Plan Review Stops For Permit 20110373 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2021-12-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-12-08 |
Time |
05:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-12-06 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2021-08-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-16 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-16 |
Time |
07:42 |
Sent To |
|
|
Notes |
2021-08-16 09:27:12 | PLAN REVIEW / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | PREVIOUS COMMENTS. | | | | | | NOTICE: VALUE WAS ADJUSTED FROM $80,000.00 TO | | $159,671.00 BASED ON THE ICC BUILDING VALUATION TABLES. | | | | NOTICE: PALM BEACH COUNTY IMPACT FEES MAY APPLY. | | (SUBMIT A PALM BEACH COUNTY IMPACT FEE QUESTIONAIRE) | | | | 1. PROVIDE SURVEY/SITE DRAINAGE PLAN. (NOT ADDRESSED) | | | | PROVIDE A SITE PLAN/DRAINAGE PLAN/SURVEY | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | | | FBC R401.3 SITE DRAINAGE | | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH | | FBC R401.3 | | | | 2. PROVIDE AN ENERGY SUBMITTAL. (NOT ADDRESSED) | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 3. STATE INSULATION R VALUES FOR CEILING, WALLS AND | | FLOOR ON PLANS. (NOT ADDRESSED) | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 4. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE THE | | FOLLOWING INFORMATION: CORRECTED | | | | 5. PROVIDE ENGINEERING PLAN. (SEE NOTE ON FOUNDATION | | PLAN FOR FINISHED FLOOR) (NOT ADDRESSED) | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 6. PROVIDE PRODUCT APPROVALS FOR SLIDING GLASS DOOR | | (SGD). (NOT ADDRESSED) | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-01 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-01 |
Time |
11:12 |
Sent To |
|
|
Notes |
2020-12-01 14:35:40 | PLAN REVIEW / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | NOTICE: VALUE WAS ADJUSTED FROM $80,000.00 TO | | $159,671.00 BASED ON THE ICC BUILDING VALUATION TABLES. | | | | NOTICE: PALM BEACH COUNTY IMPACT FEES MAY APPLY. | | | | 1. PROVIDE SURVEY/SITE DRAINAGE PLAN. | | | | PROVIDE A SITE PLAN/DRAINAGE PLAN/SURVEY | | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED | | WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY | | A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF | | NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED BOUNDARY LINE SURVEY. | | | | FBC R401.3 SITE DRAINAGE | | PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH | | FBC R401.3 | | | | 2. PROVIDE AN ENERGY SUBMITTAL. | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | 3. STATE INSULATION R VALUES FOR CEILING, WALLS AND | | FLOOR ON PLANS. | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 4. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE THE | | FOLLOWING INFORMATION: | | | | WINDOW SCHEDULE | | 1. ITEM NUMBER/LOCATION ON | | PLAN/TYPE/MFGR./MATERIAL/GLASS/TREATMENT/ROUGH | | OPENING/IMPACT RESISTANT Y/N/PRODUCT APPROVAL | | NUMBER/NOA DESIGN PRESSURE RATING/OPENING | | REQUIRED/RESSURE RATING/EGRESS REQUIRED Y/N/SHUTTER | | REQUIRED Y/N | | | | DOOR SCHEDULE | | 1. ITEM NUMBERLOCATION ON | | PLAN/SIZE/THICKNESS/TYPE/MFGR./MATERIAL/JAM/ | | ROUGH OPENING/HARDWARE/NOA DESIGN PRESSURE | | RATING/OPENING REQUIRED/PRESSURE RATING/SHUTTER | | REQUIRED Y/N | | | | 5. PROVIDE ENGINEERING PLAN. (SEE NOTE ON FOUNDATION | | PLAN FOR FINISHED FLOOR) | | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | 107.2.5. | | | | 6. PROVIDE PRODUCT APPROVALS FOR SLIDING GLASS DOOR | | (SGD). | | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2021-12-08 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-12-08 |
Time |
05:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-12-06 |
Time |
09:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2021-08-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-16 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-16 |
Time |
07:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2020-12-07 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-07 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-07 |
Time |
15:06 |
Sent To |
|
|
Notes |
2020-12-07 16:56:03 | PLAN REVIEW / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2014 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVIDE LUMINAIRE AND OUTLET IN ATTIC FOR A/H. | | E3901.12 HVAC OUTLET. M1305.3.1. | | | | 2. PROVIDE GFCI OUTLET AT 2ND FLOOR BALCONY. | | E3901.7 OUTDOOR OUTLETS. | | | | 3. PROVIDE 2ND GROUND ROD AT SERVICE. | | RISER DIAGRAM SHOWS A SINGLE GROUND ROD AS A | | SUPPLEMENTAL GROUNDING ELECTRODE. THIS SUPPLEMENTAL | | GROUNDING ELECTRODE NEEDS TO BE AUGMENTED BY AN | | ADDITIONAL ELECTRODE AT LEAST 6 FEET AWAY OR PROVIDE | | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. | | NEC 250.53(A)(2); FBC RE E3608.4 | | | | 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS. | | LUMINAIRES: ENERGY CODE ? FBC EC C405.1, R404.1 | | A NOTE ON PLANS WILL SUFFICE. | | | | 5. PROVIDE COMPLIANCE: A NOTICE IS POSTED ON THE | | ELECTRIC SERVICE PANEL INDICATING TO THE HOMEOWNER THAT | | THE AIR HANDLER IS LOCATED IN THE ATTIC. SAID NOTICE | | SHALL BE IN ALL CAPITALS, IN 16-POINT TYPE, WITH THE | | TITLE AND FIRST PARAGRAPH IN BOLD: | | SECTION R405. | | A NOTE ON PLANS WILL SUFFICE. | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | REVIEWED SHEETS DETACHED. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2021-12-20 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-12-20 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-12-20 |
Time |
09:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2021-12-17 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-12-17 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-11-24 |
Time |
15:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2021-09-01 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-09-01 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-08-04 |
Time |
10:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2021-01-14 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-01-14 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2020-11-20 |
Time |
07:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2021-12-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2021-12-22 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2021-12-20 |
Time |
14:45 |
Sent To |
|
|
Notes |
2021-12-22 11:28:22 | RECEIPT MU-2021-059112 - $4783.30 PAID | 2021-12-20 14:46:07 | 12/20/21 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-01 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-01 |
Time |
13:26 |
Sent To |
|
|
Notes |
2020-12-01 13:27:12 | PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2021-11-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-11-29 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-11-29 |
Time |
08:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2021-08-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-08-19 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-08-19 |
Time |
10:26 |
Sent To |
|
|
Notes |
2021-08-19 10:27:06 | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-20110373 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS | | PROJECT. FBC EC 101.5.1.1.2 | | | | 2) THIS PROJECT REQUIRES A MECHANICAL SUB PERMIT. NO | | MECHANICAL SUB PERMIT HAS BEEN APPLIED FOR. PLEASE | | EITHER HAVE A FLORIDA LICENSED ENGINEER DIGITALLY SIGN | | AND SEAL THE MECHANICAL DRAWING OR ONCE THE MECHANICAL | | SUB PERMIT IS APPLIED FOR THE MECHANICAL CONTRACTOR | | HOLDING THE PERMIT TO INSTALL THE SYSTEM FOR THIS | | PROJECT CAN PRINT AND SIGN THEIR NAME ON THE DRAWING. | | F.S. 417.003 (H) | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2020-12-01 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2020-12-01 |
Time |
08:05 |
Sent To |
|
|
Notes |
2020-12-01 10:40:52 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT-20110373 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) I CANNOT DO A MECHANICAL REVIEW ON THIS PROJECT | | UNTIL A THE ITEMS BELOW ARE SUBMITTED. | | | | 2) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THIS | | PROJECT. FBC EC 101.5.1.1.2 | | | | 3) PLEASE PROVIDE THE MECHANICAL DRAWINGS SHOWING THE | | MECHANICAL SYSTEMS AND THE DUCT WORK. FBC 107.2.1 | | | | 4) PLEASE SHOW THE BATH EXHAUST FAN EXHAUST | | TERMINATIONS LOCATION. | | | | 5) PLEASE PROVIDE THE CONDENSATION PIPING AND LOCATION | | OF DISCHARGE. FBC RES 1411.3 | | | | 6) PLEASE SHOW THE LOCATION AND ANCHORAGE OF THE | | CONDENSING UNITS ON THE MECHANICAL DRAWING. FBC RES | | M1307.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2021-11-30 |
|
|
Cont ID |
|
Sent By |
abelisle |
Date |
2021-11-30 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
abelisle |
Date |
2021-11-30 |
Time |
17:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2021-08-10 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2021-08-10 |
Time |
13:55 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2021-08-10 |
Time |
13:55 |
Sent To |
|
|
Notes |
2021-08-10 13:55:46 | 08/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2020-11-30 |
|
|
Cont ID |
|
Sent By |
lcrespo |
Date |
2020-11-30 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
lcrespo |
Date |
2020-11-30 |
Time |
13:09 |
Sent To |
|
|
Notes |
2020-11-30 13:09:36 | 11/30/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | AVOID VOIDING OF THE PERMIT. | | | | LUIS A. CRESPO | | PLUMBING PLAN EXAMINER / INSPECTOR | | EMAIL: [email protected] OFFICE: 561 805-6720 | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
N |
Date |
2021-08-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-16 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-16 |
Time |
07:43 |
Sent To |
|
|
Notes |
2021-08-16 09:34:11 | PROVISO ON SHT. 11 OF 14. A SEPERATE ROOFING PERMIT IS | | REQUIRED. CT |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-01 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-01 |
Time |
11:12 |
Sent To |
|
|
Notes |
2020-12-01 13:51:17 | PROVISO: A SEPERATE ROOFING PERMIT IS REQUIRED. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2021-11-29 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2021-11-29 |
Time |
08:10 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2021-11-29 |
Time |
08:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2021-08-16 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2021-08-16 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2021-08-16 |
Time |
07:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2020-12-01 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2020-12-01 |
Time |
13:54 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2020-12-01 |
Time |
11:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2021-12-20 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-12-20 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-12-20 |
Time |
14:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2021-12-16 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2021-12-16 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2021-12-16 |
Time |
14:42 |
Sent To |
|
|
Notes |
2021-12-16 14:43:39 | 12/16/21- FAILED. PLEASE PROVIDE A SITE PLAN/SURVEY | | INDICATING THE SETBACKS FROM THE PROPERTY LINE OF THE | | NEW ADDITION. | | | | ANGELLA VANN | | 561-822-1441 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2021-08-31 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-08-31 |
Time |
19:39 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-08-31 |
Time |
19:39 |
Sent To |
I |
|
Notes |
2021-08-31 19:40:47 | PREVIOUS ZONING COMMENTS NOT MET. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2021-01-11 |
|
|
Cont ID |
|
Sent By |
kalexand |
Date |
2021-01-11 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
kalexand |
Date |
2021-01-11 |
Time |
13:35 |
Sent To |
I |
|
Notes |
2021-01-11 13:55:38 | ZONING PLAN REVIEW | | ________________________________________ | | | | DATE OF REVIEW: | | ________________________________________ | | | | REVIEW STATUS: FAILED | | ________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PROVIDE TWO (2) COPIES OF A CURRENT AND/OR SURVEY, | | WHICH INCLUDES THE PROPERTY'S ADDRESS AND LEGAL | | DESCRIPTION. PLEASE ILLUSTRATE THE FOLLOWING ON THE | | SURVEY AND/OR SITE PLAN: | | - LOCATION OF THE PROPOSED ADDITION. | | - INDICATE THE SETBACK DIMENSIONS FROM ANY EXTERIOR | | IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. PURSUANT | | TO THE ZLDR, SECTION 94-72(A)(2): SINGLE-FAMILY LOW | | DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM SETBACKS | | FOR PRINCIPAL BUILDING ARE AS FOLLOWS: | | | | A. FRONT: 25 FEET; | | | | B. CORNER: 12.5 FEET; | | | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, | | WHICHEVER IS LESS; | | | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | 2. AS THE TOTAL VALUE OF THE ADDITIONS EXCEEDS 50% OF | | THE IMPROVEMENT VALUE OF THE STRUCTURE, A LANDSCAPE | | PERMIT MUST BE SUBMITTED TO PLANNING AND ZONING | | DIVISION. | | | | ________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD | | LIKE TO RESUBMIT ELECTRONICALLY, EMAIL | | [email protected] AND REQUEST TO HAVE YOUR | | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG | | IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. | | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU | | ARE FINISHED UPLOADING. | | ________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | KIZZI ALEXANDRE, ASSOCIATE PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1442 | | TTY: 800.955.8771 | | E: [email protected] | | | | W: WPB.ORG | | |
|
|