Plan Review Details - Permit 20110336
Plan Review Stops For Permit 20110336
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By cpuell Date 2020-11-20 Time 09:30 Rev Time 0.00
Received By cpuell Date 2020-11-20 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-14 Cont ID  
Sent By cthroop Date 2021-01-14 Time 13:14 Rev Time 0.00
Received By cthroop Date 2021-01-14 Time 10:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-26 Cont ID  
Sent By cthroop Date 2020-12-26 Time 08:15 Rev Time 0.00
Received By cthroop Date 2020-12-21 Time 10:11 Sent To  
Notes
2020-12-26 08:21:53PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. ROOF FRAMING PLAN - PROVIDE TRUSS AND GIRDER LAYOUT,
 PROVIDE UPLIFT AT ALL BEARING POINTS, SPECIFY
 CONNECTORS FOR EACH TRUSS AND GIRDER.
  
 2. PROVIDE WIND DESIGN PRESSURES FOR EACH ROOF ZONE
 WITH FASTENER TYPE AND SPACING FOR EACH ZONE.
  
 3. CONSTRUCTION TYPE ON PLAN PAGE 3 OF 19 STATES TYPE
 IIB. THIS STRUCTURE IS TYPE VB.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 10:02 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
2020-11-30 10:08:59PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: THE VALUE HAS BEEN ADJUSTED FROM $575,000 TO
 $728,377 BASED ON THE ICC BUILDING VALUATION TABLES.
  
 1. ROOF FRAMING PLAN - PROVIDE TRUSS LAYOUT, BEARING
 POINTS, WIND LOAD DESIGN PRESSURES AND FASTENER
 SCHEDULE.
  
 2. PROVIDE A WINDOW AND DOOR SCHEDULE. INCLUDE ITEM
 NUMBER WITH REFERENCE TO PLAN, ROUGH OPENING, AND
 DESIGN PRESSURES FOR EACH OPENING.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By cthroop Date 2020-12-21 Time 14:55 Rev Time 0.00
Received By cthroop Date 2020-12-21 Time 10:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 11:33 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
2020-11-30 11:35:33PLAN REVIEW / ELECTRIC
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AIC: - N/A
  
 2. SMOKE DETECTORS ARE MISSING ON 1ST FLOOR.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. 1.IN EACH SLEEPING ROOM.
 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE
 IMMEDIATE VICINITY OF THE BEDROOMS.
 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING,
 INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT
 INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN
 DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND
 WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT
 LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL
 SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED
 THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW
 THE UPPER LEVEL.
 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3
 FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF
 A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS
 THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED
 BY SECTION R314.3
  
 3. PROVIDE CARBON MONOXIDE DETECTORS:
  
 R314.5 COMBINATION ALARMS.
 COMBINATION SMOKE AND CARBON MONOXIDE ALARMS SHALL BE
 PERMITTED TO BE USED IN LIEU OF SMOKE ALARMS.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 4. HIGH EFFICACY LAMPS
  
 PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS".
  
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 5. PROVIDE GFCI OUTLET AT REAR OF STRUCTURE.
  
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
  
 6. RE: RISER DIAGRAHM - PANELS A AND B:
  
 E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR.
 AN EQUIPMENT GROUNDING CONDUCTOR AS DESCRIBED IN
 SECTION E3908 SHALL BE RUN WITH THE SUPPLY CONDUCTORS
 AND CONNECTED TO THE BUILDING OR STRUCTURE
 DISCONNECTING MEANS AND TO THE GROUNDING ELECTRODE(S).
 THE EQUIPMENT GROUNDING CONDUCTOR SHALL BE USED FOR
 GROUNDING OR BONDING OF EQUIPMENT, STRUCTURES OR FRAMES
 REQUIRED TO BE GROUNDED OR BONDED. THE EQUIPMENT
 GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH
 SECTION E3908.12. ANY INSTALLED GROUNDED CONDUCTOR
 SHALL NOT BE CONNECTED TO THE EQUIPMENT GROUNDING
 CONDUCTOR OR TO THE GROUNDING ELECTRODE(S). [250.32(B)
 AND TABLE 250.122]
  
 1ST MEANS OF DISCONNECT
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
 THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONNECTED TO
 THE GROUNDED SERVICE CONDUCTOR AT ANY ACCESSIBLE POINT
 FROM THE LOAD END OF THE OVERHEAD SERVICE CONDUCTORS,
 SERVICE DROP, UNDERGROUND SERVICE CONDUCTORS, OR
 SERVICE LATERAL TO AND INCLUDING THE TERMINAL OR BUS TO
 WHICH THE GROUNDED SERVICE CONDUCTOR IS CONNECTED AT
 THE SERVICE DISCONNECTING MEANS. A GROUNDING CONNECTION
 SHALL NOT BE MADE TO ANY GROUNDED CIRCUIT CONDUCTOR ON
 THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS,
 EXCEPT AS PROVIDED IN SECTION E3607.3.2. [250.24(A)(1)
 AND (A)(5)] NEC 250.24 (A)
  
 7. PROVIDE CIRCUT FOR T/W/H IGNITER CIRCUTS.
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
  
 8. PROVIDE INTERSYSTEM BONDING TERMINAL.
  
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status N Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 13:24 Rev Time 0.00
Received By cthroop Date 2020-11-30 Time 06:13 Sent To  
Notes
2020-11-30 13:25:23NO LV PLAN PROVIDED FOR REVIEW. CT

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 09:30 Rev Time 0.00
Received By cthroop Date 2020-11-25 Time 08:38 Sent To  
Notes
2020-11-30 09:37:41PLAN REVIEW / FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: N/A
 ADDRESS THE ATTACHED COMMENTS AND SUBMIT FUEL GAS
 PERMIT APPLICATION
  
 NO FUEL GAS REVIEW PERFORMED AT THIS TIME.
  
 1. SEPARATE GAS PERMIT REQUIRED
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING AND
 GAS APPLIANCE INSTALLATIONS.
 PROVIDE A COMPLETE SET OF PLANS AND PRODUCT SUBMITTALS.
 INCLUDE A GAS RISER DRAWING, COMBUSTION AIR
 CALCULATIONS AND VENTING DIAGRAMS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-14 Cont ID  
Sent By cthroop Date 2021-01-14 Time 13:14 Rev Time 0.00
Received By cthroop Date 2021-01-04 Time 17:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 14:26 Rev Time 0.00
Received By cpuell Date 2020-12-18 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-12-03 Cont ID  
Sent By jleahy Date 2020-12-03 Time 09:42 Rev Time 0.00
Received By jleahy Date 2020-11-19 Time 16:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-01-27 Cont ID  
Sent By lmarchan Date 2021-01-27 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2021-01-14 Time 14:30 Sent To  
Notes
2021-01-27 09:55:49RECEIPT MU-2021-003341 - $22.46 - PAID
2021-01-14 14:30:191/14/21 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 10:05 Rev Time 0.00
Received By cthroop Date 2020-11-25 Time 10:05 Sent To  
Notes
2020-11-25 10:06:23PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 07:18 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 10:22 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
2020-11-30 11:28:19PLAN REVIEW / MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PROVIDE ENGINEERING FOR INSTALLATION OF THE CONDENSER
 PAD AND MOUNTING OF THE CONDENSER- SECTIONS
 M1305.1.4.1, M1307.2 AND M1401.4 FBC RES.
  
 M1305.1.4.1 GROUND CLEARANCE.
 EQUIPMENT AND APPLIANCES SUPPORTED FROM THE GROUND
 SHALL BE LEVEL AND FIRMLY SUPPORTED ON A CONCRETE SLAB
 OR OTHER APPROVED MATERIAL EXTENDING NOT LESS THAN 3
 INCHES (76 MM) ABOVE THE ADJOINING GROUND. SUCH SUPPORT
 SHALL BE IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. APPLIANCES SUSPENDED FROM
 THE FLOOR SHALL HAVE A CLEARANCE OF NOT LESS THAN 6
 INCHES (152 MM) FROM THE GROUND.
  
 2. PROVIDE DETAIL FOR BATHROOM EXHAUST FANS
  
 M1507.2RECIRCULATION OF AIR.
 EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT
 BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER
 DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS
 SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE OR OTHER
 AREAS INSIDE THE BUILDING.
  
 3. PROVIDE LOCKING FREON PORTS.
  
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
  
 4. PROVIDE KITCHEN RANGE EXHAIUST HOOD SPECIFICATIONS.
  
 M1503.3 KITCHEN EXHAUST RATES.
 WHERE DOMESTIC KITCHEN COOKING APPLIANCES ARE EQUIPPED
 WITH DUCTED RANGE HOODS OR DOWN-DRAFT EXHAUST SYSTEMS,
 THE FANS SHALL BE SIZED IN ACCORDANCE WITH SECTION
 M1507.4.
  
 5. PROVIDE RANGE HOOD EXHAUST DETAIL.
  
 M1501.1OUTDOOR DISCHARGE.
 THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL BE DISCHARGED TO THE OUTDOORS IN ACCORDANCE WITH
 SECTION M1506.3. AIR SHALL NOT BE EXHAUSTED INTO AN
 ATTIC, SOFFIT, RIDGE VENT OR CRAWL SPACE.
  
 6. PROVIDE DETAIL FOR A/C CONDENSATE DISPOSAL.
  
 M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-26 Cont ID  
Sent By cthroop Date 2020-12-26 Time 07:15 Rev Time 0.00
Received By cthroop Date 2020-12-21 Time 10:11 Sent To  
Notes
2020-12-26 07:16:17PROVISO: SEPERATE PERMIT REQUIRED FOR BACKFLOW
 PREVENTER. CT

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-11-30 Cont ID  
Sent By cthroop Date 2020-11-30 Time 13:27 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
2020-11-30 13:37:50PLAN REVIEW / PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROVIDE A PLUMBING PLAN.
  
 1. COMPLETE
  
 2. PROVIDE SHOWER PAN DETAIL.
  
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
 WHERE A SHOWER RECEPTOR HAS A FINISHED CURB THRESHOLD,
 IT SHALL BE NOT LESS THAN 1 INCH (25 MM) BELOW THE
 SIDES AND BACK OF THE RECEPTOR. THE CURB SHALL BE NOT
 LESS THAN 2 INCHES (51 MM) AND NOT MORE THAN 9 INCHES
 (229 MM) DEEP WHEN MEASURED FROM THE TOP OF THE CURB TO
 THE TOP OF THE DRAIN. THE FINISHED FLOOR SHALL SLOPE
 UNIFORMLY TOWARD THE DRAIN NOT LESS THAN 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) NOR
 MORE THAN 1/2 UNIT VERTICAL PER 12 UNITS HORIZONTAL
 (4-PERCENT SLOPE) AND FLOOR DRAINS SHALL BE FLANGED TO
 PROVIDE A WATER-TIGHT JOINT IN THE FLOOR.
 P2709.3 SHOWER PAN LINING INSTALLATION.
 LINING MATERIALS SHALL BE SLOPED ONE FOURTH UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) TO
 WEEP HOLES IN THE SUBDRAIN BY MEANS OF A SMOOTH,
 SOLIDLY FORMED SUBBASE, SHALL BE PROPERLY RECESSED AND
 FASTENED TO APPROVED BACKING SO AS NOT TO OCCUPY THE
 SPACE REQUIRED FOR THE WALL COVERING, AND SHALL NOT BE
 NAILED OR PERFORATED AT ANY POINT LESS THAN 1 INCH
 (25.4 MM) ABOVE THE FINISHED THRESHOLD.
  
 P2708.4SHOWER CONTROL VALVES. INDIVIDUAL SHOWER AND
 TUB/ SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH
 CONTROL VALVES OF THE PRESSURE-BALANCE,
 THERMOSTATIC-MIXING OR COMBINATION
 PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE TYPES WITH A
 HIGH LIMIT STOP IN ACCORDANCE WITH ASSE 1016/ASME
 A112.1016/CSA B125.16. THE HIGH LIMIT STOP SHALL BE SET
 TO LIMIT THE WATER TEMPERATURE TO NOT GREATER THAN
 120?F (49?C). IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 USED FOR COMPLIANCE WITH THIS SECTION.
  
 3. SHOW LOCATION OF HOSE BIBS ON FLOOR PLAN.
  
 P2903.10HOSE BIBB.
  
 HOSE BIBBS SUBJECT TO FREEZING, INCLUDING THE
 ?FROSTPROOF? TYPE, SHALL BE EQUIPPED WITH AN ACCESSIBLE
 STOP-AND-WASTE-TYPE VALVE INSIDE THE BUILDING SO THAT
 THEY CAN BE CONTROLLED AND DRAINED DURING COLD PERIODS.
  
 4.PROVIDE BACKFLOW PREVENTER.
  
 BACKFLOW PREVENTER FOR IRRIGATION AND MAIN SERVICE
 REQUIRED PER THE CITY OF WEST PALM BEACH ORD #2853-95.
 A PERMIT REQUIRED BY A LICENSED CONTRACTOR AND MUST BE
 CERTIFIED BY UTILITIES PRIOR TO FINAL INSPECTION.
 PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240
 FOR FURTHER DIRECTIONS.
  
 P2902.3BACKFLOW PROTECTION.
 A MEANS OF PROTECTION AGAINST BACKFLOW SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTIONS P2902.3.1 THROUGH
 P2902.3.6. BACKFLOW PREVENTION APPLICATIONS SHALL
 CONFORM TO TABLE P2902.3, EXCEPT AS SPECIFICALLY STATED
 IN SECTIONS P2902.4 THROUGH P2902.5.5.
  
 5. PROVIDE WATER HAMMER DETAIL.
  
 P2903.5WATER HAMMER.
  
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 10:06 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-14 Cont ID  
Sent By cthroop Date 2021-01-14 Time 13:14 Rev Time 0.00
Received By cthroop Date 2021-01-14 Time 10:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By medwards Date 2020-12-21 Time 07:22 Rev Time 0.00
Received By medwards Date 2020-12-21 Time 07:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-25 Cont ID  
Sent By cthroop Date 2020-11-25 Time 10:06 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 06:26 Sent To  
Notes
2020-11-25 10:07:40PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: MECHANICAL PLANS
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-01-13 Cont ID  
Sent By awooten Date 2021-01-13 Time   Rev Time 0.00
Received By awooten Date 2021-01-13 Time   Sent To  
Notes
2021-01-13 12:14:35**********ZONING***************
  
 CUSTOMER SUBMITTED A CONDITIONAL LANDSCAPE APPROVAL
 FORM.
  
 ******ZONING PROVISO******
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE
 PLAN, SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR
 REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
2021-01-07 15:27:49**********ZONING PLAN REVIEW FAILED************
  
 LANDSCAPING IS REQUIRED FOR ALL NEW SINGLE FAMILY
 RESIDENTIAL DEVELOPMENT. PROVIDE A SEPARATE LANDSCAPE
 AND IRRIGATION PLAN SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ADDITIONAL PERMITS WILL BE REQUIRED FOR FENCES, PAVING,
 POOL, GENERATOR, DRIVEWAY, MECHANICAL EQUIPMENT,
 LANDSCAPING AND IRRIGATION.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2020-12-28 Time   Rev Time 0.00
Received By   Date 2020-12-28 Time   Sent To  
Notes
2020-12-28 16:32:54**********ZONING PLAN REVIEW FAILED************(REPEAT
 COMMENTS)
  
 LANDSCAPING IS REQUIRED FOR ALL NEW SINGLE FAMILY
 RESIDENTIAL DEVELOPMENT. PROVIDE A SEPARATE LANDSCAPE
 AND IRRIGATION PLAN SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-02 Cont ID  
Sent By awooten Date 2020-12-02 Time   Rev Time  
Received By awooten Date 2020-12-02 Time   Sent To  
Notes
2020-12-02 15:49:43**********ZONING PLAN REVIEW FAILED************
  
 LANDSCAPING IS REQUIRED FOR ALL NEW SINGLE FAMILY
 RESIDENTIAL DEVELOPMENT. PROVIDE A SEPARATE LANDSCAPE
 AND IRRIGATION PLAN SHOWING THE FOLLOWING:
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]