2020-11-17 14:53:36 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20110593 |
| 11/17/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER DRAWING: |
| A) CORRECT THE BTU LOAD OF THE GENERATOR LOAD AND THE |
| TOTAL LOAD OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & |
| G2413.2 FBC RES. THE APPROVED GENERATOR PERMIT- 2009009 |
| SHOWS A 327,000 BTUH LOAD. |
| B) INDICATE A NEW OR EXISTING GAS METER AND SHOW THE |
| DELIVERY PRESSURE- G2413.1 |
| C) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET- |
| G2413.4.1 AND G2413.4.2. |
| D) SHOW THE LOCATIONS OF REGULATORS AND THEIR OUTLET |
| PRESSURES- G2421.1 & G2421.2. PLEASE NOTE THAT THE |
| GENERATOR SPECS INDICATE AN INPUT PRESSURE OF 3.5- 7 |
| IN. W.C. |
| |
| 2) PROVIDE VENTING DIAGRAMS FOR THE TANKLESS WATER |
| HEATER, RANGE AND DRYER, OR INDICATE TO BE DONE UNDER A |
| SEPARATE PERMIT BY A LICENSED MECHANICAL CONTRACTOR- |
| SECTIONS 105.1, 107.2.1, 107.3.5.3 WPB. SHOW CLEARANCE |
| DISTANCES FOR THE WATER HEATER PER THE MANUFACTURER?S |
| SPECIFICATIONS- SECTION G2448.1 FBC RES. |
| |
| 3) SUBMIT SPEC SHEETS FOR THE APPLIANCES OR PROVIDE A |
| NOTE TO BE ONSITE FOR INSPECTION- SECTION 107.2.1 WPB. |
| |
| 4) THE $3000.00 VALUE APPEARS LOW FOR THE SCOPE OF |
| WORK. SUBMIT A COPY OF A SIGNED CONTRACT AND/OR |
| ESTIMATES AND INVOICES TO VERIFY THE TOTAL COST |
| INCLUDING LABOR, MATERIAL, AND THE COST OF THE |
| APPLIANCES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |