Plan Review Details - Permit 20110767
Plan Review Stops For Permit 20110767
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-03 Cont ID  
Sent By rmcdouga Date 2020-12-03 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2020-12-03 Time 09:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By rmcdouga Date 2020-11-19 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-11-19 Time 16:23 Sent To  
Notes
2020-11-19 16:24:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SOUND TESTING THAT WAS SUBMITTED WAS TESTED WITH
 A SUSPENDED CEILING BELOW THE SLAB. THE TEST IS
 REQUIRED TO MATCH THE CONDITIONS AT THE SITE. FBC
 107.2.1
  
 2) SUBMIT THE TEST FOR FLAME SPREAD AND SMOKE
 DEVELOPED. FBC 107.2.1
  
 THE REQUIRED TESTS ARE:
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-03 Cont ID  
Sent By rmcdouga Date 2020-12-03 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2020-11-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By rmcdouga Date 2020-11-19 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2020-11-17 Time 16:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-11-19 Cont ID  
Sent By rmcdouga Date 2020-11-19 Time 16:23 Rev Time 0.00
Received By rmcdouga Date 2020-11-19 Time 16:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved