Plan Review Details - Permit 20110156
Plan Review Stops For Permit 20110156
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By cthroop Date 2020-12-21 Time 17:07 Rev Time 0.00
Received By cthroop Date 2020-12-21 Time 16:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-11-17 Cont ID  
Sent By cthroop Date 2020-11-17 Time 13:31 Rev Time 0.00
Received By cthroop Date 2020-11-17 Time 13:11 Sent To  
Notes
2020-11-17 13:49:47PLAN REVIEW GENERATOR / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1) PROVIDE STRUCTURAL DETAIL OF GENERATOR PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2) STRUCTURAL PAD DETAIL SHALL BE SIGNED BY DESIGNER.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
 3) ADJUST THE LOCATION OF THE GENERATOR ON THE SURVEY.
 GENERATOR SHALL BE LOCATED PER R303.5.1.
 R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 PROVIDE SETBACK DIMENSIONS TO PROPERTY LINES, BUILDING
 AND BUILDING OPENINGS PER PER 107.2 CONSTRUCTION
 DOCUMENTS.
  
 4) PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). TOP OF GENERATOR PAD SHALL BE AT OR ABOVE 8.0
 FEET NAVD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-12-23 Cont ID  
Sent By equinone Date 2020-12-23 Time 09:00 Rev Time 0.00
Received By equinone Date 2020-12-23 Time 09:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 15:34 Rev Time 0.00
Received By equinone Date 2020-11-20 Time 15:34 Sent To  
Notes
2020-11-20 15:42:18CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE PROVIDE SPECS FOR TRANSFER SWITCH AND SHOW ON
 RISER DIAGRAM. TRANSFER SWITCH MUST BE LISTED FOR
 EMERGENCY POWER SYSTEM USE. PLEASE CONFIRM THAT THERE
 IS A SERVICE RATED DISCONNECT AHEAD OF TRANSFER SWITCH.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-23 Cont ID  
Sent By equinone Date 2020-12-23 Time 09:00 Rev Time 0.00
Received By equinone Date 2020-12-18 Time 15:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-11-20 Cont ID  
Sent By equinone Date 2020-11-20 Time 15:35 Rev Time 0.00
Received By equinone Date 2020-11-05 Time 08:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By cthroop Date 2020-12-21 Time 17:07 Rev Time 0.00
Received By cthroop Date 2020-12-21 Time 16:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-11-20 Cont ID  
Sent By cthroop Date 2020-11-20 Time 14:56 Rev Time 0.00
Received By cthroop Date 2020-11-20 Time 14:56 Sent To  
Notes
2020-11-20 15:00:19PLAN REVIEW / SIGNATURES
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NO SIGNATURE REVIEW PERFORMED AT THIS TIME. SUBMIT
 STRUCTURAL PAD DESIGN PER BLDG REVIEW COMMENTS.
  
 FOR ENGINEERED PRE-CAST PAD
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
 FOR CONTRACTOR DESIGNED SLAB ON GRADE
  
  
 1. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE
 THEIR PRINTED NAME AND SIGNATURE ON PLAN SHEETS UNDER
 THEIR AUTHORITY ?
 2017 WPB AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, SECTION 107.2.1.
  
 2. EITHER UPLOAD DOCUMENTS VIA THE PROJECTDOX PORTAL
 WITH SIGNATURE OF DESIGNER AS APPLICABLE; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT OR DROP
 OFF (OR MAIL) ONE PAPER ORIGINAL WITH CONTRACTORS
 SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-12-21 Cont ID  
Sent By fmittner Date 2020-12-21 Time 10:37 Rev Time 0.00
Received By fmittner Date 2020-12-21 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-12-10 Cont ID  
Sent By kalexand Date 2020-12-10 Time 11:53 Rev Time 0.00
Received By kalexand Date 2020-12-10 Time 11:53 Sent To I
Notes
2020-12-10 11:59:00ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW:
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. GENERATOR EQUIPMENT ENCROACHES TOO FAR INTO REQUIRED
 SETBACK. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 2. INDICATE SETBACKS FROM ALL ADJACENT PROPOERTY LINES.
  
 PURSUANT TO ZLDR SEC. 94-82 THE SETBACKS FOR THIS
 PROPERTY ARE AS FOLLOWS:
 REAR: 15 FEET, OR 10 PERCENT OF THE LOT DEPTH,
 WHICHEVER IS LESS.
 SIDE MINIMUM (ONE SIDE ONLY):
 --FOR LOTS UP TO 9,999 SQUARE FEET: 5 FEET;
 --FOR LOTS 10,000 SQUARE FEET AND OVER: 10 FEET.
 SIDE MINIMUM CUMULATIVE (BOTH SIDES):
 --FOR LOTS UP TO 7,499 SQUARE FEET: 15 FEET;
 --FOR LOTS 7,500 TO 9,999 SQUARE FEET: 20 FEET;
 --FOR LOTS 10,000 SQUARE FEET AND OVER: 25 FEET.
  
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD
 LIKE TO RESUBMIT ELECTRONICALLY, EMAIL
 [email protected] AND REQUEST TO HAVE YOUR
 PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOG
 IN INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL.
 PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU
 ARE FINISHED UPLOADING.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 KIZZI ALEXANDRE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  