Plan Review Details - Permit 20110528
Plan Review Stops For Permit 20110528
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By jwitmer Date 2020-11-17 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2020-11-17 Time 14:15 Sent To  
Notes
2020-11-17 14:28:05BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-25 Cont ID  
Sent By jleahy Date 2021-06-25 Time 12:52 Rev Time 0.00
Received By jleahy Date 2021-06-25 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-06-23 Cont ID  
Sent By jleahy Date 2021-06-23 Time 16:46 Rev Time 0.00
Received By jleahy Date 2021-06-23 Time 16:46 Sent To  
Notes
2021-06-23 16:47:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF ADDITIONAL ELECTRICAL WORK NOT ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 12:17 Rev Time 0.00
Received By jleahy Date 2020-12-04 Time 12:14 Sent To  
Notes
2020-12-04 12:20:17 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF ADDITIONAL ELECTRICAL WORK NOT SHOWN ON
 REVISION APPLICATION.
  
 2) YOU SHOW 2 MAINS OF THREE IS THE OTHER LOCATED IN
 SAME ROOM AS OTHRS? 230.71
  
 3) FPL CT CAN IS NOT USED FOR SPLICING OF CONDUCTORS,
 CONDUCTORS ARE TO BE CONTINUOUS THROUGH THE CT CAN. YOU
 MAY SET A GUTTER AFTER THE CT CAN FOR SLICING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By pleduc Date 2020-11-17 Time   Rev Time 0.00
Received By pleduc Date 2020-11-17 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-06-25 Time   Rev Time 0.00
Received By lmarchan Date 2021-06-11 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-04 Cont ID  
Sent By jleahy Date 2020-12-04 Time 12:20 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 14:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By medwards Date 2021-06-23 Time 09:00 Rev Time 0.00
Received By medwards Date 2021-06-23 Time 09:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By medwards Date 2020-11-20 Time 09:10 Rev Time 0.00
Received By medwards Date 2020-11-20 Time 08:31 Sent To  
Notes
2020-11-20 09:10:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110528
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1; PLEASE PROVIDE EXPLANATION FOR THE
 CHANGES. IS THE AHU-1 NOT BEING INSTALLED NOW? IF IT IS
 STILL BEING INSTALLED PLEASE INCLUDE IT IN THE REVISED
 DRAWINGS AS THIS DRAWING WOULD REPLACE THE OLD M1.1
 SHEET. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-06-25 Cont ID  
Sent By ccole Date 2021-06-25 Time 07:36 Rev Time 0.00
Received By ccole Date 2021-06-24 Time 16:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By ccole Date 2020-11-30 Time 17:24 Rev Time 0.00
Received By ccole Date 2020-11-30 Time 17:24 Sent To  
Notes
2020-11-30 17:24:411ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110528
 11/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: THE DRAINAGE FROM THE CHILLER SHALL NOT
 BE DISCHARGED INTO THE PLUMBING SYSTEM WITHOUT BEING
 THOROUGHLY DILUTED, NEUTRALIZED OR TREATED BY PASSING
 THROUGH AN APPROVED DILUTION OR NEUTRALIZING DEVICE-
 SEE SECTION 803.1 FBC P.
  
 2) P1.1: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE CHILLER- SECTIONS 608.3 FBC P.
  
 3) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-06-23 Cont ID  
Sent By medwards Date 2021-06-23 Time 09:06 Rev Time 0.00
Received By medwards Date 2021-06-23 Time 09:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-13 Cont ID  
Sent By equinone Date 2020-11-13 Time 13:28 Rev Time 0.00
Received By equinone Date 2020-11-13 Time 13:28 Sent To  
Notes
2020-11-13 13:29:43PAPER DRAWINGS HAVE ORIGINAL SEAL AND SIGNATURE. ROUTED
 TO STORAGE. EQ