2021-01-13 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2021-01-13 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-09 Cont ID  
Sent By jwitmer Date 2021-01-09 Time 15:42 Rev Time 0.00
Received By jwitmer Date 2021-01-09 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 17:43 Rev Time 0.00
Received By jwitmer Date 2021-01-05 Time 16:00 Sent To  
Notes
2021-01-05 17:39:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:20110928
 ADD: 2505 METROCENTRE BLVD. W. # 300
 CONT: CHANDLER CONSTRUCTION CO.
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JAN. 05/2021
 ACTION: DENIED
  
 1-5) COMPLIED.
 .
 6) NEW COMMENT.
  
 6A) DISCREPANCY IN IDENTIFYING DOOR JUST IN FRONT OF
 THE WOMEN?S RESTROOM 132. SHEET A-1 LABELS THE DOOR
 EITHER ( O ) OR 3, ON THE LIFE SAFETY PLAN THE SAME
 DOOR IS LABELED AS ( C ). DISCREPANCY IN PLANS.
 107.2.1.2.ADDITIONAL INFORMATION IS REQUIRED.
  
 6B) THIS SAME DOOR SHOWS DIFFERENT DOOR SWINGS
 DEPENDING ON THE PLAN. THE COVERSHEET AND LS-1 SHEET
 THE DOOR SWINGS ONE WAY AND THE OTHER SHEET A-1 THE
 DOOR SWINGS INTO A DIFFERENT CORRIDOR BLOCKING THE
 REQUIRED EGRESS FOR THAT CORRIDOR. SECTION 1005.7.1 OF
 THE 2017 FBC-B STATES DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED WIDTH OF MORE THAN ONE HALF THE
 REQUIRED WIDTH OF THE CORRIDOR. WHEN CALIBRATING THE
 MEASURING TOOL IN PROJECT DOX THERE IS ONLY 1 FOOT FROM
 THE CORNER OF THE WALL TO THE DOOR WING DURING THE
 TRAVEL OF THE DOOR IN THE RADIUS. FOR OCCUPANT LOADS
 LESS THAN 50 THE MINIMUM CORRIDOR WIDTH OF 36 INCHES
 WOULD REQUIRE A CLEAR MEASUREMENT OF 18 INCHES. THE
 MINIMUM CORRIDOR WIDTH IS 44 INCHES FOR OCCUPANT LOADS
 50 OR MORE FOR A BUSINESS OCCUPANCY THE MINIMUM CLEAR
 WIDTH UNOBSTRUCTED WOULD BE 22 INCHES FOR DOOR SWINGS.
 SEE TABLE 1020.2 OF THE 2017 FBC-B.
  
 6C) THE DESIGNER OF RECORD QUESTIONS THE OCCUPANT LOAD
 CALCULATIONS AND REFENCE SPEAKING WITH R. GATHRIGHT FOR
 BREAKROOMS. WE HAVE TO LOOK AT THIS ON A CASE BY CASE
 BASIS, NOT A BLANKET STATEMENT. THE ISSUE THAT HAS TO
 BE DETERMINED IS THE OTHER ASSEMBLY AREAS ON THE TOTAL
 FLOOR PLATE, NOT JUST THE TENANT SPACE IN QUESTION
 WHERE THE ASSEMBLY AREA WOULD BE OVER 10 % OF THE FLOOR
 AREA FOR THE ENTIRE FLOOR, IF SO THEN THE FLOOR IS
 CONSIDERED A MIXED OCCUPANCY BETWEEN BUSINESS AND
 ASSEMBLY. PLEASE REVIEW 508.2.3. AGGREGATE ACCESSORY
 OCCUPANCIES OF THE 2017 FBC-B. ONCE THIS IS COMPLETED
 WE WOULD KNOW THE TOTAL OCCUPANT LOAD FOR THIS TENANT
 SPACE AND DOOR SWING, OCCUPANT LOADS OF 50 OR MORE ARE
 REQUIRED TO SWING IN THE DIRECTION OF EGRESS TRAVEL
 2017 FBC-BUILDING SECTION 1010.1.2.1.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By jwitmer Date 2020-11-24 Time 14:59 Rev Time 0.00
Received By jwitmer Date 2020-11-24 Time 13:46 Sent To  
Notes
2020-11-24 14:59:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT:20110928
 ADD: 2505 METROCENTRE BLVD. W. # 300
 CONT: CHANDLER CONSTRUCTION CO.
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 24TH/ 2020
 ACTION: DENIED
  
 1) ON BOTH THE D1 SHEET AND A1 SHEET THE PLANS SHOW
 WORK TO BE COMPLETED IN THE COMMON AREA. THERE IS A
 NOTE THAT STATES ALL COST ASSOCIATED WITH THIS WORK TO
 BE SEPARATELY PRICED. PLEASE NOTE WORK IN THE COMMON
 AREAS ARE USUALLY OUT OF THE LEASE LINES, CONSIDERED
 COMMON AREAS AND UNDER SEPARATE PERMIT. PLEASE NOTE THE
 WORK CAN BE SHOWN ON THIS PLAN PUT THEN NEITHER PERMIT
 CAN BE ISSUED UNTIL BOTH PERMITS ARE CODE COMPLIANT.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1 PERMITS.
  
 2) SHEET A-3 SHOWS THE DOOR SCHEDULE 22 OF THE 34 DOORS
 SHOWN STATE THAT THEY ARE EXISTING AND DO NOT PROVIDE
 THE WIDTH OF THE DOOR. THE EXISTING DOOR SIZE NEEDS TO
 BE KNOWN TO SEE IF THEY MEET THE EGRESS REQUIREMENTS
 AND ACCESSIBILITY MINIMUM WIDTHS.
 2017 ACCESS. CODE 404.2.3. CLEAR WIDTH & SIZE OF DOORS,
 2017 FBC-B 1010.1.1. WHERE THIS SECTION REQUIRES A
 MINIMUM CLEAR WIDTH OF 32 INCHES. THE MINIMUM SIZE OF A
 SWING DOORS IS MEASURED CLEAR OPENING OF THE DOORWAY
 WITH THE SWINGING DOORS SHALL BE MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
 THE PERMIT APPLICATION INDICATES THE PERMIT VALUE FOR
 THE WORK TO BE ACCOMPLISHED UNDER THIS PERMIT IS
 $68,000.00 DOLLARS OF VALUE. PLEASE REVIEW HOW YOU ARE
 TO MEET DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 THE DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW
 HOW THEY ARE GOING TO SPEND UP TO THE 20%
 DISPROPORTIONATE FUNDS LISTED ($13,600.00 DOLLARS) FOR
 EACH ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2017 ACCESSIBILITY CODE. IF CODE COMPLIANCE IS
 MET BEFORE THE VALUE OF WORK $13,600.00 NOTE THE BIG
 QUESTION IS THE DOORS.IS SPENT THEN NO MORE FUNDS NEED
 TO BE SPENT FOR ACCESSIBILITY UPGRADES.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COST ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COST ASSOCIATED WITH RELOCATING AN ACCESSIBLE DRINKING
 FOUNTAIN.
  
 3) PLEASE NOTE BOTH THE D1 SHEET AND A1 SHEET BOTH SHOW
 WORK IN THE EXISTING PRIVATE BATHROOM. 2017 EXISTING
 BUILDING CODE. 801.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING AS WELL AS THE ACCESSIBILITY CODE. CURRENTLY
 THIS BATHROOM DOES NOT MEET ANY OF THE ACCESSIBLE
 ELEMENTS OF CHAPTER 6 OF THE ACCESSIBILITY CODE. MUST
 MEET THE REQUIREMENTS FOR SIZE OF THE RESTROOM AND
 BACKING REQUIREMENTS WHICH CURRENTLY IT DOES NOT MEET
 EVEN FOR THE PRIVATE BATHROOM. PLUMBING WILL PROVIDE
 MORE DETAIL ON HOW THEY VIEW A REMODELED PRIVATE
 BATHROOM.
  
 4) SHEET A1 RESTROOMS 124, 130, 131, AND PRIVATE
 BATHROOM 107, NONE ARE DIMENSIONED AS TO VERIFY CODE
 COMPLIANCE WITH CLEARANCES AT WATER CLOSETS. 604.3
 CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS AND IN
 TOILET COMPARTMENTS SHALL COMPLY WITH 604.3 OF THE 2017
 FBC-ACCESSIBILITY CODE.
 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR
 WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE
 7-FOOT 1 INCH.
  
 5) SHEET A-3 ACCESSIBLE DETAILS:
 5A) GRAB BARS ARE DIMENSIONED TO CENTERLINE NOT THE TOP
 OF THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY CODE
 SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE, NOT CENTERLINE.
  
 5B) LAV & SINK DETAILS. EXPOSED PIPES. 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 15:26 Rev Time 0.00
Received By equinone Date 2020-12-04 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-01-08 Cont ID  
Sent By pleduc Date 2021-01-08 Time   Rev Time 0.00
Received By pleduc Date 2021-01-08 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-12-21 Cont ID  
Sent By pleduc Date 2020-12-21 Time   Rev Time 0.00
Received By pleduc Date 2020-12-21 Time 11:07 Sent To  
Notes
2020-12-21 11:43:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) UNFORTUNATLEY, ON REVIEW OF THE REVISED SUBMITTAL,
 THE PROPOSED INDICATES A DOOR SWINGING AGAINST EGRESS.
  
 PER NFPA 101, CH 39 EXIISTING BUSINESS OCCUPANCIES
  
 39.2.2.2 DOORS.
 39.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
  
 39.2.4 NUMBER OF MEANS OF EGRESS.
 39.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE
 FOLLOWING,
 EXCEPT AS OTHERWISE PERMITTED BY 39.2.4.2 THROUGH
 39.2.4.6:
 (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH
 7.4.1.1 AND 7.4.1.3 THROUGH 7.4.1.6.
 (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED
 ON EVERY
 STORY.
 (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE
 ACCESSIBLE FROM
 EVERY PART OF EVERY STORY.
  
 IT APPEARS THAT YOUR OCCCUPANCY DOESS NOT MEET THE
 SINGLE EXIT REQUIREMENTS AND THIS EXIT DOOR IS
 REQUIRED.
  
 PER CH 7, MEANS OF EGRESS:
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 AS PER MY PREVIOUS COMMENT, THE DOOR CAN BE FULL SWING
 BUT IS REQUIRED TO SWING OUT INTO THE HALLWAY/CORRIDOR.
  
 PLEASE REVIEW AND CORRECT.
  
 1A) FYI - SHEET LS - 1, DOES NOT SHOW ANY CHANGE,
  
 PLEASE ENSURE THE LIFE SAFETY PLAN INDICATES THE
 APPLICABLE CHANGE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-11-24 Cont ID  
Sent By pleduc Date 2020-11-24 Time   Rev Time 0.00
Received By pleduc Date 2020-11-24 Time 15:51 Sent To  
Notes
2020-11-24 16:10:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS - 1 - DOOR # 3 OPENS OUT INTO THE CORRIDOR,
 HOWEVER, IT OPENS AND RESTRICTS THE EGRESS FROM THE ADA
 WOMENS TOILET.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN.
  
  
 THOUGH THIS MAY BE AN EXISTING CONDITION, IT IS
 REQUIRED TO BE CORRECTED.
  
 A RH180 DEGREE DOOR SWING OUT INTO THE CORRIDOR MAY BE
 A CONSIDERATION.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-01-13 Time 10:28 Rev Time 0.00
Received By lmarchan Date 2021-01-11 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-09 Cont ID  
Sent By jwitmer Date 2021-01-09 Time 15:45 Rev Time 0.00
Received By jwitmer Date 2021-01-07 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 17:43 Rev Time 0.00
Received By jwitmer Date 2020-12-18 Time 12:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-04 Cont ID  
Sent By equinone Date 2020-12-04 Time 15:27 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-11-27 Cont ID  
Sent By medwards Date 2020-11-27 Time 09:33 Rev Time 0.00
Received By medwards Date 2020-11-27 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-30 Cont ID  
Sent By ccole Date 2020-12-30 Time 09:04 Rev Time 0.00
Received By ccole Date 2020-12-30 Time 08:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-03 Cont ID  
Sent By ccole Date 2020-12-03 Time 16:50 Rev Time 0.00
Received By ccole Date 2020-12-03 Time 15:44 Sent To  
Notes
2020-12-03 16:51:091ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110928
 12/3/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PROVIDE PLUMBING FIXTURE CALCULATIONS AND
 A SCHEDULE SHOWING THE REQUIRED AND PROVIDED FIXTURES
 IN COMPLIANCE WITH TABLE 403.3 FBC P. PLEASE NOTE THAT
 TWO MALE AND TWO FEMALE WATER CLOSETS ARE REQUIRED FOR
 THE B OCCUPANCY WITH 53 OCCUPANTS. THE PLAN SHOWS
 NON-COMPLIANCE.
  
 2) A1: PROVIDE TOILET ROOM LENGTH AND WIDTH DIMENSIONS-
 SECTION 107.2.1 WPB.
  
 3) A1: SHOW THE CLEAR FLOOR DIAGRAM AND DIMENSIONS AT
 THE NEW BREAKROOM SINK- SECTION 305.3 FBC ACC.
  
 4) A3: SHOW THE HEIGHTS OF THE WATER CLOSETS FROM THE
 FINISHED FLOORS TO THE TOPS OF THE SEATS- SECTION 604.4
 FBC ACC.
  
 5) A3: SHOW THE HEIGHTS OF THE GRAB BARS FROM THE
 FINISHED FLOORS TO THE TOPS OF THE GRIPPING SURFACES-
 SECTION 609.4 FBC ACC.
  
 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-05 Cont ID  
Sent By jwitmer Date 2021-01-05 Time 17:42 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-27 Cont ID  
Sent By medwards Date 2020-11-27 Time 09:38 Rev Time 0.00
Received By medwards Date 2020-11-27 Time 09:38 Sent To  
Notes
***NONE***