Plan Review Details - Permit 20110196
Plan Review Stops For Permit 20110196
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 16:27 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-12-11 Cont ID  
Sent By cthroop Date 2020-12-11 Time 15:53 Rev Time 0.00
Received By cthroop Date 2020-12-11 Time 15:10 Sent To  
Notes
2020-12-11 15:54:38PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. CLEARANCE TO BUILDING OPENINGS IS 10 FEET PER
 R303.5.1. CORRECTED
  
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2. PROVIDE A COPY OF THE PROPOSED GENERATOR
 SPECIFICATIONS. (NOT ADDRESSED)
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-19 Cont ID  
Sent By cthroop Date 2020-11-19 Time 11:42 Rev Time 0.00
Received By cthroop Date 2020-11-19 Time 10:57 Sent To  
Notes
2020-11-19 11:47:08PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CLEARANCE TO BUILDING OPENINGS IS 10 FEET PER
 R303.5.1.
  
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 2. PROVIDE A COPY OF THE PROPOSED GENERATOR
 SPECIFICATIONS.
  
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 10:19 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 10:19 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-01-05 Cont ID  
Sent By tklarge Date 2021-01-05 Time 05:14 Rev Time 0.00
Received By tklarge Date 2021-01-04 Time 10:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 15:59 Rev Time 0.00
Received By medwards Date 2020-11-23 Time 15:19 Sent To  
Notes
2020-11-23 16:00:031ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110196
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE GENERATOR.
 FBC 107.2.1
  
 2) THE GAS RISER DIAGRAM MUST INCLUDE THE NAME OF OWNER
 AND ADDRESS OF PROPERTY. IT MUST ALSO INCLUDE THE
 PRINTED NAME AND SIGNATURE OF THE PERSON THAT DREW THE
 GAS RISER DIAGRAM.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 3) PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 4) SHOW DRIP LEG ON EQUIPMENT INSTALLED PER THE 2017
 FBC RES. SEC. G2419.2 OR 2017 FBC FG 408.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 16:27 Rev Time 0.00
Received By cthroop Date 2021-01-06 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-01-05 Cont ID  
Sent By tklarge Date 2021-01-05 Time 05:14 Rev Time 0.00
Received By tklarge Date 2020-12-04 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-24 Cont ID  
Sent By lmarchan Date 2020-11-24 Time 14:35 Rev Time 0.00
Received By lmarchan Date 2020-11-06 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-01-04 Cont ID  
Sent By abelisle Date 2021-01-04 Time 17:58 Rev Time 0.00
Received By abelisle Date 2021-01-04 Time 17:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2020-11-23 Cont ID  
Sent By medwards Date 2020-11-23 Time 16:05 Rev Time 0.00
Received By medwards Date 2020-11-23 Time 16:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-01-12 Cont ID  
Sent By cthroop Date 2021-01-12 Time 16:27 Rev Time 0.00
Received By cthroop Date 2021-01-12 Time 15:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-01-05 Cont ID  
Sent By tklarge Date 2021-01-05 Time 05:14 Rev Time 0.00
Received By tklarge Date 2021-01-05 Time 05:14 Sent To  
Notes
2020-12-11 15:52:55ENGINEERS SIGNATURE ON CONCRETE PAD VALID PER FBPE
 EMERGENCY RULE. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-19 Cont ID  
Sent By cthroop Date 2020-11-19 Time 11:47 Rev Time 0.00
Received By cthroop Date 2020-11-19 Time 11:47 Sent To  
Notes
2020-11-19 11:48:21ENGINEER'S SIGNATURE VALID PER FBPE RULE 61G15 ER20.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-11-24 Cont ID  
Sent By kalexand Date 2020-11-24 Time 08:17 Rev Time 0.00
Received By kalexand Date 2020-11-24 Time 08:17 Sent To I
Notes
***NONE***