2020-11-25 09:09:51 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20110461 |
| 11/25/20 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 1A/B SANITARY RISER: |
| |
| A) THE WET VENTING SYSTEMS FOR THE GUEST HOUSE BATH AND |
| BATHS 2 & 3 ARE NOT IN COMPLIANCE WITH SECTION |
| P3108.2.1- NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN |
| SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE |
| DRAIN CONNECTION. |
| |
| B) WASHER: SHOW A 2 IN. FIXTURE DRAIN CONNECTING TO A 3 |
| IN. VERTICAL STACK- SECTION 406.2 FBC P. |
| |
| 2) SHOW THE LOCATIONS OF THE WASHER SHUT OFF VALVES AND |
| INDICATE THAT THEY WILL BE ACCESSIBLE PER SECTION |
| P2903.9.3 FBC RES. |
| |
| 3) WATER HEATER: THE ENERGY FORM R405-2017 INDICATES A |
| 40-GALLON NATURAL GAS WATER HEATER. SHOW THE LOCATION |
| OF THE WATER HEATER ON THE PLAN, PROVIDE AN EQUIPMENT |
| SCHEDULE AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| SECTION G2448.1 FBC RES. PLEASE NOTE A SEPARATE PERMIT |
| AND PLANS ARE REQUIRED FOR THE GAS PIPING TO THE WATER |
| HEATER AND ALL OTHER GAS FIRED APPLIANCES AND |
| EQUIPMENT- SECTIONS 105.1 AND 107.2.1 WPB. THE GAS |
| PLANS SHALL INCLUDE COMBUSTION AIR CALCULATIONS AND |
| VENTING PLANS FOR ALL GAS-FIRED APPLIANCES. |
| |
| 4) PROVIDE A WATER RISER- SECTION 107.3.5.3 WPB. |
| |
| 5) PROVIDE SHOWER PAN DETAILS- SECTION P2709.2 FBC RES. |
| |
| 6) BACKFLOW PREVENTER FOR POTABLE WATER SERVICE: PLEASE |
| NOTE A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC, |
| 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT. AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |