Plan Review Details - Permit 20110373
Plan Review Stops For Permit 20110373
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-12-08 Cont ID  
Sent By cthroop Date 2021-12-08 Time 05:48 Rev Time 0.00
Received By cthroop Date 2021-12-06 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-16 Cont ID  
Sent By cthroop Date 2021-08-16 Time 09:21 Rev Time 0.00
Received By cthroop Date 2021-08-16 Time 07:42 Sent To  
Notes
2021-08-16 09:27:12PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 NOTICE: VALUE WAS ADJUSTED FROM $80,000.00 TO
 $159,671.00 BASED ON THE ICC BUILDING VALUATION TABLES.
  
 NOTICE: PALM BEACH COUNTY IMPACT FEES MAY APPLY.
 (SUBMIT A PALM BEACH COUNTY IMPACT FEE QUESTIONAIRE)
  
 1. PROVIDE SURVEY/SITE DRAINAGE PLAN. (NOT ADDRESSED)
  
 PROVIDE A SITE PLAN/DRAINAGE PLAN/SURVEY
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3
  
 2. PROVIDE AN ENERGY SUBMITTAL. (NOT ADDRESSED)
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. STATE INSULATION R VALUES FOR CEILING, WALLS AND
 FLOOR ON PLANS. (NOT ADDRESSED)
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE THE
 FOLLOWING INFORMATION: CORRECTED
  
 5. PROVIDE ENGINEERING PLAN. (SEE NOTE ON FOUNDATION
 PLAN FOR FINISHED FLOOR) (NOT ADDRESSED)
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PROVIDE PRODUCT APPROVALS FOR SLIDING GLASS DOOR
 (SGD). (NOT ADDRESSED)
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By cthroop Date 2020-12-01 Time 14:19 Rev Time 0.00
Received By cthroop Date 2020-12-01 Time 11:12 Sent To  
Notes
2020-12-01 14:35:40PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE WAS ADJUSTED FROM $80,000.00 TO
 $159,671.00 BASED ON THE ICC BUILDING VALUATION TABLES.
  
 NOTICE: PALM BEACH COUNTY IMPACT FEES MAY APPLY.
  
 1. PROVIDE SURVEY/SITE DRAINAGE PLAN.
  
 PROVIDE A SITE PLAN/DRAINAGE PLAN/SURVEY
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
  
 FBC R401.3 SITE DRAINAGE
 PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3
  
 2. PROVIDE AN ENERGY SUBMITTAL.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. STATE INSULATION R VALUES FOR CEILING, WALLS AND
 FLOOR ON PLANS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE THE
 FOLLOWING INFORMATION:
  
 WINDOW SCHEDULE
 1. ITEM NUMBER/LOCATION ON
 PLAN/TYPE/MFGR./MATERIAL/GLASS/TREATMENT/ROUGH
 OPENING/IMPACT RESISTANT Y/N/PRODUCT APPROVAL
 NUMBER/NOA DESIGN PRESSURE RATING/OPENING
 REQUIRED/RESSURE RATING/EGRESS REQUIRED Y/N/SHUTTER
 REQUIRED Y/N
  
 DOOR SCHEDULE
 1. ITEM NUMBERLOCATION ON
 PLAN/SIZE/THICKNESS/TYPE/MFGR./MATERIAL/JAM/
 ROUGH OPENING/HARDWARE/NOA DESIGN PRESSURE
 RATING/OPENING REQUIRED/PRESSURE RATING/SHUTTER
 REQUIRED Y/N
  
 5. PROVIDE ENGINEERING PLAN. (SEE NOTE ON FOUNDATION
 PLAN FOR FINISHED FLOOR)
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PROVIDE PRODUCT APPROVALS FOR SLIDING GLASS DOOR
 (SGD).
  
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-08 Cont ID  
Sent By cthroop Date 2021-12-08 Time 05:48 Rev Time 0.00
Received By cthroop Date 2021-12-06 Time 09:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-08-16 Cont ID  
Sent By cthroop Date 2021-08-16 Time 09:48 Rev Time 0.00
Received By cthroop Date 2021-08-16 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-12-07 Cont ID  
Sent By cthroop Date 2020-12-07 Time 16:38 Rev Time 0.00
Received By cthroop Date 2020-12-07 Time 15:06 Sent To  
Notes
2020-12-07 16:56:03PLAN REVIEW / ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE LUMINAIRE AND OUTLET IN ATTIC FOR A/H.
 E3901.12 HVAC OUTLET. M1305.3.1.
  
 2. PROVIDE GFCI OUTLET AT 2ND FLOOR BALCONY.
 E3901.7 OUTDOOR OUTLETS.
  
 3. PROVIDE 2ND GROUND ROD AT SERVICE.
 RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A
 SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL
 GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN
 ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
 NEC 250.53(A)(2); FBC RE E3608.4
  
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS.
 LUMINAIRES: ENERGY CODE ? FBC EC C405.1, R404.1
 A NOTE ON PLANS WILL SUFFICE.
  
 5. PROVIDE COMPLIANCE: A NOTICE IS POSTED ON THE
 ELECTRIC SERVICE PANEL INDICATING TO THE HOMEOWNER THAT
 THE AIR HANDLER IS LOCATED IN THE ATTIC. SAID NOTICE
 SHALL BE IN ALL CAPITALS, IN 16-POINT TYPE, WITH THE
 TITLE AND FIRST PARAGRAPH IN BOLD:
 SECTION R405.
 A NOTE ON PLANS WILL SUFFICE.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-20 Cont ID  
Sent By ajones Date 2021-12-20 Time 14:32 Rev Time 0.00
Received By ajones Date 2021-12-20 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-17 Cont ID  
Sent By lmarchan Date 2021-12-17 Time 16:45 Rev Time 0.00
Received By lmarchan Date 2021-11-24 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-01 Cont ID  
Sent By lmarchan Date 2021-09-01 Time 08:45 Rev Time 0.00
Received By lmarchan Date 2021-08-04 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-01-14 Cont ID  
Sent By lmarchan Date 2021-01-14 Time 16:11 Rev Time 0.00
Received By lmarchan Date 2020-11-20 Time 07:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-12-22 Cont ID  
Sent By lmarchan Date 2021-12-22 Time 12:41 Rev Time 0.00
Received By lmarchan Date 2021-12-20 Time 14:45 Sent To  
Notes
2021-12-22 11:28:22RECEIPT MU-2021-059112 - $4783.30 PAID
2021-12-20 14:46:0712/20/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By cthroop Date 2020-12-01 Time 13:26 Rev Time 0.00
Received By cthroop Date 2020-12-01 Time 13:26 Sent To  
Notes
2020-12-01 13:27:12PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-11-29 Cont ID  
Sent By medwards Date 2021-11-29 Time 08:10 Rev Time 0.00
Received By medwards Date 2021-11-29 Time 08:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-19 Cont ID  
Sent By medwards Date 2021-08-19 Time 10:26 Rev Time 0.00
Received By medwards Date 2021-08-19 Time 10:26 Sent To  
Notes
2021-08-19 10:27:062ND REVIEW FBC-2020 MECHANICAL
 PERMIT-20110373
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT. FBC EC 101.5.1.1.2
  
 2) THIS PROJECT REQUIRES A MECHANICAL SUB PERMIT. NO
 MECHANICAL SUB PERMIT HAS BEEN APPLIED FOR. PLEASE
 EITHER HAVE A FLORIDA LICENSED ENGINEER DIGITALLY SIGN
 AND SEAL THE MECHANICAL DRAWING OR ONCE THE MECHANICAL
 SUB PERMIT IS APPLIED FOR THE MECHANICAL CONTRACTOR
 HOLDING THE PERMIT TO INSTALL THE SYSTEM FOR THIS
 PROJECT CAN PRINT AND SIGN THEIR NAME ON THE DRAWING.
 F.S. 417.003 (H)
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-12-01 Cont ID  
Sent By medwards Date 2020-12-01 Time 10:40 Rev Time 0.00
Received By medwards Date 2020-12-01 Time 08:05 Sent To  
Notes
2020-12-01 10:40:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110373
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) I CANNOT DO A MECHANICAL REVIEW ON THIS PROJECT
 UNTIL A THE ITEMS BELOW ARE SUBMITTED.
  
 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS
 PROJECT. FBC EC 101.5.1.1.2
  
 3) PLEASE PROVIDE THE MECHANICAL DRAWINGS SHOWING THE
 MECHANICAL SYSTEMS AND THE DUCT WORK. FBC 107.2.1
  
 4) PLEASE SHOW THE BATH EXHAUST FAN EXHAUST
 TERMINATIONS LOCATION.
  
 5) PLEASE PROVIDE THE CONDENSATION PIPING AND LOCATION
 OF DISCHARGE. FBC RES 1411.3
  
 6) PLEASE SHOW THE LOCATION AND ANCHORAGE OF THE
 CONDENSING UNITS ON THE MECHANICAL DRAWING. FBC RES
 M1307.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-11-30 Cont ID  
Sent By abelisle Date 2021-11-30 Time 18:05 Rev Time 0.00
Received By abelisle Date 2021-11-30 Time 17:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-08-10 Cont ID  
Sent By lcrespo Date 2021-08-10 Time 13:55 Rev Time 0.00
Received By lcrespo Date 2021-08-10 Time 13:55 Sent To  
Notes
2021-08-10 13:55:4608/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-11-30 Cont ID  
Sent By lcrespo Date 2020-11-30 Time 13:09 Rev Time 0.00
Received By lcrespo Date 2020-11-30 Time 13:09 Sent To  
Notes
2020-11-30 13:09:3611/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2021-08-16 Cont ID  
Sent By cthroop Date 2021-08-16 Time 09:33 Rev Time 0.00
Received By cthroop Date 2021-08-16 Time 07:43 Sent To  
Notes
2021-08-16 09:34:11PROVISO ON SHT. 11 OF 14. A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-12-01 Cont ID  
Sent By cthroop Date 2020-12-01 Time 13:50 Rev Time 0.00
Received By cthroop Date 2020-12-01 Time 11:12 Sent To  
Notes
2020-12-01 13:51:17PROVISO: A SEPERATE ROOFING PERMIT IS REQUIRED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-29 Cont ID  
Sent By medwards Date 2021-11-29 Time 08:10 Rev Time 0.00
Received By medwards Date 2021-11-29 Time 08:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-16 Cont ID  
Sent By cthroop Date 2021-08-16 Time 09:43 Rev Time 0.00
Received By cthroop Date 2021-08-16 Time 07:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-12-01 Cont ID  
Sent By cthroop Date 2020-12-01 Time 13:54 Rev Time 0.00
Received By cthroop Date 2020-12-01 Time 11:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2021-12-20 Cont ID  
Sent By ajones Date 2021-12-20 Time 14:32 Rev Time 0.00
Received By ajones Date 2021-12-20 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2021-12-16 Cont ID  
Sent By ajones Date 2021-12-16 Time 14:42 Rev Time 0.00
Received By ajones Date 2021-12-16 Time 14:42 Sent To  
Notes
2021-12-16 14:43:3912/16/21- FAILED. PLEASE PROVIDE A SITE PLAN/SURVEY
 INDICATING THE SETBACKS FROM THE PROPERTY LINE OF THE
 NEW ADDITION.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By kalexand Date 2021-08-31 Time 19:39 Rev Time 0.00
Received By kalexand Date 2021-08-31 Time 19:39 Sent To I
Notes
2021-08-31 19:40:47PREVIOUS ZONING COMMENTS NOT MET.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-01-11 Cont ID  
Sent By kalexand Date 2021-01-11 Time 13:35 Rev Time 0.00
Received By kalexand Date 2021-01-11 Time 13:35 Sent To I
Notes
2021-01-11 13:55:38ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE TWO (2) COPIES OF A CURRENT AND/OR SURVEY,
 WHICH INCLUDES THE PROPERTY'S ADDRESS AND LEGAL
 DESCRIPTION. PLEASE ILLUSTRATE THE FOLLOWING ON THE
 SURVEY AND/OR SITE PLAN:
 - LOCATION OF THE PROPOSED ADDITION.
 - INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. PURSUANT
 TO THE ZLDR, SECTION 94-72(A)(2): SINGLE-FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
  A. FRONT: 25 FEET;
  
  B. CORNER: 12.5 FEET;
  
  C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
  
  D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 2. AS THE TOTAL VALUE OF THE ADDITIONS EXCEEDS 50% OF
 THE IMPROVEMENT VALUE OF THE STRUCTURE, A LANDSCAPE
 PERMIT MUST BE SUBMITTED TO PLANNING AND ZONING
 DIVISION.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  