2020-11-09 12:06:26 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20110190 |
| 11/9/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| G2413.4.2 FBC RES. |
| |
| 2) LIST THE PIPE SIZING TABLES FOR THE 2 PSI GALVANIZED |
| AND PE- SEE TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| |
| 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| |
| 4) CORRECT THE NOTE ON THE SURVEY TO INDICATE THE |
| MINIMUM 10 FT. CLEARANCE FOR THE GNERATOR EXHAUST TO |
| AIR INTAKES AND WINDOW AND DOOR OPENINGS INTO THE |
| BUILDING- SECTION R303.5.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |