Plan Review Details - Permit 20110273
Plan Review Stops For Permit 20110273
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By jwitmer Date 2021-01-04 Time 15:12 Rev Time 0.00
Received By jwitmer Date 2021-01-04 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-12-16 Cont ID  
Sent By jwitmer Date 2020-12-16 Time 12:31 Rev Time  
Received By jwitmer Date 2020-12-16 Time 11:30 Sent To  
Notes
2020-12-16 12:29:57WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 20110273
 W. P. B. PERMIT: 20050017
 ADD: 2218 S DIXIE HWY.
 CONT: MARION CONSTRUCTION INC.
 TEL: 561-324-3163 / WES PARRISH
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 16TH/ 2020
 ACTION: DENIED
  
 1) THIS REVISION INCLUDES 10 SETS OF WINDOWS AND DOORS,
 MANY INCLUDE 3 INDIVIDUAL PANES OF GLASS WITHIN THE
 WINDOW OPENING. THE VALUE OF THE TOTAL REVISION
 SUBMITTED IS FOR $15,000.00 DOLLARS THAT WOULD NOT EVEN
 COVER THE COST OF THE WINDOWS, LABOR, MATERIALS AND
 OVERHEAD, THE VALUE SUBMITTED IS EXTREMELY LOW.
 109.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) THE SUBMITTED SHOP DRAWING BY THOMAS J. TWOMEY P. E.
 NONE OF THE 11 PAGES ARE SIGNED AND SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-12-15 Cont ID  
Sent By jleahy Date 2020-12-15 Time 08:08 Rev Time 0.00
Received By jleahy Date 2020-12-15 Time 08:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-12-10 Cont ID  
Sent By pleduc Date 2020-12-10 Time   Rev Time 0.00
Received By pleduc Date 2020-12-10 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-01-04 Time 15:14 Rev Time 0.00
Received By lcrespo Date 2020-12-21 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-12-16 Time 12:33 Rev Time 0.00
Received By lmarchan Date 2020-12-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-12-10 Cont ID  
Sent By medwards Date 2020-12-10 Time 11:22 Rev Time 0.00
Received By hmoser Date 2020-12-10 Time 10:23 Sent To  
Notes
2020-12-10 11:22:46PASS PROVISO
 REFER TO SECTION 606.2.1 DUCT DETECTORS REQUIRED
 IN BOTH MECHANICAL ROOMS 2017 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By lcrespo Date 2020-12-21 Time 12:21 Rev Time 0.00
Received By lcrespo Date 2020-12-21 Time 12:21 Sent To  
Notes
2020-12-21 12:22:4112/21/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-12-14 Cont ID  
Sent By lcrespo Date 2020-12-14 Time 16:15 Rev Time 0.00
Received By lcrespo Date 2020-12-14 Time 14:30 Sent To  
Notes
2020-12-14 16:16:0012/14/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE LIFE SAFETY L-1 PLAN, IT SHOWS A DOUBLE
 DRINKING FOUNTAIN, AND ON MP-1 AND E-1, IT SHOWS A
 SINGLE PLEASE CORRECT, AND PLEASE SHOW THE FORWARD
 APPROACH AS IT IS A HIGH AND LOW PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. PLEASE SHOW THE CLEAR FLOOR SPACE FOR LAV ON THE
 CORRECT SIDE. THE LAV WAS MOVED AND NOT THE CLEAR FLOOR
 SPACE LAYOUT PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE UPDATE THE PROVISOS THAT ARE APPROVED IN
 VERSION ONE PLANS;
  
 A. TEMPERED WATER DEVICE ON LAV THAT COMPLIES WITH ASSE
 1070 PER THE 2017 FBC SEC. P 607.4.
  
 B. WATER SERVICE SUPPLY AND SHUT OFF VALVES FOR
 DRINKING FOUNTAIN ON ISOMETRIC PER 2017 FBC SEC. P
 306.4.
  
 C. HAMMER ARRESTORS FOR DRINKING FOUNTAIN PER THE 2017
 FBCSE. 604.9.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-04 Cont ID  
Sent By jwitmer Date 2021-01-04 Time 15:13 Rev Time 0.00
Received By jwitmer Date 2021-01-04 Time 14:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-12-16 Cont ID  
Sent By jwitmer Date 2020-12-16 Time 12:32 Rev Time  
Received By jwitmer Date 2020-12-16 Time 11:30 Sent To  
Notes
2020-12-16 12:31:11THE SUBMITTED SHOP DRAWING BY THOMAS J. TWOMEY P. E.
 NONE OF THE 11 PAGES ARE SIGNED AND SEALED.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS (DIGITAL SIGNATURES),
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
  