2021-04-23 09:21:02 | 1ST REVIEW FBC-2017 RES. |
| PERMIT- 20110913 |
| 4/23/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS |
| |
| PLAN REVIEW RESULTS: DENIED. |
| PLEASE NOTE THE PLANS FOR THE POOL ARE COPIES OF |
| DIGITALLY SIGNED AND SEALED PLANS THAT WERE SCANNED |
| INTO THE SYSTEM FOR REVIEW. AS A RESULT, SOME OF THE |
| PRINT AND DETAILS ON THE PLANS ARE NOT LEGIBLE. A |
| COMPLETE REVIEW WILL DEPEND ON RESUBMITTAL OF DIGITALLY |
| SIGNED AND SEALED AND ELECTRONICALLY TRANSMITTED PLANS. |
| PLEAE COMPLY WITH PRELIMINARY COMMENTS BELOW. |
| |
| 1) SHEET 1: THE POOL EQUIPMENT SCHEDULE DOES NOT |
| INCLUDE THE RAYPACK POOL HEATER- SECTION 107.2.1 WPB. |
| PLEASE UPDATE THE SCHEDULE TO INDICATE THE SELECTED |
| MODEL AS INDICATED IN THE SUBMITTED PRODUCT SPECS- |
| SECTION R4501.14 FBC RES. |
| |
| 2) SHEET 1 SPECIFICATIONS: PLEASE PROVIDE THE POOL |
| TURNOVER RATE IN COMPLIANCE WITH SECTION 9.1.3 |
| ANSI/APSP/ICC-5 2011. |
| |
| 3) SHEETS 1 & 3: PROVIDE THE WATER VELOCITY OF THE |
| SUCTION AND PRESSURE PIPING- SECTION 9.2 |
| ANSI/APSP/ICC-5 2011, AND SECTION R4501.6.3 FBC RES. |
| |
| 4) SHEET 3: PROVIDE A COMPLETE TDH CALCULATION THAT |
| INCLUDES THE POOL HEATER AND SUBMIT THE WORKSHEET. |
| SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM |
| SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP |
| CURVE AND THE SIMPLIFIED TOTAL DYNAMIC HEAD CALCULATION |
| IS NO LONGER ALLOWED TO BE USED IN DETERMINING MAXIMUM |
| SYSTEM FLOW RATE PER ANSI/APSP/ICC 7- 2013 SECS. 4.4.9, |
| 4.4.9.1. THE 2013 EDITION ADDRESSES FLOW RATE IN |
| GALLONS PER MINUTE (GPM). IT REQUIRES THAT MAXIMUM |
| SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM |
| FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN |
| COVER). THE TDH CALCULATIONS MUST INCLUDE ALL OF THE |
| SYSTEM COMPONENTS INCLUDING SUCTION AND RETURN PIPING, |
| FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| SYSTEM COMPONENTS EXCEPT THE PUMP. |
| |
| 5) SHEET 3: THE MODEL NUMBER OF THE PUMP IN THE TABLE |
| AND IN THE CURVE IS NOT LEGIBLE. PROVIDE A LEGIBLE |
| CURVE THAT IDENTIFIES ON THE CURVE KEY THE SELECTED |
| PUMP TO BE INSTALLED ON THIS POOL. THIS IS NEEDED TO |
| CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH |
| CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, |
| 4.4.9.1. |
| |
| 6) SHEETS 1 & 3: INDICATE HOW WATER BE SUPPLIED TO THE |
| POOL. PLEASE NOTE IF AN AUTOFILL IS TO BE INSTALLED A |
| BACKFLOW DEVICE SHALL BE INSTALLED AT THE AUTOFILL, AND |
| A REDUCED PRESSURE BACKFLOW DEVICE SHALL BE INSTALLED |
| AT THE METER UNDER A SEPARATE PERMIT- SECTION R4501.10 |
| FBC RES. |
| NOTE: A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| 7) SHEETS 1 & 3: PROVIDE POOL PIPING TEST CRITERIA- |
| SECTION R4501.12.1 FBC RES. PLEASE NOTE THAT AIR TESTS |
| ARE PROHIBITED FOR PVC PIPING- SECTION 312.1 FBC P. |
| |
| 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PUMP, |
| FILTER, AND MAIN DRAIN COVER- SECTION R4501.6.2 FBC |
| RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |