Plan Review Details - Permit 20110867
Plan Review Stops For Permit 20110867
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 11:12 Rev Time 0.00
Received By ccole Date 2021-02-05 Time 09:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 10:38 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 08:54 Sent To  
Notes
2020-12-15 10:38:501ST REVIEW FBC-2017 RES. FUEL GAS
 PERMIT- 20120071
 12/15/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A GAS RISER DRAWING- SECTION 107.3.5.3 WPB.
 THE RISER SHALL PROVIDE THE FOLLOWING INFORMATION:
  
 A) DELIVERY PRESSURE AT THE METER- SECTIONS G2413.1 FBC
 RES.
  
 B) TOTAL DEVELOPED LENGTH OF THE PIPING FROM THE METER
 TO THE MOST REMOTE GAS OUTLET- SECTION G2413.4.1.
  
 D) BRANCH AND CUT PIPING LENGTHS- SECTION G2413.4.2.
  
 E) INDIVIDUAL GAS LOADS AT OUTLETS AND TOTAL LOAD OF
 THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC
 RES.
  
 F) LOCATIONS OF REGULATORS AND OUTLET PRESSURES-
 SECTIONS G2421.1 & G2421.2.
  
 G) PIPE SIZING TABLES- SECTION G2413.3.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS AND RANGE SHOWING THE BTUH LOAD CAPACITIES AND
 INLET PRESSURES- SECTIONS G2447.1 & G2448.1 FBC RES.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS MARKED OR HIGHLIGHTED TO SHOW THE SELECTED
 MODELS, INLET AND OUTLET PIPE SIZES AND PRESSURES, AND
 ORIFICE SIZES- SECTIONS G2421.1 & G2421.2 FBC RES.
  
 4) SHEET GP-2: PLEASE SHOW THE CLEARANCE DISTANCE FROM
 THE WATER HEATER VENT OPENINGS TO THE WINDOW- SECTIONS
 G2427.8 & G2448.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-02-05 Time   Rev Time 0.00
Received By ccarvaja Date 2021-02-02 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-12-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 09:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 10:21 Rev Time 0.00
Received By ccole Date 2021-02-05 Time 09:41 Sent To  
Notes
2021-02-05 10:21:59PLUMBING FOR WATER HEATERS UNDER MASTER PERMIT-
 20010033 AND SUB- 20010037.
 CCOLE
 2/5/21

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 10:40 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 08:53 Sent To  
Notes
2020-12-15 10:42:47PLUMBING FOR WATER HEATERS UNDER MASTER PERMIT-
 20010033 AND SUB- 20010037.
 CCOLE
 12/15/20

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-02-05 Cont ID  
Sent By ccole Date 2021-02-05 Time 10:22 Rev Time 0.00
Received By ccole Date 2021-02-05 Time 09:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By ccole Date 2020-12-15 Time 10:59 Rev Time 0.00
Received By ccole Date 2020-12-15 Time 08:54 Sent To  
Notes
2020-12-15 11:06:02SIGNATURE REVIEW
 12/15/2020
  
 1) THE DIGITALLY SIGNED AND SEALED PLANS SHALL ALSO
 BEAR THIS STATEMENT IN ACCORDANCE WITH SECTION
 61G15-23.005- "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED
 AND SEALED BY _________ON DATE________USING A SHA-1
 AUTHENTICATION CODE." PLEASE NOTE THAT ENGINEERS MAY
 NOT SELF-CERTIFY ELECTRONIC SIGNATURES AND SEALS.
 ELECTRONIC SIGNATURES AND SEALS SHALL BE VERIFIED BY A
 CERTIFICATION AUTHORITY PER SECTION 61G15-23.004(2).
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  