Plan Review Details - Permit 20110707
Plan Review Stops For Permit 20110707
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2021-03-23 Cont ID  
Sent By cpuell Date 2021-03-23 Time 15:40 Rev Time 0.00
Received By cpuell Date 2021-03-23 Time 15:40 Sent To  
Notes
2021-03-23 15:41:11HALF ADDRESSES RETIRED

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2021-03-29 Cont ID  
Sent By scwelter Date 2021-03-29 Time 12:50 Rev Time 0.00
Received By scwelter Date   Time   Sent To  
Notes
2021-03-29 12:54:45PUBLIC ART NOT REQUIRED -

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By rmcphers Date 2021-03-26 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2021-03-26 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By mcphers Date 2021-03-05 Time 12:26 Rev Time 0.00
Received By rmcphers Date 2021-03-05 Time 12:26 Sent To  
Notes
2021-03-05 12:37:20REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) REVISED 2ND FLOOR EXIT ACCESS USING THE PIAZZA -
 PLEASE SHOW THE WIDTH OF THE PIAZZA AND ADDED DOOR TO
 COMPLY WITH FBC 1005.4 CONTINUITY.
 THE MINIMUM WIDTH OR REQUIRED CAPACITY OF THE MEANS OF
 EGRESS REQUIRED FROM ANY STORY OF A BUILDING SHALL NOT
 BE REDUCED ALONG THE PATH OF EGRESS TRAVEL UNTIL
 ARRIVAL AT THE PUBLIC WAY.
  
 PROVISO: (EXTERIOR DESIGN OF ROOF TOP BAR WALLS AND
 OVERHEAD DOOR WILL NEED TO MEET WIND LOADS (FBC 1609)
 WITH GLAZING TO MEET IMPACT LOADS (FBC 1609.1.2) )
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By rmcphers Date 2020-12-07 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2020-12-07 Time 08:06 Sent To  
Notes
2020-12-07 11:14:41SUNSET LOUNGE REVISION TO 18110093
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) 2ND FLOOR BALLROOM EXIT - BALLROOM EXIT SEPARATION
 DISTANCE NEEDS TO BE SHOWN (SHOW THE DIAGONAL
 MEASUREMENT OF THE BALLROOM AND SHOW THE EXIT DISTANCE
 SEPARATION MEASUREMENT) TO COMPLY WITH FBC 1007.1.1 TWO
 EXITS OR EXIT ACCESS DOORWAYS.
 WHERE TWO EXITS, EXIT ACCESS DOORWAYS, EXIT ACCESS
 STAIRWAYS OR RAMPS, OR ANY COMBINATION THEREOF, ARE
 REQUIRED FROM ANY PORTION OF THE EXIT ACCESS, THEY
 SHALL BE PLACED A DISTANCE APART EQUAL TO NOT LESS THAN
 ONE-HALF OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED MEASURED
 IN A STRAIGHT LINE BETWEEN THEM. (2).WHERE A BUILDING
 IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1 OR
 903.3.1.2, THE SEPARATION DISTANCE SHALL BE NOT LESS
 THAN ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE AREA SERVED.
 2) DOORS THAT PENETRATE FIRE RATED WALLS SHALL BE FIRE
 RATED PER FBC 716.5
 3) 716.5.9 DOOR CLOSING. FIRE DOORS SHALL BE LATCHING
 AND SELF- OR AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS
 SECTION.
 4) PARKING LOT SHOWS CAR CHARGING STATIONS ADDED - YOU
 ARE ADDING AN "ELEMENT" (CHARGING STATION) TO THE
 PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN
 ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO
 COMPLY WITH 2017 FBC ACCESSIBILITY
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-03-03 Cont ID  
Sent By jleahy Date 2021-03-03 Time 10:41 Rev Time 0.00
Received By jleahy Date 2021-03-01 Time 14:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By jleahy Date 2020-12-07 Time 17:36 Rev Time 0.00
Received By jleahy Date 2020-12-07 Time 17:36 Sent To  
Notes
2020-12-07 17:48:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO POWER PLANS SUBMITTED, PLEASE SUBMIT PLANS SHOWING
 LOCATIONS OF RECEPTACLE OUTLETS AND OTHER EQUIPMENT.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-03-24 Cont ID  
Sent By pleduc Date 2021-03-24 Time   Rev Time 0.00
Received By pleduc Date 2021-03-24 Time 10:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-23 Cont ID  
Sent By pleduc Date 2020-11-23 Time   Rev Time 0.00
Received By pleduc Date 2020-11-20 Time 14:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 14:30 Rev Time 0.00
Received By ccole Date 2021-03-26 Time 08:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-03-04 Cont ID  
Sent By ccole Date 2021-03-04 Time 15:16 Rev Time 0.00
Received By ccole Date 2021-03-04 Time 14:05 Sent To  
Notes
2021-03-04 15:17:061ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20110707
 3/4/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P503 GAS ISOMETRIC:
  
 A) PLEASE LABEL THE REGULATORS AND SHOW THE OUTLET
 PRESSURES- SECTION 410.1 FBC FG. SUBMIT MANUFACTURER'S
 SPECIFICATIONS MARKED UP TO SHOW THE INLET AND OUTLET
 PRESSURE PIPE SIZES AND PRESSURES.
  
 B) SHOW THE LOCATION OF THE AUTO GAS VALVE FOR THE FIRE
 SUPPRESSION SYSTEM- SEC.10.4.1 NFPA 96.
  
 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES- SECTION 304.1 FBC FG. INDICATE WHICH METHOD
 WILL BE USED TO SUPPLY THE AIR.
  
 3) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE FOR
 THE WATER HEATERS- SECTIONS 505 7 503 FBC FG.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND WATER HEATERS- SECTIONS 623.1 AND 624.1
 FBC FG. PLEASE INCLUDE THE SPECS FOR THE DIRECT VENT
 AIR INTAKE AND EXHAUST SYSTEM FOR THE WATER HEATER AS
 SHOWN ON SHEET M102.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-12-07 Cont ID  
Sent By ccole Date 2020-12-07 Time 15:50 Rev Time 0.00
Received By ccole Date 2020-12-07 Time 15:50 Sent To  
Notes
2020-12-07 15:53:45A SEPARATE PRIMARY PERMIT AND PLANS ARE REQUIRED FOR
 THE GAS PIPING INSTALLATIONS- SECTION 105.1 & 107.2.1
 WPB. COMPLETE SETS OF PLANS AND SPECIFICATIONS ARE
 REQUIRED INCLUDING A GAS RISER, A GAS PIPING PIPING
 LAYOUT DRAWING, EQUIPMENT AND APPLIANCE PRODUCT
 SUBMITTALS, AND COMBUSTION AIR CALCULATIONS- SECTIONS
 105.1 & 107.2.1 WPB.
  
 CCOLE
 12/7/2020

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-11-24 Cont ID  
Sent By fmittner Date 2020-11-24 Time 16:37 Rev Time 0.00
Received By fmittner Date 2020-11-24 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-26 Cont ID  
Sent By rmcphers Date 2021-03-26 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2021-03-23 Time 15:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-03-10 Cont ID  
Sent By lmarchan Date 2021-03-10 Time 14:36 Rev Time 0.00
Received By lmarchan Date 2021-02-16 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-07 Cont ID  
Sent By jleahy Date 2020-12-07 Time 17:49 Rev Time 0.00
Received By jleahy Date 2020-11-18 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By medwards Date 2021-03-26 Time 16:28 Rev Time 0.00
Received By medwards Date 2021-03-26 Time 08:16 Sent To  
Notes
2021-03-26 16:29:093RD REVIEW FBC-2020 MECHANICAL
 PERMIT-20110707
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: APPROVED WITH THE FOLLOWING
 PREVISO: NOTE (5) OF THE MECHANICAL REVIEWER?S COMMENTS
 WILL NEED TO BE ADDRESSED BY 04/09/2021
  
 1) AS OF THIS DATE (03-26-2021) THERE HAVE BEEN NO
 MECHANICAL PERMITS PULLED FOR THE MECHANICAL SYSTEMS
 FOR THIS PROJECT.
  
 2) CHRIS COLE?S COMMENT ON 04/22/2019: 1) IN ACCORDANCE
 WITH THE ARCHITECT'S NARRATIVE, THE KITCHEN COOKING
 APPLIANCES AND EQUIPMENT, THE KITCHEN HOODS AND FIRE
 SUPPRESSION SYSTEMS WILL BE DONE UNDER SEPARATE PERMIT.
 AS A RESULT, THE NARRATIVE INDICATES GAS-FIRED COOKING
 APPLIANCE SUBMITTALS, COMBUSTION AIR CALCULATIONS, AIR
 BALANCE CALCULATIONS, AND MAKE UP AIR TEMPERATURE
 COMPLIANCE WILL ALSO BE DEFERRED TO A FUTURE DATE.
 PLEASE PLACE LARGE BOLD NOTES ON THE PLAN TO INDICATE
 THIS FOR PUBIC RECORD AND FOR THE CONTRACTORS IN THE
 FIELD.
  
 3) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED
 SEPARATELY FOR REVIEW AND PERMITTING. HOOD PLANS HAVE
 BEEN LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION.
 PLEASE CONTACT THE PERMIT LIBRARIAN AT
 [email protected] TO HAVE THE HOOD SHEETS REMOVED
 FROM THIS SUBMITTAL.
  
 4) REFRIGERATION EQUIPMENT MUST BE SUBMITTED SEPARATELY
 FOR REVIEW AND PERMITTING. REFRIGERATION PLAN HAS BEEN
 LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION.
 PLEASE CONTACT THE PERMIT LIBRARIAN AT
 [email protected] TO HAVE THE REFRIGERATION SHEET
 REMOVED FROM THIS SUBMITTAL.
  
 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE IN THIS BUILDING. EXAMPLE: 1ST FLOOR HAS A BAR
 AREA BESIDE OF THE DINING ROOM/LOUNGE IT SHOULD BE
 CALCULATED AT 100 OCCUPANTS PER 1000 SQ FT. THE
 VESTIBULE SHOULD BE COUNTED AS A LOBBY. THERE IS ALSO A
 STAGE IN THIS AREA WHICH SHOULD BE COUNTED AS 70
 OCCUPANTS PER 1000 SQ.FT. THE 2ND FLOOR HAS A
 LOBBY/PREFUNCTION AREA THAT NEEDS MORE OUTDOOR AIR THAN
 A LOBBY. THE STAGE ON THE MEZZANINE SHOULD BE COUNTED
 AS 70 OCCUPANTS PER 1000 SQ.FT.. THE RELAX AREA SHOULD
 BE COUNTED AS PART OF THE LOBBY/PREFUNCTION AREA. THE
 ROOF HAS A ROOF TOP BAR THAT ISN?T SHOWN AT ALL IN THE
 OUTDOOR AIR CALCULATIONS. ONCE THESE AREAS HAVE CHANGED
 THE AIR BALANCE SCHEDULES SHOULD BE UPDATED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-02 Time 17:27 Rev Time 0.00
Received By medwards Date 2021-03-02 Time 14:04 Sent To  
Notes
2021-03-02 17:27:351ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110707 2ND CYCLE
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR THE
 KITCHEN HOODS AND THE REFRIGERATION EQUIPMENT.
  
  
 1) PLEASE PROVIDE A LETTER SHOWING A CHANGE OF EOR.
  
 2) SHEET M-501: PLEASE CHECK LABELING OF DUCTWORK FOR
 DETAIL (2) AS IT APPEARS THE OUTDOOR AIR IS LABELED SA,
 AND IT APPEARS THAT SA IS DUCTED INTO EACH RA. FBC
 107.2.1
  
 3) OUTDOOR AIR CALCULATIONS MUST BE CALCULATED
 ACCORDING TO TABLE 403.3.1.1 NOT BY THE OCCUPANCY SHOWN
 IN THE ARCHITECTURAL DRAWINGS. FBC M 403.3.1.1
  
 4) SHEET M-702: PLEASE PROVIDE A COMPLETE OUTDOOR AIR
 CALCULATION CHART, THERE APPEARS TO BE SEVERAL SPACES
 IN THIS BUILDING THAT DO NOT APPEAR IN THE VENTILATION
 RATE CALCULATIONS. FBC M 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By medwards Date 2020-11-30 Time 10:28 Rev Time 0.00
Received By medwards Date 2020-11-27 Time 07:05 Sent To  
Notes
2020-11-30 10:28:121ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110707-
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-001 IS REVISED WITH SHEET M-101 THESE SHEETS
 DO NOT MATCH. PLEASE SUBMIT MATCHING SHEET NUMBERS. FBC
 107.2
  
 2) SHEET M-102: PLEASE SHOW FIRE DAMPER FOR DUCT
 PENETRATING THE RATED WALL OF THE LOBBY/PRE-FUNCTION
 AREA. FBC M607
  
 3) PLEASE PROVIDE INFORMATION AS TO WHY FCU-2-5 IS
 LOCATED IN THE RATED AREA OF THE LOBBY/PRE-FUNCTION
 AREA. FBC 107.2
  
 4) WHY IS FCU-3-3 IN STAIRWAY?
  
 5) PLEASE PROVIDE SPECS FOR THE EQUIPMENT ON THIS
 CYCLE.
  
 6) SHEET M-103: PLEASE IDENTIFY ON THE DRAWING THE UNIT
 CONDITIONING THE BATHROOMS, HALL, AND LOBBY. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 14:30 Rev Time 0.00
Received By ccole Date 2021-03-26 Time 08:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-03-04 Cont ID  
Sent By ccole Date 2021-03-04 Time 13:56 Rev Time 0.00
Received By ccole Date 2021-03-02 Time 13:35 Sent To  
Notes
2021-03-04 13:57:082ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110707
 3/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDENTS TO THE FBC SIXTH EDITION
 2017
  
 PLAN REVIEW RESULTS: DENIED.
 BASED ON THE RESUBMITTED PLANS AND NARRATIVE RESPONSES,
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW.
 REMARKS IN CAP LETTERS HAVE BEEN ADDED FOR FURTHER
 CLARIFICATION.
  
 13) FAILED. P103 & P503: REFER TO SECTION 1107.1 FBC P
 AND VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM
 POSSIBLE DEPTH OF WATER THAT WILL POND THEREON AS
 DETERMINED BY THE RELATIVE LEVELS OF ROOF DECK AND
 OVERFLOW WEIRS, SCUPPERS, EDGES OR SERVICEABLE DRAINS
 IN COMBINATION WITH THE DEFLECTED STRUCTURAL ELEMENTS.
 IN DETERMINING THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL
 PRIMARY ROOF DRAINAGE MEANS SHALL BE ASSUMED TO BE
 BLOCKED. THE MAXIMUM POSSIBLE DEPTH OF WATER ON THE
 ROOF SHALL INCLUDE THE HEIGHT OF THE WATER REQUIRED
 ABOVE THE INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO
 ACHIEVE THE REQUIRED FLOW RATE OF THE SECONDARY
 DRAINAGE MEANS TO ACCOMMODATE THE DESIGN RAINFALL RATE
 AS REQUIRED BY SECTION 1106. THE NARRATIVE REFERENCES
 SHEETS A1.03A, A1.03B, & A1.03C. I WAS NOT ABLE TO
 LOCATE THE SHEETS IN THE SET, HOWEVER THE ROOF DRAINAGE
 PLANS ARE SHOWN ON SHEET A1.04. THE SHEET IS
 INCOMPLETE. REFER TO THE SCHEDULES ON THE PLANS AND
 LABEL THE 01. 02, 03, 04 AREAS ON THE PLANS, AND ALL
 ROOF DRAIN LOCATIONS ON FLAT ROOFS. PLEASE NOTE SOME DS
 LOCATIONS ARE NOT MARKED IN ACCORDANCE WITH MARKS SHOWN
 IN THE SCHEDULE.
  
 14) FAILED. P103, P104 & P503: PROVIDE SECONDARY OR
 EMERGENCY OVERFLOW ROOF DRAIN SYSTEMS INCLUDING
 CALCULATIONS AND OVERFLOW DRAIN DETAILS- SEE SECTION
 1108 FBC P. SEE COMMENT NOTES FOR #13.
  
 15) FAILED. P503: PROVIDE A CONDENSATE DISPOSAL RISER-
 SECTION 107.2.1 WPB. THE RISER IS INCOMPLETE AND DOES
 NOT INCLUDE ALL THE FAN COIL UNITS THROUGHOUT THE
 FLOORS.
  
 18) FAILED P501, SANITARY D: PROVIDE CLEANOUTS AT THE
 BASES OF THE 3 IN. STACKS. A) THE REVISION CLOUD IS
 BLOCKING THE TEXT OF NOTE 8. PLEASE PROVIDE THE CLOUD
 AROUND THE NUMBERS ONLY. B) ISO C: LABEL THE ISO AS
 GREASE WASTE ISOMETRIC AND LABEL THE GREASE WASTE LINE-
 GW. REMOVE THE HANDSINKS AND FLOOR SINK BY THE ICEMAKER
 AND ROUTE THE DRAINAGE TO THE SANITARY LINE. PLEASE SEE
 REMARKS UNDER NEW COMMENT #2 BELOW.
  
 19) FAILED. P601: PLEASE PROVIDE INDIRECT WASTE
 PLUMBING PIPING DETAILS FOR THE 2 AND 3-COMPARTMENT
 SINKS, THE DISHWASHER, AND ALL OTHER DISHWASHING SINKS
 AND FOOD HANDLING EQUIPMENT OR FIXTURES- REFER TO
 SECTIONS 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2
 FBC P. A MINIMUM 4 IN. AIR GAP IS REQUIRED FOR A 2 IN.
 WASTE PIPE- SECTION 802.2.1 FBC P.
  
 20) FAILED. P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR
 TO BE MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
 ALL OTHER FIXTURES FROM THE KITCHEN CONSULTANT LIST ARE
 INCLUDED IN THE SCHEDULE. PLEASE NOTE THAT THE
 3-COMPARTMENT SINK IS NOT IN THE KITCHEN SCHEDULE ON
 A4.04.
  
 21) FAILED. P701: ITEM #35 WHICH IS REFERENCED IN ITEM
 #36 & 37 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1
 WPB. SEE COMMENT # 20 REMARKS.
  
 25) FAILED. P-202, P403, P404 & P502: SHOW SHUTOFF
 VALVES FOR THE RISERS UP TO THE HOSE BIBS, BAR AND
 BATHROOMS- SECTION 606.1 FBC P. VALVES NOT SHOWN. NOTE
 112 IS REQUIRING AN IN-LINE BF PREVENTER FOR THE HOSE
 BIB. REFER TO SECTION - 608.15.4.2 HOSE CONNECTIONS.
 SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND OTHER OPENINGS
 WITH A HOSE CONNECTION SHALL BE PROTECTED BY AN
 ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A
 PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) SHEETS P000, P101: LABEL THE GREASE WASTE LINE- (GW)
 AND THE SANITARY LINE- (SAN) PER THE SYMBOL LIST. THE
 GREASE WASTE IS MARKED ST AND MANY OF THE SANITARY
 LINES ARE NOT MARKED.
  
 2) P101, P401, A4.04: IN COMPLIANCWE WITH SECTION
 1003.3.1 FBC P, THE CHIEF PLUMBING INSPECTOR IS NOT
 PERMITTING HANDSINKS TO BE DRAINED INTO A GREASE
 INTERCEPTOR- PLEASE CORRECT THE PLANS SECTION 1003.3.1
 FBC P. THE PLAN ALSO SHOWS CLEAR WATER WASTE FROM FLOOR
 SINKS BY THE ICE MACHINE (K12) DRAINING INTO THE GREASE
 WATE LINE WHICH IS NOT PERMITTED. PLEASE ROUTE THE
 DRAINAGE FROM THESE FIXTURES TO THE SANITARY.
  
 2) P102: LABEL THE SAN DOWN IN THE CHASE.
  
 3) P103: LABEL THE SAN DOWN IN THE MEN'S AND WOMEN'S
 RESTROOMS.
  
 4) P401, DETAIL C: LABEL THE GREASE WASTE LINE- (GW)
 PER THE SYMBOL LIST. IT IS MARKED ST.
  
 5) P501: A) THE REVISION CLOUD IS BLOCKING THE TEXT OF
 NOTE 8. PLEASE PROVIDE THE CLOUD AROUND THE NUMBERS
 ONLY. B) ISO C; LABEL THE ISO AS GREASE WASTE ISOMETRIC
 AND LABEL THE GREASE WASTE LINE- GW. REMOVE THE
 HANDSINKS AND FLOOR SINK BY THE ICEMAKER AND ROUTE THE
 DRAINAGE FROM THESE FIXTURES TO THE SANITARY LINE.
  
 6) P701: EQUIPMENT SCHEDULES FOR TEA-1 AND TEA-2 ARE
 NOT PROVIDED. PLEASE NOTE THAT THERMAL EXPANSION TANKS
 SHALL BE INSTALLED ON THE WH COLD WATER INLET PIPE AT A
 POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE
 REDUCING VALVES AND BACKFLOW PREVENTERS.
  
 7) P701: IT IS ACKNOWLEDFGED THAT THE GREASE
 INTERCEPTOR SHALL BE SEPARATELY PERMITTED. COMPLETE
 PLANS, CALCULATIONS, AND PRODUCT SPECIFICATIONS SHALL
 BE SUBMITTED. PLEASE NOTE THAT THE CURRENT CALCULATIONS
 DO NOT INCLUDE THE 2-COMPARTMENT SINK, AND THE DRAINAGE
 FROM THE FLOOR SINKS SERVING COOKING APPLIANCES, AND
 THE TRENCH DRAIN.
  
 8) P702: PLEASE ADD A BACKFLOW PREVENTER FOR THE WATER
 FILTRATION SYSTEM FOR PROTECTION AGAINST CONTAMINATION-
 SECTION 608.3 FBC P.
  
 9) IRR-1: BACKFLOW PREVENTERS ARE REQUIRED TO PROTECT
 THE POTABLE WATER SYSTEM PER SECTION 608.1 FBC P. THE
 POTABLE WATER FOR THE BUILDING IS CITY SUPPLIED, AND
 THE IRRIGATION WATER IS WELL SUPPLIED. PLEASE CLARIFY
 THE NEEED FOR THE BF PREVENTER. IS IT FOR PROTECTION OF
 THE PUMP, THE WELL WATER?
  
 10) P-503: PLEASE SEE SEPARATE GAS REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By tklarge Date 2020-12-07 Time 15:37 Rev Time 0.00
Received By ccole Date 2020-12-04 Time 12:45 Sent To  
Notes
2020-12-07 15:38:031ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110707
 12/7/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-000:
  
 A) PROVIDE A LIST OF SEPARATELY PERMITTED ITEMS
 INCLUDING THE WATER SERVICE BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, GAS PIPING, GENERATOR, AND THE IRRIGATION
 SYSTEM. PLEASE NOTE COMPLETE SETS OF PLANS AND
 SPECIFICATIONS ARE REQUIRED FOR REVIEW- SECTION 107.2.1
 WPB.
  
 B) PROVIDE A LIST OF DEFERRED SUBMITTALS INCLUDING THE
 FOOD SERVICE EQUIPMENT PLANS, AND ALL PLUMBING
 FIXTURES, APPLIANCES, DEVICES, AND EQUIPMENT
 SPECIFICATIONS NOT TO BE SUBMITTED UNDER THIS MAIN
 PERMIT- SECTION 107.3.4.1 WPB.
  
 2) THERE ARE TWO P-101 PLANS IN THIS SUBMITTAL- ONE
 FROM THE PREVIOUS ENGINEER AND ONE FROM THE NEW
 ENGINEER. PLEASE RENAME ONE OF THESE SHEETS- SECTION
 107.2.1 WPB.
  
 3) P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES.
  
 4) P-001: THIS PLAN SHEET IS NOT IN THE INDEX ON P-000.
 PLEASE ADD IT TO THE INDEX AND REVISE THE FIXTURE AND
 EQUIPMENT SCHEDULES ON THE PLAN TO MATCH THE SCHEDULES
 ON P701- SECTION 107.2.1 WPB.
  
 5) SHEETS A0.04 & P101: PLEASE PROVIDE THE CIVIL, PLANS
 THAT ARE REFERENCED IN THE NOTES AND OTHER PLAN SHEET
 NOTES FOR CONTINUATIONS OF THE PLUMBING AND STORM DRAIN
 PIPING SYSTEMS- SECTION 107.2.1.
  
 6) ELLIS AND GRITTER P101: REVISE THE GREASE WASTE
 PIPING LAYOUT TO MATCH THE NEW LAYOUT SHOWN ON SHEETS
 P401 & 501- SECTION 107.2.1 WPB. BOTH THE OLD AND NEW
 P101 PLAN SHEETS AND P401 & P501 SHOW THE MOP SINK
 DRAIN CONNECTING TO THE GREASE WASTE LINE, PLEASE NOTE
 IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE MOP SINK
 SHALL DRAIN INTO THE SANITARY AND NOT INTO THE GREASE
 WASTE LINE.
  
 7) P101 & P701 GREASE INTERCEPTOR: AS NOTED IN COMMENT
 #1A A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE
 GREASE INTERCEPTOR, AND THE SUBMITTAL SHALL INCLUDE THE
 FOLLOWING LIST OF ITEMS.
  
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUAL FOR THE SCHIER INTERCEPTOR WITH APPROVAL STAMPS
 BY THE EOR.
  
 B) REVISED SIZING CALCULATIONS. PLEASE NOTE THE CURRENT
 EQUIPMENT SCHEDULE SEEMS TO INDICATE TWO DIFFERENT
 SIZING METHODS- THE PDI METHOD WHICH IS BASED ON GPM
 FLOW-THRU RATINGS AND GREASE RETENTION TIME FOR THE
 FIXTURES, AND FAC RULE 64E-6.013 METHOD WHICH IS BASED
 ON THE NUMBER OF SEATS, GALLONS OF WASTEWATER ETC.-
 THIS METHOD IS COMMONLY USED FOR GRAVITY-TYPE
 INTERCEPTORS.
  
 8) P101, P601. P701 SUMP PUMP AND PIT.
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP
 PUMP. SECTION 712.3.1 FBC P. THE PUMP SHALL BE EQUIPPED
 WITH AN OIL WATER SEPARATOR OR IT SHALL BE PROVIDED
 SEPARATELY- SECTION 1003.4 FBC P.
  
 B) PROVIDE THE DIMENSIONS OF THE SUMP PIT IN THE
 DETAIL- SECTION 712.3.2.
  
 C) PROVIDE A GAS TIGHT COVER FOR THE SUMP PIT- SECTION
 712.3.2.
  
 D) PROVIDE THE SIZE OF THE DISCHARGE PIPING AND PROVIDE
 A VENT FOR THE PIT- SECTION 713.2.1.
  
 9) P101 & P102: NOTE #8 (P102) INDICATES CLEANOUTS AT
 THE BASE OF SANITARY STACKS WHICH ARE NOT SHOWN ON AT
 THE CHASE LOCATION BY THE RESTROOMS. PLEASE NOTE THAT
 SECTION 1101.8 REQUIRES STORM DRAIN CLEANOUTS TO BE
 INSTALLED IN ACCORDANCE WITH THE CODES FOR SANITARY
 DRAIN CLEANOUTS.
  
 10) P103, NOTE 306: ACCORDING TO SECTION 1104.2 FBC P
 FLOOR DRAINS SHALL NOT BE CONNECTED TO STORM DRAINS.
 PLEASE PROVIDE MORE INFORMATION AND DETAILS TO CLARIFY-
 SECTION 107.2.1 WPB.
  
 11) P103: PROVIDE PRODUCT SUBMITTALS FOR RD-2, FD-1,
 AND TD-1. PLEASE CLARIFY IF THE FD-1 AND TD-1 SHOWN IN
 THE P701 SCHEDULE FOR THE INTERIOR ARE THE SAME TYPE OF
 FIXTURES TO BE INSTALLED IN THE EXTERIOR OPEN ROOF
 AREAS- SECTION 1105.1 FBC P AND SECTION 107.2.1 WPB.
  
 12) P103: FD-1 ON THE LOWER ROOF SHALL NOT CONNECT TO
 THE SANITARY PER SEC. 90-126 WPB CODE OF ORDINANCES.
  
 13) P103 & P503: REFER TO SECTION 1107.1 FBC P AND
 VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM POSSIBLE
 DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY
 THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE
 MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL
 INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE
 INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE
 THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS
 TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY
 SECTION 1106.
  
 14) P103, P104 & P503: PROVIDE SECONDARY OR EMERGENCY
 OVERFLOW ROOF DRAIN SYSTEMS INCLUDING CALCULATIONS AND
 OVERFLOW DRAIN DETAILS- SEE SECTION 1108 FBC P.
  
 15) P503: PROVIDE A CONDENSATE DISPOSAL RISER- SECTION
 107.2.1 WPB.
  
 16) P401 SANITARY A: SEE COMMENT #7.
  
 17) P401, SANITARY C: IT APPEARS A CLEANOUT IS MISSING
 FOR THE 4 IN. GREASE WASTE BRANCH LINE IN THE KITCHEN
 BY THE DISHWASHER- SECTION 708.1.4 FBC P. CLARIFY HOW
 ACCESS TO THE WCO IN THE FREEZER WILL BE PROVIDED-
 SECTIONS 708.1.9 & 708.1.0 FBC P.
  
 18) P501, SANITARY D: PROVIDE CLEANOUTS AT THE BASES OF
 THE 3 IN. STACKS.
  
 19) P601: PLEASE PROVIDE INDIRECT WASTE PLUMBING PIPING
 DETAILS FOR THE 2 AND 3-COMPARTMENT SINKS, THE
 DISHWASHER, AND ALL OTHER DISHWASHING SINKS AND FOOD
 HANDLING EQUIPMENT OR FIXTURES- REFER TO SECTIONS
 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 FBC P.
  
 20) P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR TO BE
 MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
  
 21) P701: ITEM #35 WHICH IS REFERENCED IN ITEM #36 & 37
 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
  
 22) P201: SHOW THE LOCATIONS OF THE WATER METER AND
 MAIN SHUT OFF VALVES- SECTION 606.1 FBC P.
  
 23) P201: SHOW FULL OPEN SHUT OFF VALVES FOR THE DOWN
 FEEDING WATER SUPPLY LINES BY JAN. 118- SECTION
 606.1(5) FBC P.
  
 24) P201: THERE APPEARS TO BE A SHUT OFF VALVE MISSING
 AT THE RISER BY DOOR 108- SECTION 606.1(4) FBC P.
  
 25) P-202, P403, P404 & P502: SHOW SHUTOFF VALVES FOR
 THE RISERS UP TO THE HOSE BIBS, BAR AND BATHROOMS-
 SECTION 606.1 FBC P.
  
 26) P-201, P202, P203, P403, P404, & P502: SHOW THE
 LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS, MIXING
 VALVES, AND BACKFLOW PREVENTERS- SECTIONS 604.9, 416.4,
 607.1.2, & 608.3 FBC P. PLEASE NOTE THAT BACKFLOW
 PREVENTERS ARE REQUIRED FOR WATER SUPPLY LINES TO THE
 DISHWASHER, ICE MAKERS, WATER FILTERING SYSTEM,
 CHEMICAL STORAGE CABINET, AND BEVERAGE AND COFFEE
 DISPENSERS ETC.
  
 27) P701: PLEASE LABEL THE LOCATION OF THE CHEMICAL
 STORAGE CABINET ON THE DOMESTIC PLANS AND RISER
 DRAWINGS- SECTION 608.3 FBC P. CLARIFY IF WASTE WATER
 FROM THE CABINET WILL BE DRAINING INTO THE SANITARY
 SYSTEM AND PROVIDE A NEUTRALIZING DEVICE IF APPLICABLE-
 SECTION 803.1 FBC P.
  
 28) P601: PLEASE PROVIDE A PLUMBING DIAGRAM FOR THE
 CHEMICAL STORAGE CABINET- SECTION 107.2.1 WPB.
  
 29) P701: PROVIDE THE EFFICIENCY RATINGS OF THE WATER
 HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 30) P701: PROVIDE DRAIN PANS AND DRAIN PAN LINES FOR
 THE WATER HEATERS- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 31) P701: PROVIDE A PLUMBING DEVICE SCHEDULE SHOWING
 THE MAKES AND MODEL NUMBERS AND LISTINGS OF THE WATER
 HAMMER ARRESTORS, BACKFLOW PREVENTERS, MIXING VALVES,
 AND TRAP PRIMERS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2020-12-07 Cont ID  
Sent By ccole Date 2020-12-07 Time 15:54 Rev Time 0.00
Received By ccole Date 2020-12-07 Time 15:54 Sent To  
Notes
2020-12-07 15:57:44A SEPARATE PRIMARY PERMIT AND PLANS ARE REQUIRED FOR
 INSTALLATION OF THE GREASE INTERCEPTOR- SECTION 105.1 &
 107.2.1 WPB.
 COMPLETE PLANS AND SPECIFICATIONS ARE REQUIRED
 INCLUDING A GREASE WASTE PIPING PLAN, GREASE WASTE
 CALCULATIONS, EQUIPMENT SCHEDULE, AND PRODUCT
 SUBMITTALS.
  
 CCOLE
 12/7/2020

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2021-03-26 Cont ID  
Sent By ccole Date 2021-03-26 Time 09:53 Rev Time 0.00
Received By ccole Date 2021-03-26 Time 09:53 Sent To  
Notes
2021-03-26 09:57:46THE IRRIGATION PLANS FOR THE PROJECT HAVE BEEN VOIDED
 BY THE WPB P & Z DEPARTMENT WITH A NOTE ON THE PLAN
 REQUESTING SEPARATE LANDSCAPE PLANS.
 THE IRRIGATION PLANS CONTAINED IN THE MASTER SET SHALL
 BE SUBMITTED UNDER A SEPARATE PRIMARY PERMIT
 APPLICATION- SECTION 105.1 WPB.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By rmcphers Date 2021-03-26 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2021-03-26 Time 16:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-02 Cont ID  
Sent By medwards Date 2021-03-02 Time 17:43 Rev Time 0.00
Received By medwards Date 2021-03-02 Time 17:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By medwards Date 2020-11-30 Time 10:51 Rev Time 0.00
Received By medwards Date 2020-11-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-03-26 Cont ID  
Sent By elevesqu Date 2021-03-26 Time 08:31 Rev Time 0.00
Received By elevesqu Date 2021-03-26 Time 08:31 Sent To  
Notes
2021-03-26 08:31:23 
 PARTIALLY SATISFIED - SEE CONDITION OF APPROVAL. WHAT
 APPEARS TO BE LARGE EXHAUST FAN ON NORTH SIDE OF
 BUILDING THAT APPEARS ON SHEET A3.03 IS NOT INDICATED
 ON NORTH ELEVATION SHEET A2.01. PLEASE INCLUDE. CAN
 THIS BE SCREENED? CAN THIS BE PAINTED?
 PLEASE EVALUATE AND PROVIDE RESPONSES. ALSO PLEASE
 INCLUDE ON SHEET A3.04
 STILL ON SHEET A 3.03. EXHAUST FAN SHALL BE PAINTED TO
 MATCH BUILDING FACADE COLOR AND SCREENED TO BEST EXTENT
 POSSIBLE
  
 PARTIALLY SATISFIED - SEE CONDITION OF APPROVAL EXHAUST
 HOOD AS SHOWN ON EAST FACADE-WALL SECTION ON SHEET
 A3.10 DOES NOT SEEM TO APPEAR ON ELEVATIONS. PLEASE
 INDICATE AND INCLUDE DETAIL OF SCREENING.
 ALL ROOF MOUNTED EXHAUST HOOD SHALL BE SCREENED
  
 NEW PROVISOS:
 PANIC GATE DESIGNED BY ARTIST TO BE SUBJECT TO PERMIT
 REVISION ONCE DETAIL HAS BEEN SELECTED
  
 PREVIOUS PROVISOS FROM PERMIT 18110093 - SOME MAY
 ALREADY BE SATISFIED:
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED WITHIN 30 DAYS
 AND NEW PLANS SHALL BE UPLOADED:
 1. PLEASE SUBMIT A PHOTOMETRIC PLAN FOR THE SITE
 INCLUDING INTERIOR AND ROW LIGHTING AND PROVIDE LIGHT
 POLE DETAIL. ANY FEES ASSOCIATED WITH THE REMOVAL OF
 EXISTING STREET LIGHTS SHALL BE A COST TO THE OWNER. P
 PLEASE INCLUDE A LANDSCAPE PLAN WITHIN THE LIGHTING
 PERMIT THAT INCLUDES THE LOCATION OF THE LIGHT POLES TO
 ENSURE NO CONFLICTS WITH STREET TREES. PLEASE INCLUDE
 LIGHT POLE SPEC (CONTACT CITY CRA AND ENG. FOR
 APPROPRIATE LIGHT POLE FOR THIS STREETSCAPE)
 2. SATISFIED THE APPLICANT SHALL MOVE THE DUMPSTER
 ENCLOSURE OUT OF THE SIGHT TRIANGLE LINE AND SHALL
 BUILD THE ENCLOSURE TO MEET CITY REQUIREMENTS.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 ISSUANCE OF FINAL CO:
 1. PROPERTIES SHALL BE REPLATTED AND UNIFIED PRIOR TO
 ISSUANCE OF FINAL CO. A SIDEWALK EASEMENT IS REQUIRED
 ALONG ROSEMARY AVENUE.
 2. SATISFIED PRIOR TO THE REMOVAL OR RELOCATION OF ANY
 TREES ON THE PROPERTY, A TREE ALTERATION PERMIT SHALL
 BE SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 3. THE APPLICANT SHALL COORDINATE WITH THE ZONING
 DEPARTMENT ON THE PLACEMENT OF ABOVE GROUND UTILITIES
 INCLUDING BACKFLOW PREVENTERS, TRANSFORMERS, AND FIRE
 DEPARTMENT CONNECTIONS OUTSIDE OF THE MINIMUM SETBACK
 AREA AND SHALL LANDSCAPE THE UTILITIES FROM THE ROW.
 4. PAVEMENT SHALL BE RESURFACED IN ACCORDANCE WITH CITY
 STANDARDS TO ANY AREA WHERE PAVEMENT MARKINGS ARE
 REMOVED.
 5. THE APPLICANT SHALL COORDINATE WITH THE CITY ON THE
 FINAL CROSS SECTION OF ROSEMARY AVENUE AND CONSIDER
 ELIMINATION OF THE ROSEMARY AVENUE ON-STREET PARKING.
  
 PROVISOS:
 1. ALL CURB CUTS AND STREET CORNERS WITHIN THE PROJECT
 SITE SHALL BE DESIGNED TO MEET ADA COMPLIANT CROSSINGS.
 2. THE APPLICANT SHALL CONTINUE TO COORDINATE WITH THE
 CRA AND CITY ON 8TH STREET AND THE HEART AND SOUL PARK
 FOR A COHESIVE DESIGN.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
 4. THE LANDSCAPE AND IRRIGATION WERE NOT APPROVED
 THROUGH THIS PERMIT. A SEPARATE LANDSCAPE AND
 IRRIGATION PERMIT IS REQUIRED.
 5. THE WALL AND ALL SIGNAGE WERE NOT APPROVED THROUGH
 THIS PERMIT. SEPARATE PERMITS ARE REQUIRED.
 6. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 DEVELOPMENT. THIS WILL BE THROUGH A SEPARATE
 MAINTENANCE AGREEMENT WITH THE CITY
 7. IRRIGATION FOR STREET TREES AND LANDSCAPING IN THE
 RIGHT OF WAYS SHALL BE PROVIDED BY THE APPLICANT,
 SUCCESSORS AND ASSIGNS FROM THE SUBJECT DEVELOPMENT.
 ALL EXISTING CITY IRRIGATION LINES RUNNING TO
 INDIVIDUAL AREAS OR TREES SHALL BE REMOVED AND CAPPED
 IN SUCH A WAY TO ENSURE CITY IRRIGATION SUPPLY LINES
 SHALL REMAIN INTACT AND CONTINUOUS FOR OTHER AREAS
 SERVED BY THE LINES
 8. ALL ROOF-MOUNTED EQUIPMENT SHALL BE SCREENED FROM
 THE ROW AT THE HEIGHT OF THE EQUIPMENT.
 9. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]
  
 ANA MARIA APONTE, CITY URBAN DESIGNER - 561 822 1439
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2021-03-10 Cont ID  
Sent By elevesqu Date 2021-03-10 Time 12:19 Rev Time 0.00
Received By elevesqu Date 2021-03-10 Time 12:19 Sent To  
Notes
2021-03-10 12:18:56 
 PARTIALLY SATISFIED - SEE CONDITION OF APPROVAL. WHAT
 APPEARS TO BE LARGE EXHAUST FAN ON NORTH SIDE OF
 BUILDING THAT APPEARS ON SHEET A3.03 IS NOT INDICATED
 ON NORTH ELEVATION SHEET A2.01. PLEASE INCLUDE. CAN
 THIS BE SCREENED? CAN THIS BE PAINTED?
 PLEASE EVALUATE AND PROVIDE RESPONSES. ALSO PLEASE
 INCLUDE ON SHEET A3.04
 STILL ON SHEET A 3.03. EXHAUST FAN SHALL BE PAINTED TO
 MATCH BUILDING FACADE COLOR AND SCREENED TO BEST EXTENT
 POSSIBLE
  
 PARTIALLY SATISFIED - SEE CONDITION OF APPROVAL EXHAUST
 HOOD AS SHOWN ON EAST FACADE-WALL SECTION ON SHEET
 A3.10 DOES NOT SEEM TO APPEAR ON ELEVATIONS. PLEASE
 INDICATE AND INCLUDE DETAIL OF SCREENING.
 ALL ROOF MOUNTED EXHAUST HOOD SHALL BE SCREENED
  
 NEW PROVISOS:
 PANIC GATE DESIGNED BY ARTIST TO BE SUBJECT TO PERMIT
 REVISION ONCE DETAIL HAS BEEN SELECTED
  
 PREVIOUS PROVISOS FROM PERMIT 18110093 - SOME MAY
 ALREADY BE SATISFIED:
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED WITHIN 30 DAYS
 AND NEW PLANS SHALL BE UPLOADED:
 1. PLEASE SUBMIT A PHOTOMETRIC PLAN FOR THE SITE
 INCLUDING INTERIOR AND ROW LIGHTING AND PROVIDE LIGHT
 POLE DETAIL. ANY FEES ASSOCIATED WITH THE REMOVAL OF
 EXISTING STREET LIGHTS SHALL BE A COST TO THE OWNER. P
 PLEASE INCLUDE A LANDSCAPE PLAN WITHIN THE LIGHTING
 PERMIT THAT INCLUDES THE LOCATION OF THE LIGHT POLES TO
 ENSURE NO CONFLICTS WITH STREET TREES. PLEASE INCLUDE
 LIGHT POLE SPEC (CONTACT CITY CRA AND ENG. FOR
 APPROPRIATE LIGHT POLE FOR THIS STREETSCAPE)
 2. SATISFIED THE APPLICANT SHALL MOVE THE DUMPSTER
 ENCLOSURE OUT OF THE SIGHT TRIANGLE LINE AND SHALL
 BUILD THE ENCLOSURE TO MEET CITY REQUIREMENTS.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
  
 THE FOLLOWING ITEMS SHALL BE ADDRESSED PRIOR TO
 ISSUANCE OF FINAL CO:
 1. PROPERTIES SHALL BE REPLATTED AND UNIFIED PRIOR TO
 ISSUANCE OF FINAL CO. A SIDEWALK EASEMENT IS REQUIRED
 ALONG ROSEMARY AVENUE.
 2. SATISFIED PRIOR TO THE REMOVAL OR RELOCATION OF ANY
 TREES ON THE PROPERTY, A TREE ALTERATION PERMIT SHALL
 BE SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 3. THE APPLICANT SHALL COORDINATE WITH THE ZONING
 DEPARTMENT ON THE PLACEMENT OF ABOVE GROUND UTILITIES
 INCLUDING BACKFLOW PREVENTERS, TRANSFORMERS, AND FIRE
 DEPARTMENT CONNECTIONS OUTSIDE OF THE MINIMUM SETBACK
 AREA AND SHALL LANDSCAPE THE UTILITIES FROM THE ROW.
 4. PAVEMENT SHALL BE RESURFACED IN ACCORDANCE WITH CITY
 STANDARDS TO ANY AREA WHERE PAVEMENT MARKINGS ARE
 REMOVED.
 5. THE APPLICANT SHALL COORDINATE WITH THE CITY ON THE
 FINAL CROSS SECTION OF ROSEMARY AVENUE AND CONSIDER
 ELIMINATION OF THE ROSEMARY AVENUE ON-STREET PARKING.
  
 PROVISOS:
 1. ALL CURB CUTS AND STREET CORNERS WITHIN THE PROJECT
 SITE SHALL BE DESIGNED TO MEET ADA COMPLIANT CROSSINGS.
 2. THE APPLICANT SHALL CONTINUE TO COORDINATE WITH THE
 CRA AND CITY ON 8TH STREET AND THE HEART AND SOUL PARK
 FOR A COHESIVE DESIGN.
 3. THE PROJECT IS REQUIRED TO COMPLY WITH THE ART IN
 PUBLIC PLACES ORDINANCE.
 4. THE LANDSCAPE AND IRRIGATION WERE NOT APPROVED
 THROUGH THIS PERMIT. A SEPARATE LANDSCAPE AND
 IRRIGATION PERMIT IS REQUIRED.
 5. THE WALL AND ALL SIGNAGE WERE NOT APPROVED THROUGH
 THIS PERMIT. SEPARATE PERMITS ARE REQUIRED.
 6. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 DEVELOPMENT. THIS WILL BE THROUGH A SEPARATE
 MAINTENANCE AGREEMENT WITH THE CITY
 7. IRRIGATION FOR STREET TREES AND LANDSCAPING IN THE
 RIGHT OF WAYS SHALL BE PROVIDED BY THE APPLICANT,
 SUCCESSORS AND ASSIGNS FROM THE SUBJECT DEVELOPMENT.
 ALL EXISTING CITY IRRIGATION LINES RUNNING TO
 INDIVIDUAL AREAS OR TREES SHALL BE REMOVED AND CAPPED
 IN SUCH A WAY TO ENSURE CITY IRRIGATION SUPPLY LINES
 SHALL REMAIN INTACT AND CONTINUOUS FOR OTHER AREAS
 SERVED BY THE LINES
 8. ALL ROOF-MOUNTED EQUIPMENT SHALL BE SCREENED FROM
 THE ROW AT THE HEIGHT OF THE EQUIPMENT.
 9. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 561 822 1426
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By elevesqu Date 2020-11-25 Time 12:14 Rev Time 0.00
Received By elevesqu Date 2020-11-25 Time 12:14 Sent To  
Notes
2020-11-25 10:25:02CANOPY WITH VERTICAL SUPPORT ALONG 8TH STREET- CANNOT
 HAVE VERTICAL ELEMENTS WITHIN MINIMUM SETBACK.
 AWNINGS AND CANOPIES TO BE REVIEWED THROUGH SEPARATE
 PERMIT
  
 PLEASE UPDATE CALC FOR "TOTAL COVERED ROOF STRUCTURES
 PER DEFINITION" AND "TOTAL OVERED STRUCTURES AREA" TO
 REFLECT NEW COVERED HALL ON SHEET A0.08
  
 PLEASE SUBMIT UPDATE TO LANDSCAPE PERMIT FOR
 MODIFICATIONS (DUMPSTER ENCLOSURE) FOR PLAN CONSISTENCY
 AND FOR UPDATES TO ROOF GARDEN
  
 PLEASE SUBMIT SHEET A4.15 FOR BAR PLAN. MUST BE OPEN
 AIR, NOT COVERED, AND NOT CLIMATE CONTROLLED PER
 SECTIONN 94-109 COVERED STRUCTURE DEFINTION. IF THE BAR
 AREA IS COVERED, THIS WOULD COUNT TOWARDS 30% OF
 COVERED STRUCTURE PERMITTED. CANNOT BE ENCLOSED
  
 PLEASE SUBMIT A PERMIT FOR INSTALLATION OF STREET LIGHT
 POLES PRIOR TO INSTALLATION OF ANY POLES. PLEASE
 INCLUDE A LANDSCAPE PLAN THAT INCLUDES THE LOCATION OF
 THE LIGHT POLES TO ENSURE NO CONFLICTS WITH STREET
 TREES. PLEASE INCLUDE LIGHT POLE SPEC (CONTACT CITY CRA
 AND ENG. FOR APPROPRRIATE LIGHT POLE FOR THIS
 STREETSCAPE)
  
 PLEAE EVALUATE - IS THERE OTHER MEANS OTHER THAN
 DOWNNSPOUTS FOR STORMWATER COLLECTION?
  
 MINOR SUBDIVISION FOR REPLAT IS REQUIRED PRIOR TO CO -
 PLEASE SUBMIT THROUGH P&Z
  
 WHAT APPEARST TO BE LARGE EXHAUST FAN ON NORTH SIDE OF
 BUILDING THAT APPAERAS ON SHEET A3.03 IS NOT INDICATED
 ON NORTH ELEVATION SHEET A2.01. PLEASE INCLUDE. CAN
 THIS BE SCREENED? CAN THIS BE PAINTED?
 PLEASE EVALUATE AND PROVIDE RESPONSES. ALSO PLEASE
 INCLUDE ON SHEET A3.04
  
 UPDATE LABEL FOR MECHANICAL WELL SECTION ON SHEET A3.10
 - APPEARS A WINDOW PLACEMENT CHANGED BYT LABEL WAS NOT
 MODIFIED. WHAT WINDOW IS THIS ON THE ELEVATION? PLEASE
 RESPOND IN COMMENT RESPONSE MEMO
  
 EXHAUST HOOD AS SHOWN ON EAST FACADE-WALL SECTION ON
 SHEET A3.10 DOES NOT SEEM TO APPEAR ON ELEVATIONS.
 PLEASE INDICATE AND INCLUDE DETAIL OF SCREENING.
  
 ADA PARKING SIGN CANNOT BE WITHIN 2 FOOT OVERHANG
  
 ARE THERE TWO GENERATORS NOW? GENERATOR UP AGAINST
 SIDEWALK IS NOT IDEAL. PLEASE EVALUATE OTHER LOCATIONS.
 PLEASE PROVIDE ENCLOSURE DETAILS FOR GENERATOR UP
 AGAINST SIDEWALK. HEIGHT, MATERIALS, ETC. - WILL NEED
 TO BE EVALUATED FOR SCREENING
  
 IS NOTE NUMBER 32 BACKFLOW ASSEMBLY TO SERVE THE
 BUILDING? CAN THIS BE RELOCATED ALONG THE INTERNAL
 DRIVE? PLEASE EVALUATE AND DISCUSS WITH MARK HURLEY IN
 PUBLIC UTILITIES AND WITH ZONING
  
 WHAT IS THE MEANING OF THE "X" SYMBOL ON THE FENCE
 DETAILS?
  
 PROPOSED PROVISOS:
 PANIC GATE DESIGNED BY ARTIST TO BE SUBJECT TO PERMIT
 REVISION ONCE DETAIL HAS BEEN SELECTED
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]