Plan Review Details - Permit 20110569
Plan Review Stops For Permit 20110569
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-15 Cont ID  
Sent By rmcphers Date 2020-12-15 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2020-12-15 Time 07:38 Sent To  
Notes
2020-12-15 07:54:33CAR CHARGING STATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 YOU ARE ADDING AN "ELEMENT" (CHARGING STATION) TO THE
 PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN
 ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO
 COMPLY WITH 2017 FBC ACCESSIBILITY - SEE CODE SECTIONS
 BELOW.
  
 106.1 ELEMENT. AN ARCHITECTURAL OR MECHANICAL COMPONENT
 OF A BUILDING, FACILITY, SPACE, OR SITE.
  
 201.4SCOPE OF COVERAGE.
 THIS CODE APPLIES TO FIXED OR BUILT-IN ELEMENTS OF
 BUILDINGS, STRUCTURES, SITE IMPROVEMENTS AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE. UNLESS
 SPECIFICALLY STATED OTHERWISE, ADVISORY NOTES, APPENDIX
 NOTES AND FIGURES CONTAINED IN THE CODE EXPLAIN OR
 ILLUSTRATE THE REQUIREMENTS; THEY DO NOT ESTABLISH
 ENFORCEABLE REQUIREMENTS.
  
 202.3ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING
 PARKING.
  
 206.2.2WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 228DEPOSITORIES, VENDING MACHINES, CHANGE MACHINES,
 MAIL BOXES, AND FUEL DISPENSERS
 228.1 GENERAL.
 WHERE PROVIDED, AT LEAST ONE OF EACH TYPE OF
 DEPOSITORY, VENDING MACHINE, CHANGE MACHINE, AND FUEL
 DISPENSER SHALL COMPLY WITH 309.
  
 309 OPERABLE PARTS
  
 309.1GENERAL.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 EXCEPTION: GAS PUMP NOZZLES SHALL NOT BE REQUIRED TO
 PROVIDE OPERABLE PARTS THAT HAVE AN ACTIVATING FORCE OF
 5 POUNDS (22.2 N) MAXIMUM.
  
 DRAWING C3-00 SHOWS CODE VERSION (IBC) NEEDS TO SHOW
 2017 FBC
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By jleahy Date 2020-12-10 Time 07:54 Rev Time 0.00
Received By jleahy Date 2020-12-10 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-15 Cont ID  
Sent By rmcphers Date 2020-12-15 Time 07:56 Rev Time 0.00
Received By rmcphers Date 2020-11-24 Time 14:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By rmcphers Date 2020-12-15 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2020-12-15 Time 07:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-14 Cont ID  
Sent By eschneid Date 2020-12-14 Time 17:04 Rev Time 0.50
Received By eschneid Date 2020-12-14 Time 17:04 Sent To  
Notes
2020-12-14 17:06:34FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE CITY OF WEST PALM BEACH DOES NOT PERMIT
 ELECTRONIC SIGNS FOR COMMERCIAL SHOPPING CENTERS
 (EITHER STATIC OR CHANGEABLE COPY); THEREFORE, THE
 DIGITAL ADVERTISING COPY ON THE SIGNS IS NOT PERMITTED.
 IF NON-ELECTRONIC SIGNAGE (I.E. STATIC SIGNAGE) IS
 USED, THEN IT MAY NOT ADVERTISE OFF PREMISE BUSINESSES
 AND IT MUST COMPLY WITH THE SQUARE FOOTAGE ALLOWANCES
 FOR LOW FREE STANDING SIGNS WITHIN THE VILLAGE COMMONS
 COMMERCIAL PLANNED DEVELOPMENT.
  
 2) A MINOR PLANNED DEVELOPMENT AMENDMENT IS REQUIRED TO
 BE SUBMITTED TO AND APPROVED BY THE PLANNING DIVISION
 PRIOR TO THE ZONING APPROVAL OF THIS PERMIT. THE MINOR
 PLANNED DEVELOPMENT AMENDMENT MUST INCLUDE THE UPDATE
 TO THE SITE PLAN TO SHOW THE CHARGING STATIONS AND THE
 PARKING TABLE WITH THE REMOVAL OF THE TWO PARKING
 SPACES THAT WILL BE RESERVED FOR EV USE FROM THE TOTAL
 PARKING SPACES PROVIDED. ADDITIONALLY, THE LANDSCAPE
 PLAN MUST BE UPDATED TO SHOW THE CHARGING STATIONS.
  
 3) STAFF WILL NOT SUPPORT THE PLACEMENT OF THE CHARGING
 STATIONS AT THESE TWO PARKING SPACES. THEY HAVE
 HISTORICALLY BEEN DESIGNATED AS 15 MINUTE SPACES TO
 ALLOW FOR TO GO PICK UP FROM THE RESTAURANTS LOCATED
 WITHIN CLOSE DISTANCE TO THE SPACES.
  
 4) AFTER DISCUSSING THE REQUEST WITH THE CITY'S
 BUILDING OFFICIAL, YOU MAY NOT PROVIDE CHARGING
 STATIONS FOR REGULAR PARKING SPACES UNLESS YOU ALSO
 PROVIDE A CHARGING STATION FOR AN ADA PARKING SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  