Plan Review Details - Permit 20110495
Plan Review Stops For Permit 20110495
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-03-23 Cont ID  
Sent By pvalenti Date 2021-03-23 Time 15:13 Rev Time 0.00
Received By pvalenti Date 2021-03-23 Time 15:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-01-17 Cont ID  
Sent By jwitmer Date 2021-01-17 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2021-01-17 Time 13:46 Sent To  
Notes
2021-01-17 13:51:05COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-12-14 Cont ID  
Sent By jwitmer Date 2020-12-14 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2020-12-14 Time 12:40 Sent To  
Notes
2020-12-14 12:40:59COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By jwitmer Date 2020-11-18 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2020-11-18 Time 13:01 Sent To  
Notes
2020-11-18 14:32:00COMMERCIAL ASBESTOS
  
 TO THE BUILDING CONTRACTOR:
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-01-17 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2021-01-17 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2020-12-14 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2020-12-14 Time 12:39 Sent To  
Notes
2020-12-14 13:27:20WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110495
 ADD: 625 N. FLAGLER DR. / 10TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-615-3903 / MICHAEL MCCLOSKEY
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. DEC. 14TH/2020
 ACTION: BUILDING PROVISO:
  
 1) BUILDING PROVISO: WIND DESIGN DATA WILL BE SUBMITTED
 AT TIME OF PRODUCT APPROVALS AND SHOP DRAWING SHEETS.
 COMPOENTS & CLADDING. 2017 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) GATES, EXTERIOR DOORS, MULLIONS.
 (G) ROOFTOP PRE-ENGINEERED A/C STANDS
  
 W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 2) BUILDING PROVISO: THE ROOF TOP A/C STAND PRODUCT
 APPROVALS, TO BE REVIEWED BY THE DESIGNER OF RECORD.
 PLEASE IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING
 THE AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-18 Cont ID  
Sent By jwitmer Date 2020-11-18 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2020-11-18 Time 13:01 Sent To  
Notes
2020-11-18 14:29:53WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20110495
 ADD: 625 N. FLAGLER DR. / 10TH FLOOR
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-615-3903 / MICHAEL MCCLOSKEY
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. /NOV. 18TH/2020
 ACTION: DENIED
  
 1) SHEET A0.02 PLEASE INDICATE IF THERE IS ANY WORK TO
 BE COMPLETED UNDER THIS PERMIT FOR THE 1ST FLOOR, OR
 WAS IT SUBMITTED FOR LIFE SAFETY CONCERNS IN EXITING?
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. SHEET
 A1.10 GROUND FLOOR CONSTRUCTION NOTE ONE INDICATES A
 NEW ELECTRONIC ROLL-UP DOOR AND ACCESS CONTROL SYSTEM.
 WHAT THE 1ST FLOOR LIFE SAFETY PLAN DOES NOT SHOW IS
 HOW ONCE THE OCCUPANTS LEAVE THE 2 HOUR EXIT HOW THEY
 ARE GOING TO BE ABLE TO TRAVEL TO THE PUBLIC WAY? 2017
 FBC-B 1028.5 ACCESS TO A PUBLIC WAY.
  
 2) SHEET A0.03 LIFE SAFETY PLAN 10TH FLOOR SUITE: 1001:
  
 2A) UNDER THE HEADING CODE REQUIREMENTS THE LISTING
 EXIT ACCESS DOORWAYS, PLANS INDICATE 1 REQUIRED, 2
 PROVIDED AND SECTION TABLE 1006.2.1. PLEASE BE AWARE
 THAT TABLE 1006.2.1 IS TO BE USED FOR THE GRADE FLOOR
 ONLY. TABLE 1006.3.2(1) IS FOR R-2 OCCUPANCIES 1ST-3RD
 FLOOR, AND TABLE 1006.3.2(2) IS TO BE USED FOR LISTED
 OCCUPANCIES FOR STORIES FIRST FLOOR ABOVE OR BELOW
 GRADE PLANE AND THE 2ND STORY ABOVE GRADE PLANE. ALSO
 REVIEW SECTION 1006.3 OF THE 2017 FBC-BUILDING.
  
 2B) EXIT ACCESS TRAVEL IS FOUND IN TABLE 1017.2 OF THE
 2017 FBC-BUILDING. PLEASE UPDATE PLANS.
  
 3) SHEET A4.22 SHOWS THE PEDESTRIAN GATE AND ELECTRONIC
 OVERHEAD ROLL-UP GARAGE DOOR, BOTH OF THESE WOULD
 APPEAR TO NEED PRODUCT APPROVALS AS WELL AS WIND DESIGN
 PRESSURES. THERE ARE NO STRUCTURAL DETAILS OF HOW THE
 ROLL UP OVERHEAD DOOR IS TO BE ANCHORED FOR THE DOOR
 ASSEMBLY ITSELF NOR THE TRACK SYSTEM FOR THE DOOR TO
 MOVE IN VERTICALLY. THE SAME REQUIREMENTS ARE MISSING
 FOR THE PEDESTRIAN GATE. THE PEDESTRIAN GATE IS A ONE
 TYPE OF FABRICATION I WOULD BELIEVE AND WOULD ONLY
 REQUIRE THE ENGINEERING FOR THIS TYPE OF INSTALLATION
 AND EXPOSURE.
  
 3A) 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3B) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS.
  
 3C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3D) WITHOUT STRUCTURAL DETAILS FOR THE 2 NEW PRODUCTS
 DOOR OPENINGS THIS MAY OR MAY NOT BE REQUIRED.
 WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 11:23 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-17 Cont ID  
Sent By jleahy Date 2020-11-17 Time 17:37 Rev Time 0.00
Received By jleahy Date 2020-11-13 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2020-12-16 Cont ID  
Sent By jleahy Date 2020-12-16 Time 11:24 Rev Time 0.00
Received By jleahy Date 2020-12-16 Time 11:23 Sent To  
Notes
2020-12-16 11:24:29VOCE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By pleduc Date 2020-12-14 Time   Rev Time 0.00
Received By pleduc Date 2020-12-14 Time 12:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By pleduc Date 2020-11-18 Time   Rev Time 0.00
Received By pleduc Date 2020-11-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-11 Cont ID  
Sent By cpuell Date 2021-02-11 Time 10:17 Rev Time 0.00
Received By cpuell Date 2021-01-15 Time 15:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 13:49 Rev Time 0.00
Received By medwards Date 2020-12-10 Time 15:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By lcrespo Date 2020-11-20 Time 15:49 Rev Time 0.00
Received By lcrespo Date 2020-11-12 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-01-19 Cont ID  
Sent By medwards Date 2021-01-19 Time 07:35 Rev Time 0.00
Received By medwards Date 2021-01-19 Time 07:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-12-16 Cont ID  
Sent By medwards Date 2020-12-16 Time 13:48 Rev Time 0.00
Received By medwards Date 2020-12-16 Time 13:48 Sent To  
Notes
2020-12-16 13:48:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110495
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PROJECT SUMMARY FOR THE ENERGY CALCULATIONS HAS
 A TOTAL CONDITIONED AREA IS 110 SF. SHEET A0.03
 INDICATES THE AREA OF WORK IS 4226 SF. PLEASE PROVIDE A
 PROJECT SUMMARY FOR THE MECHANICAL SIZING CALCULATIONS
 BASED ON THE SF INDICATED ON SHEET A0.03. FBC 107.2.1
  
 2) SHEET M6.1: OUTDOOR AIR CALCULATIONS DO NOT MATCH
 TABLE 403.3.1.1. THE OFFICE SPACES ARE CALCULATED AT
 #/1000SQ.FT ( 4226\1000= 4.226 X 5 OCC. DENSITY = 21.13
 + 4226X.06= 253.56)
 21.13 + 253.56 = 274.69 CFM OF OUTDOOR AIR REQUIRED.
 FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By medwards Date 2020-11-17 Time 07:03 Rev Time 0.00
Received By medwards Date 2020-11-16 Time 16:16 Sent To  
Notes
2020-11-17 07:03:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110495
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT HEATING AND
 COOLING SIZING. FBC EC C403.2.1
  
 2) THE SQUARE FOOTAGE IS OFF ON SHEETS A0.03 AND M6.1.
 PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON THE
 ARCHITECTURAL SQUARE FOOTAGE AND THE OCCUPANT LOAD
 BASED ON THAT. FBC M 403.3.1.1
  
 3) PLEASE SHOW FIRE DAMPERS FOR THE RATED WALL
 PENETRATIONS OF THE EXISTING DUCTWORK. FBC M 607.5
  
 4) SHEET A0.03 INDICATES RATED WALLS AT ROOMS- O.FILES,
 S STORAGE AND WAITING. PLEASE SHOW FIRE DAMPERS AT EACH
 LOCATION THAT DUCT WORK PENETRATES THESE WALLS. FBC M
 607.5
  
 5) PLEASE SHOW FIRE DAMPERS IN ALL LOCATIONS WHERE THE
 DUCTWORK PENETRATES A RATED WALL. FBC M 607.5
  
 6) PROVIDE A MECHANICAL DEMO SHEET THAT INCLUDES THE
 EXISTING DUCTWORK SIZES. FBC 107.2
  
 7) AREA ABOVE CEILING IS CONSIDERED A PLENUM, PLEASES
 MAKE SURE ALL TRADES ARE AWARE. FBC M 602.2.1MATERIALS
 WITHIN PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.7, MATERIALS WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING
 A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By lcrespo Date 2020-12-14 Time 16:45 Rev Time 0.00
Received By lcrespo Date 2020-12-14 Time 16:45 Sent To  
Notes
2020-12-14 16:45:5712/14/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By lcrespo Date 2020-11-20 Time 15:48 Rev Time 0.00
Received By lcrespo Date 2020-11-20 Time 14:32 Sent To  
Notes
2020-11-20 15:49:0211/20/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SHEET A0.03 ROOM 1024 HAS A TOILET FACILITY WITH A
 LAV ON TOP OF THIS IS NOT AN APPROVED HANDICAP SETUP.
 PLEASE SHOW LAV AWAY FROM THE TOILET. PLEASE ALSO SHOW
 CLEAR FLOOR SPACE WITH DIMENSIONS ON ALL ACCESSIBLE
 FIXTURES (DRINKING FOUNTAIN, TOILET, SINK AS WELL PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 2. SHEET A0.05;
 A. THE SHOWER COMPARTMENT DETAIL TWO SHOWS A SEAT
 PLEASE PROVIDE BACKING DETAIL FOR IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. PLEASE PROVIDE DETAILS FOR ROOM 1024 TOILET FACILITY
 ACCESSIBLE DETAILS AND SHOW GRAB BARS, TOILET PAPER
 HOLDER, AND OTHER ACCESSIBLE ELEMENTS IN THAT ROOM,
 CLEAR FLOOR SPACE SHALL BE 60? INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDEWALL AND 56? INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE REAR WALL PER 2017 FBC
 ACC. SEC. 604.3.1.
  
 C. PLEASE SHOW TEMPERED WATER ON LAV AND IT SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS, AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
  
 3. SHEET P0.1;
 A. ISOMETRIC DRAWING THAT SHOWS FLOOR DRAIN WITH TRAP
 PRIMER IN THE SHOWER STALL PLEASE CHANGE AND DELETE
 TRAP PRIMER AND LABEL ACCORDINGLY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. ON THE WATER ISOMETRIC, THERE IS A LINE MISSING FOR
 THE ICE MAKER AND IT REQUIRES AN INLINE BACKFLOW DEVICE
 WITH ASSE 1024 PER THE 2017 FBC SEC. 608.13.10.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2021-01-17 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2021-01-17 Time 13:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-14 Cont ID  
Sent By jwitmer Date 2020-12-14 Time 13:29 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-18 Cont ID  
Sent By jwitmer Date 2020-11-18 Time 14:28 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-02-10 Cont ID  
Sent By aaponte Date 2021-02-10 Time 18:51 Rev Time 0.00
Received By aaponte Date 2021-02-10 Time 18:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-11-13 Cont ID  
Sent By aaponte Date 2020-11-13 Time 16:58 Rev Time 0.00
Received By aaponte Date 2020-11-13 Time 16:58 Sent To  
Notes
2020-11-13 17:00:12PLEASE CLARIFY THE PROPOSED USED FOR THE AREA OF THE
 GROUND FLOOR INCLUDED IN THE SCOPE OF WORK. DRAWINGS
 INDICATE PARKING BUT NO SPACES STRIPED.
 FOR ADDITINAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.